32
Description
This function ensures a delay between the starting/stopping of
one pump and the starting/stopping of another pump.
The purpose of the function is to prevent constant starting and
stopping of pumps.
Setting range
From 1 to 300 seconds.
Setting via control panel
1. Mark the
Settings
menu with
.
2. Mark
Pump cascade control
with
or
and press
.
3. Mark
Min. time between start/stop
with
or
and
press .
4. Mark
Min. time between start/stop
with
or
and
press .
5. Set the required minimum time with
or
and save with
.
Factory setting
The minimum time between start/stop of pumps has been set to:
10.7.12 Max. number of starts/hour (4.2.1)
Fig. 38
Max. number of starts/hour
Description
This function limits the number of pump starts and stops per hour
for the complete system. It reduces noise emission and improves
the comfort of booster sets with mains-operated pumps.
Each time a pump starts or stops, the controller calculates when
the next pump is allowed to start/stop in order not to exceed the
permissible number of starts per hour.
The function always allows pumps to be started to meet the
requirement, but pump stops will be delayed, if needed, in order
not to exceed the permissible number of starts/stops per hour.
The time between pump starts must be between the minimum
time between start/stop, see display
, and 3600/n, n being
the set number of starts per hour.
Setting range
1 to 253 starts per hour.
Setting via control panel
1. Mark the
Settings
menu with
.
2. Mark
Pump cascade control
with
or
and press
.
3. Mark
Max. number of starts/hour
with
or
and press
.
4. Mark
Max. number of starts/hour
with
or
and press
.
5. Set the permissible number of starts per hour with
or
and save with
.
Factory setting
10.7.13 Standby pumps (4.2.3)
Fig. 39
Standby pumps
Description
This function makes it possible to limit the maximum performance
of the Hydro MPC, by selecting one or more pumps as standby
pumps.
If a three-pump system has one standby pump, maximum two
pumps are allowed to be in operation at a time.
If one of the two pumps in operation has a fault and is switched
off, the standby pump will be started. The performance of the
booster set is thus not reduced.
The status as standby pump alternates between all pumps.
Setting range
The number of possible standby pumps in a Hydro MPC booster
set is equal to the total number of pumps in the system minus 1.
Setting via control panel
1. Mark the
Settings
menu with
.
2. Mark
Pump cascade control
with
or
and press
.
3. Mark
Standby pumps
with
or
and press
.
4. Select the number of standby pumps with
or
and
save with
.
Factory setting
The number of standby pumps is set to 0, i.e. function is
deactivated.
Hydro MPC-E and -EF: 1 second
≤
15 HP 240 sec.
Other variants:
> 20 HP 360 sec.
TM
03
23
67
40
05
Hydro MPC-E and -EF: 200 starts per hour
≤
15 HP.
Other variants:
100 starts per hour > 20 HP
T
M
03
23
66
40
0
5
www.motralec.com / [email protected] / 01.39.97.65.10
Содержание BoosterpaQ Hydro MPC
Страница 12: ...12 INSTALLATION AND STARTUP NOTES www motralec com service commercial motralec com 01 39 97 65 10 ...
Страница 54: ...54 Variable frequency drive setting notes www motralec com service commercial motralec com 01 39 97 65 10 ...
Страница 58: ...58 www motralec com service commercial motralec com 01 39 97 65 10 ...