Page 13
OCF 6.1 Open Channel Flow Monitor
CALIBRATION
Press
to
Calibration
and
to enter. Use
or
to position
before
each menu item and
to enter. When settings are completed press
to
store and return to the Calibration menu.
Min Range
Distance from the sensor face to highest expected level.
Max Range
Distance from sensor to Zero level.
MaxVol
For Volume and HRT mode only. Enter the maximum
volume of the vertical or horizontal tank.
Mode
Shows the Mode set in the Units/Mode menu. Read-only.
20mA
Sets the 20mA output value, in engineering units set in the
Units/Mode menu.
4mA
Sets the 4mA output value, in engineering units set in the
Units/Mode menu.
Offset
Sets an Offset value, in engineering units set in the
Units/Mode menu. This parameter can be used to be a one-
point adjustment to the Range reading.
LOE Time
Press
and
or
to change the number of seconds
without receiving an echo before the OCF 6.1 displays ECHO
LOSS, and Control relays change state as calibrated under
Relay Parameters.
Factory default is 30 seconds and is recommended for most
applications, Minimum is 1 second and maximum is 99
seconds.
- - Ca l i b r a t i o n - - - - - - -
Ra n g e
Ma x
3 2 . 0 0 f t
Mi n
1 . 0 0 f t
Mo d e
Fl o w
2 0 mA
2 8 . 8 9 0 L / s
4 mA
1 8 . 8 7 8 L / s
Of f s e t
0 . 0 0 f t
L OE T i me
3 0 s e c
Da mp i n g
Mo d e
F I R
Pe r c e n t
1 0 %
Wi n d o w
0 . 0 8 f t
Mi n F l o w
0 . 0 0 L / s