Setting range
The setting range of setpoints for closed-loop control depends on
the range of the primary sensor, see
Open-loop control: 0-100%.
Setting via control panel
1. Mark the
Operation
menu with
.
2. Mark
Setpoints
with
or
and press
.
3. Select the setpoint with
or
.
4. Set the setpoint with
or
and press
.
Factory setting
Setpoint 1 for closed-loop control is a value suitable for the
Hydro MPC in question.
The other setpoints for closed-loop control are 3 bar.
All setpoints for open-loop control are 70%.
10.5.5 Forced control (2.4) + (2.4.1 to 2.4.6)
Fig. 20
Forced control
Description
It is possible to change the operating mode from automatic
operation to one of the manual operating modes.
Auto
The pumps are controlled by the PI controller, ensuring that the
booster set delivers the required performance (pressure).
Manual
The pump is not controlled by the PI controller, but set to one of
the following manual operating modes:
•
Max.
The pump runs at a set maximum speed.
•
Normal
The pump runs at a set speed. (This operating mode can only
be selected for variable-speed pumps.)
•
Min.
The pump runs at a set minimum speed. (This operating mode
can only be selected for variable-speed pumps.)
•
Stop
The pump has been forced to stop.
Pumps in manual operation are not part of the normal pump
cascade and speed control. The manual pumps are a
"disturbance" of the normal control of Hydro MPC.
If one or more pumps are in manual operation, Hydro MPC may
not be able to deliver the set performance.
There are two displays for the function. In the first display the
pump to be set is selected, and in the next display the operating
mode is selected.
Setting range
All pumps can be selected.
Setting via control panel
1. Mark the
Operation
menu with
.
2. Mark
Individual pump control
with
or
and press
.
3. Select the pump with
or
and press
.
10.5.6 Setting of individual operating mode (2.4.1 to 2.4.6)
Fig. 21
Setting of individual operating mode
Description
This display is shown for the individual pumps and makes it
possible to set an operating mode.
Setting range
It is possible to select
Auto
or
Manual
as well as the operating
mode of the pump for manual operation -
Normal
,
Max.
,
Min.
or
Stop
. For mains-operated pumps only
Max.
or
Stop
can be
selected.
Setting via control panel
1. Mark the
Operation
menu with
.
2. Mark
Individual pump control
with
or
and press
.
3. Select the pump with
or
and press
.
4. Mark
Auto
or
Manual
with
or
and press
.
5.
Manual:
Select the operating mode with
or
and press
.
6.
Normal:
Mark
Setpoint
with
or
.
Set the speed of the variable-speed pump with
or
and press
.
Factory setting
Auto
.
TM
03
22
75
40
05
TM
0
3
2
281
4
005
www.motralec.com / [email protected] / 01.39.97.65.10
Содержание BoosterpaQ Hydro MPC
Страница 12: ...12 INSTALLATION AND STARTUP NOTES www motralec com service commercial motralec com 01 39 97 65 10 ...
Страница 54: ...54 Variable frequency drive setting notes www motralec com service commercial motralec com 01 39 97 65 10 ...
Страница 58: ...58 www motralec com service commercial motralec com 01 39 97 65 10 ...