Page 13
AVFM 6.1 Area-Velocity Flow Meter
CALIBRATION
Range
Max
Only shown when the level sensor used is a through-air PZ
type. Max range should be set as the distance from the face of
the PZ sensor to the zero level reference point of the
pipe/channel it is installed above. See drawing below.
Min
Only shown when the level sensor used is a through-air PZ
type. Min range should be set as the distance from the face of
the PZ sensor to the maximum water level of the pipe/channel
it is installed above. The water in the pipe/channel should get
no closer than 8 inches for a PZ15-LP sensor type. See
drawing below.
SUNSCREEN
SENSOR
MaxRg
Range
MinRg > dead band
Level
Max
For QZ02L (submersible, default) level sensor, set the
maximum height the level should reach in the system, in units
configured in the Units/Mode menu. If a Round pipe is
selected in the Channel Setup menu, then this value should be
set to the same value as the inside diameter.
Min
For QZ02L (submersible, default) level sensor, set the
minimum height the level should reach in the system, in units
configured in the Units/Mode menu. Minimum level for the
QZ02L sensor is 1 inch, however, this value could be set to a
larger value if you want to ignore levels greater than 1 inch.
20mA
Set the 20mA value for the level analog output, in units
configured in the Units/Mode menu.
--Calibration-------
Range
Max
180.00 in
Min
8.00 in
Level
Max
180.00 in
Min
1.00 in
20mA
180.00 in
4mA
0.00 in
Velocity
20mA
10.00 ft/s
4mA
0.00 ft/s
Flow
Min
0.00 gal/m
20mA
500.00 gal/m
4mA
0.00 gal/m
Lvl Offset
0.00 in
Signal Cutoff
10 %
Damping
Velocity
10 %
Level
10 %
LOE Time
30 sec
Cal Constant
1.000
Содержание AVFM 6.1
Страница 2: ...Note This page has been left blank intentionally ...
Страница 28: ...Page 28 AVFM 6 1 Area Velocity Flow Meter ...
Страница 34: ...Page 34 AVFM 6 1 Area Velocity Flow Meter Resistance vs Temperature ...
Страница 40: ...Page 40 AVFM 6 1 Area Velocity Flow Meter SS PIPE MOUNTING BAND OPTION VSJ ...
Страница 61: ...Page 61 AVFM 6 1 Area Velocity Flow Meter Dual Non Contacting Sensor Configuration ...