Commissioning
44 | 76
Should, after some time, "raw water shut-off valve at connection block still
closed" appear in the display, open the shut-off valve for raw water.
14.
Open the soft water shut-off valve.
15.
Confirm with ▼.
16.
Check the water hardness on exchanger 1 as described in chapter 7.7.
» Upon confirmation with ENTER, exchanger 1 is put out of operation and exchanger
2 is put into operation.
17.
Check the water hardness on exchanger 2 as described in chapter 7.7.
18.
Confirm with ▼.
With these tests, the function of the exchangers is checked. The water
sample must have a hardness of less than 1 °dH.
19.
Use ▲ and ▼ to set the required value for the soft water hardness.
• Recommendation for Germany: Soft water hardness 3 - 5 °dH.
• Recommendation for Austria: Soft water hardness at least 8.4 °dH.
Take the maximum admissible sodium concentration of your drinking water
into consideration (refer to chapter 13.2).
20.
Press ENTER to start the test regenerations.
» The remaining time will be indicated in the display. The remaining time for the
regeneration of both exchangers is counted down.
The test regenerations take approx. 33 minutes for both exchangers.
6.2
Handing over the product to the owner/user
Proceed as follows during the handover of the product:
1.
Inform the owner-user how the water softener works.
2.
Hand over all documents to the owner/user for keeping.
3.
Use the manual to brief the owner/user, and answer any questions.
4.
Inform the owner/user about the need for inspections and maintenance.
5.
Inform the owner/user about the influence of the water hardness on the dosage
rate of detergents and cleaning agents.
6.
Advise the owner/user of the adsorber replacement interval.