37
VersiVent Energy Recovery Ventilator
Troubleshooting – Refrigeration Circuit
Symptom
Possible Cause
Corrective Action
Compressor
starts but
cuts out on
high pressure
switch
High pressure
activates at
600 PSIG
Refrigerant overcharge.
Check pressures, charge by subcooling.
Condenser fan motor defective.
Check fan motor.
Condenser coil inlet obstructed or dirty.
Check coil and clearances. Clean coil if necessary.
Air or non-condensables in system.
Check high side equalized pressures, check thermal expansion
valves.
Defective high pressure switch.
Replace.
Restriction in discharge or liquid line.
Check refrigerant line pressures, check thermal expansion
valves, replace any defective component.
Condensing fan relay not pulling in.
Replace.
Compressor
cuts out
on thermal
overload
Low voltage.
Check voltage.
Sustained high discharge pressure.
Check running amperage and conditions described under “low
suction pressure” symptoms.
High suction and discharge pressures.
Check thermal expansion valve setting, check for air in system.
Check air conditions and cfm.
Defective compressor overload.
If compressor is hot, allow compressor to cool for two hours.
Recheck for open circuit.
Improper refrigerant charge.
Check subcooling.
Improperly wired.
Review wiring schematics.
Loose wiring.
Check all connections.
Defective start relay.
Replace relay.
Motor windings damaged.
Verify amp draw.
Compressor
hums, but will
not start
Improperly wired.
Review wiring schematics.
Low line voltage.
Check voltage.
Loose wiring.
Check all connections.
Defective start relay.
Replace relay.
Motor winding damaged.
Verify amp draws. Replace compressor if necessary.
Internal compressor mechanical damage.
Replace.
Compressor
noisy or
vibrating
Refrigerant overcharge.
Check pressures and subcooling.
Liquid floodback.
Check thermal expansion valve setting. Check for refrigerant
overcharge.
Tubing rattle.
Dampen tubing vibration by taping or clamping. Carefully bend
tubing away from contact where possible.
Scroll compressor rotating in reverse.
(3-phase)
Check high and low side pressures during operation to confirm.
Rewire for opposite rotation.
Damaged compressor.
Replace the compressor.
Improper mounting on unit base.
Check that compressor is properly isolated and mounting bolts
are tight.
Always have a completed Pre-Start-Up Checklist and Start-Up Checklist prior to requesting parts or service
information.