Pellet burner GP 45 IV 17
5. MOUNTING AND INSTALLATION.
5.1.
MAIN REQUIREMENTS FOR INSTALLATION OF AUTOMATED WOOD PELLET
BURNER FROM SERIES “GP 45 IV”.
The burner has to be positioned in a way that provides enough free space for its
servicing and cleaning;
The burner has to be mounted to an appliance (hot water boiler, other heat energy
consumer) in a way that provides availability for easy servicing and cleaning from the
ash residues;
It is not allowed to mount the burner to appliance that is installed in living premises,
including corridors;
The burner mounting to an appliance must be performed by a qualified technician
only;
The installation and maintenance of the automated pellet burner must be performed
by specialized companies, which have acquired legal rights for such activities;
The automated pellet burner from series “GP” must be connected to the electrical
supply system by an authorized electrician only;
Before initialization of the burner in operation the heat energy consuming devices
working order must be ensured;
The burner servicing/handling must be performed by adult persons only, which are
well familiar with the appliance operation manual book.
The burner mounting to a hot water boiler (consuming appliance) has to be done
by bolts (or studs) and nuts. It is required to fasten the burner to the appliance
with the use of a tool (for example wrench). It is not allowed to fasten it by hand.
The mounting and removal of the burner must be performed by an eligible person
equipped with proper tools.
5.2.
BURNER INSTALLATION.
The burner installation to an appliance requires preliminary prepared project, complying with
the acting norms and regulations.
In case the heat consuming appliance is a hot water boiler, then the requirements of
standard BNS EN 303-5/2000 – “Central heating hot water boilers - part 5: Central
heating solid fuel hot water boilers with nominal heating output of maximum 300 kW –
terminology, requirements, tests and notation” must be observed;
In case the heat consuming appliance is not a hot water boiler, then the prescribed
standard requirements for the relevant appliance type, must be observed;
Fire safety requirements;
To the electrical supply network - BNS EN 60335-1/1997 – “Safety of domestic
electrical devices”
Observe the chimney draught requirements, presented in the hot water boiler’s
technical data table, when installing the burner to the boiler.