38
Setting range
It is possible to select one function in each display:
•
Not used
•
System in operation
•
Alarm, system
•
Warning, system
•
Ready, system
•
Water shortage
•
Min. pressure
•
Max. pressure
•
Pump 1 is running
•
Pump 2 is running
•
Pump 3 is running
•
Pump 4 is running
•
Pump 5 is running
•
Pump 6 is running
•
Alarm, pump 1
•
Alarm, pump 2
•
Alarm, pump 3
•
Alarm, pump 4
•
Alarm, pump 5
•
Alarm, pump 6.
Setting via control panel
1. Mark the
Settings
menu with
.
2. Mark
Secondary functions
with or
and press
.
3. Mark
Digital outputs
with
or
and press
.
4. Select the digital output with
or
and press
.
5. Mark the desired function with
or
and activate it with
.
The activation is indicated by a check mark in the box.
Factory setting
10.7.25 Min., max. and user-defined duty (4.3.14)
Fig. 52
Min., max. and user-defined duty
Description
Hydro MPC is usually controlled in a closed loop to maintain a
discharge pressure. In certain periods it may be necessary to let
the booster set run in open loop at a set pump performance.
Setting range
The CU 351 makes it possible to change between three operating
modes:
1.
2.
3.
10.7.26 Min. duty (4.3.14.1)
Fig. 53
Min. duty
Description
In all booster sets apart from Hydro MPC-S, min. duty is only
possible for variable-speed pumps. In Hydro MPC-S systems only
the number of pumps running at 100% speed can be set.
Setting range
•
Number of pumps in operation.
•
Speed as percentage (25 to 100%) for variable-speed pumps.
Setting via control panel
1. Mark the
Settings
menu with
.
2. Mark
Secondary functions
with
or
and press
.
3. Mark
Min., max. and user-defined duty
with
or
and
press .
4. Mark
Min. duty
with
or
and press
.
5. Mark
Number of pumps in operation
with
or
.
6. Set the number with
or
and save with
.
7. Mark
Speed
with
or
.
8. Set the value with
or
and save with
.
Factory setting
Digital output
Function
DO1 (CU 351) [72]
Alarm, system
DO2 (CU 351) [75]
Operation, system
T
M
03
23
51
40
05
Note
For each of these modes, the number of
operating pumps and the pump performance
(speed) can be set.
T
M
03
2
3
54
40
05
Number of pumps in operation during min. duty:
1
Speed as percentage for variable-speed pumps:
70
www.motralec.com / [email protected] / 01.39.97.65.10
Содержание BoosterpaQ Hydro MPC
Страница 12: ...12 INSTALLATION AND STARTUP NOTES www motralec com service commercial motralec com 01 39 97 65 10 ...
Страница 54: ...54 Variable frequency drive setting notes www motralec com service commercial motralec com 01 39 97 65 10 ...
Страница 58: ...58 www motralec com service commercial motralec com 01 39 97 65 10 ...