11
VersiVent Energy Recovery Ventilator
1 Fan
Wheel
Dia.
1 Fan
Wheel
Dia.
Rota
tio
n
Rota
tio
n
R
ot
ation
R
ot
ation
Length of Straight Duct
GOOD
POOR
GOOD
POOR
GOOD
POOR
Turning
Vanes
Turning
Vanes
SYSTEM EFFECT FACTOR CURVES
FPM X 100
OUTLET VELOCITY
0 5 10 15 20 25 30 35 40 45
1.2
1.0
0.8
0.6
0.4
0.2
0.0
S
TA
TIC PRESSURE LOSS
CUR
VE
1
CUR
VE
2
CUR
VE
3
CUR
VE 4
Ductwork Connections
Supply Fan
The supply fan in this unit is a plenum style fan. The
discharge opening dimensions are provided. For proper
fan performance, match the duct size to the dimensions
listed. Installation of all ducts should be done in
accordance with SMACNA.
Exhaust Fan
The exhaust fan in this unit is a forward-curved fan.
Good and poor fan-to-duct connections are shown.
Airflow out of the fan should be
directed straight or curved the
same direction as the
fan wheel rotates. Poor
duct installation will
result in low airflow and
other system effects.
Supply Fan Discharge Opening Dimensions
Unit
Supply Air
Discharge Location
Length of
Straight Duct
(Supply Fan)
Top
End
Bottom
VER-45 38.5 x 30 41.8 x 27
*
48
VER-65
50 x 31
50 x 31
*
60
VER-90
62 x 34
59.7 x 35
*
60
All dimensions shown in inches.
*
See diagram in Recommended Roof Openings section for the
Bottom Discharge opening sizes.
Recommended Exhaust Fan Discharge Duct Size
Unit
Duct Size
Exhaust
Blower Size
Length of
Straight Duct
(Exhaust Fan)
VER-45
20 x 20
12
48
VER-65
28 x 28
15
60
VER-90
32 x 32
18
60
All dimensions shown in inches.
• Recommended duct sizes are based on velocities across the
cfm range of each model at approximately 800 feet per minute
(FPM) at minimum airflow and up to 1600 fpm at maximum
airflow. Recommended duct sizes are only intended to be a
guide and may not satisfy the requirements of the project. Refer
to plans for appropriate job specific duct size and/or velocity
limitations.
• Straight duct lengths were calculated based on 100% effective
duct length requirements as prescribed in AMCA Publication
201. Calculated values have been rounded up to nearest foot.
1 Fan
Wheel
Dia.
1 Fan
Wheel
Dia.
Rota
tio
n
Rota
tio
n
R
ot
ation
R
ot
ation
Length of Straight Duct
GOOD
POOR
GOOD
POOR
GOOD
POOR
Turning
Vanes
Turning
Vanes
SYSTEM EFFECT FACTOR CURVES
FPM X 100
OUTLET VELOCITY
0 5 10 15 20 25 30 35 40 45
1.2
1.0
0.8
0.6
0.4
0.2
0.0
S
TA
TIC PRESSURE LOSS
CUR
VE
1
CUR
VE
2
CUR
VE
3
CUR