Page 10
AVFM 6.1 Area-Velocity Flow Meter
--Status------------
Level
0.00 ft
Velocity
0.00ft/s
Flow
0.000 ft/s
Min Flow
0.000USG
Signal Strength
0%
Signal Cutoff
5%
E
cho Confidence 100%
STATUS (cont.)
Echo Confidence
Displays the confidence of level measurement received
from the QZ02L submerged sensor, or PZ15 level
sensor, on a 0-100% scale. This value is a reflection of
the percent of echoes received from pulses. Example: If
8 pulses are sent from the level sensor and only 4
echoes are received, Echo Confidence will report 50%.
This does not mean that the level is inaccurate, but
instead means the level reading could be susceptible to
a loss of reading should the conditions causing missed
pulses gets worse. Like an increase in solids or bubbles
in the flow steam.
24 HR LOG
Press
from the MAIN display to view a formatted flow report from instruments
with a built-in data logger. Press
to pan through
Flow
,
Velocity
and
Level
summaries. Press
to scroll down one day or repeatedly to scroll to a
specific date. Up to 365 days can be stored for Flow, Level, and Velocity. Newest
date will overwrite the oldest. Press
to return to the main display.
Inserting a USB drive into the meter while on this screen will transfer 24 HR Log
data to the USB drive in .csv format.
PASSWORD
The Password (a number from 0000 to 9999) prevents unauthorized access to the
Calibration menu.
From the Main Display press the
key to get to
Password
. Factory default
password is 0000 and if it has not been changed, this screen will be bypassed
completely.
A new password can be stored by going to the
Special Functions New
Password
menu.
If a user password is required, press
to place the cursor under the first digit and
or
to set the number, then
to the second digit, etc. Press
or
to
proceed to the Menu Selections screen.
Содержание AVFM 6.1
Страница 2: ...Note This page has been left blank intentionally ...
Страница 28: ...Page 28 AVFM 6 1 Area Velocity Flow Meter ...
Страница 34: ...Page 34 AVFM 6 1 Area Velocity Flow Meter Resistance vs Temperature ...
Страница 40: ...Page 40 AVFM 6 1 Area Velocity Flow Meter SS PIPE MOUNTING BAND OPTION VSJ ...
Страница 61: ...Page 61 AVFM 6 1 Area Velocity Flow Meter Dual Non Contacting Sensor Configuration ...