Super Free Match
Service Manual
INSTALLATION
82
4.2.12
Installation of the Drain Pipe
1)
The diameter of the drain pipe should be larger or equal to that of the refrigerant pipe (PVC pipe, outer
dimater:25mm, wall thickness
≥
1.5mm.
2)
The drain pipe should be as short as possible and with at least a 1/100 degree of slope to avoid forming
air pockets.
3)
If the proper degree of slope of the drain pipe is not allowed, a lift pipe should be installed.
4)
A distance 1-1.5m should be kept between the hangers to avoid the drain hose making a turn.
Right
Wrong
5)
Insert the drain hose into the drain hole and tighten it with clamps.
6)
Wrap the clamps with large amount of sponge for thermal insulation.
7)
The drain hose inside the room also should be insulated.
4.2.13
Precautions for the Lift Pipe
The installation height of the lift pipe should be less than 850mm. It is recommended to set an inclination
angle 1°
~
2
°
for the lift pipe toward the drainage direction. If the lift pipe and the unit form a right angle, the
height of the lift pipe must be less than 800mm.
Содержание R410A
Страница 1: ...SUPER FREE MATCH SERIES SERVICE MANUAL T1 R410A 50Hz GC201306 CENTRAL AIR CONDITIONERS ...
Страница 5: ...Super Free Match Service Manual PRODUCT 1 PRODUCT ...
Страница 28: ...Super Free Match Service Manual CONTROL 24 CONTROL ...
Страница 29: ...Super Free Match Service Manual CONTROL 25 Control 1 OPERATION FLOWCHART ...
Страница 31: ...Super Free Match Service Manual CONTROL 27 1 2 Heating Operation ...
Страница 66: ...Super Free Match Service Manual INSTALLATION 62 INSTALLATION ...
Страница 97: ...Super Free Match Service Manual INSTALLATION 93 ...
Страница 118: ...Super Free Match Service Manual INSTALLATION 114 7 Electrical Wiring Work 7 1 Wiring Connection Precept 1 Precept 2 ...
Страница 129: ...Super Free Match Service Manual MAINTENANCE N 125 MAINTENANCE ...
Страница 152: ...Super Free Match Service Manual MAINTENANCE 148 5 Console GEH 09 AA K3DNA1C I GEH 12 AA K3DNA1C I GEH 18 AA K3DNA1C I ...
Страница 153: ...Super Free Match Service Manual MAINTENANCE N 149 4 2 3 BU module FXB3A K ...
Страница 154: ...Super Free Match Service Manual MAINTENANCE 150 FXB5A K ...
Страница 203: ...Super Free Match Service Manual MAINTENANCE N 199 7 2 3 Cassette type GKH 12 BA K3DNA2A I GKH 18 BA K3DNA2A I ...
Страница 217: ...JF00301896 ...