40
10.7.30 Pump data (4.3.19.1)
Fig. 57
Pump data
Description
In this menu it is possible to enter data describing the
performance curve of pumps in order to optimise the operation.
Setting range
The following data can be entered:
•
Nominal flow rate Q
nom
in m³/h
•
Nominal head H
nom
in metres
•
Max. head H
max
in metres.
Setting via control panel
1. Mark the
Settings
menu with
.
2. Mark
Secondary functions
with
or
and press
.
3. Mark
Pump curve data
with
or
and press
.
4. Mark
Entry of pump data
and press
.
5. Mark
Nominal flow rate Q
nom
with
or
.
6. Set the value with
or
and save with
.
7. Mark
Nominal head H
nom
with
or
.
8. Set the value with
or
and save with
.
9. Mark
Max. head H
max
with
or
.
10.Set the value with
or
and save with
.
10.7.31 Control source (4.3.20)
Fig. 58
Control source
Description
Hydro MPC can be remote-controlled via an external bus
connection (option), see
. The setpoint and
operating mode are then set via the bus connection.
In this display the control source, CU 351 or the external bus
connection, is selected.
1. Mark the
Settings
menu with
.
2. Mark
Secondary functions
with
or
and press
.
3. Mark
Control source
with
or
and press
.
4. Select the desired control source with
or
and save
with .
Factory setting
The control source is CU 351.
10.7.32 Monitoring functions (4.4)
Fig. 59
Monitoring functions
Description
Hydro MPC has a series of functions that constantly monitor the
operation of the booster set.
The primary purpose of the monitoring functions is to ensure that
faults do not damage pumps or the system connected to the
booster set.
T
M
03
23
46
40
05
Note
This setting is not necessary, as pump curve data
is entered at factory.
TM
03
17
06
27
06
Note
Q
nom
and H
nom
are the rated duty point of the
pumps and usually the duty point with the
highest efficiency.
H
Q
H
max
H
nom
Q
nom
T
M
03
23
42
40
05
TM
03
23
12
40
05
www.motralec.com / [email protected] / 01.39.97.65.10
Содержание BoosterpaQ Hydro MPC
Страница 12: ...12 INSTALLATION AND STARTUP NOTES www motralec com service commercial motralec com 01 39 97 65 10 ...
Страница 54: ...54 Variable frequency drive setting notes www motralec com service commercial motralec com 01 39 97 65 10 ...
Страница 58: ...58 www motralec com service commercial motralec com 01 39 97 65 10 ...