Super Free Match
Service Manual
INSTALLATION
124
9
Installation of Protective Layer on Connection Pipe
1)
The refrigerant pipes should be insulated by the heat insulation material and plastic tape in order to
prevent water condensation and leakage.
2)
Do not use the foam on the branch pipe as the material for heat insulation.
The heat insulation material: Heat resistance to 100 or more;
℃
Thickness of 9mm or more.
3)
The joints of the system should be wrapped with the heat insulation material and no gap is allowed on the
joint of the system, as shown in the following figure.
4)
Bundle the refrigerant pipe and transmission line together with tape, and separate them from the drain pipe
to prevent the condensate water overflowing.
5)
Wrap the pipe from the bottom of the outdoor unit to the top of the pipe where it enters the wall. During
the wrapping, the later circle should cover half of the former one.
6)
At intervals of about 1 meter, fix the refrigerant pipes to the wall with brackets, that is, don’t let the unit
withstand the weight of it or float it in the air.
Caution
!
After the pipe is protected well enough, never bend it to form a small angle(
<
90
°
), otherwise it would
crack or break.
Do not wrap the refrigerant pipes very tight, otherwise the insulation effect would be weakened.
Additionally, make sure the drain hose is separated from the refrigerant pipes.
After that, cover the hole on the wall with sealing materials to prevent wind and noise going into the
room.
Содержание R410A
Страница 1: ...SUPER FREE MATCH SERIES SERVICE MANUAL T1 R410A 50Hz GC201306 CENTRAL AIR CONDITIONERS ...
Страница 5: ...Super Free Match Service Manual PRODUCT 1 PRODUCT ...
Страница 28: ...Super Free Match Service Manual CONTROL 24 CONTROL ...
Страница 29: ...Super Free Match Service Manual CONTROL 25 Control 1 OPERATION FLOWCHART ...
Страница 31: ...Super Free Match Service Manual CONTROL 27 1 2 Heating Operation ...
Страница 66: ...Super Free Match Service Manual INSTALLATION 62 INSTALLATION ...
Страница 97: ...Super Free Match Service Manual INSTALLATION 93 ...
Страница 118: ...Super Free Match Service Manual INSTALLATION 114 7 Electrical Wiring Work 7 1 Wiring Connection Precept 1 Precept 2 ...
Страница 129: ...Super Free Match Service Manual MAINTENANCE N 125 MAINTENANCE ...
Страница 152: ...Super Free Match Service Manual MAINTENANCE 148 5 Console GEH 09 AA K3DNA1C I GEH 12 AA K3DNA1C I GEH 18 AA K3DNA1C I ...
Страница 153: ...Super Free Match Service Manual MAINTENANCE N 149 4 2 3 BU module FXB3A K ...
Страница 154: ...Super Free Match Service Manual MAINTENANCE 150 FXB5A K ...
Страница 203: ...Super Free Match Service Manual MAINTENANCE N 199 7 2 3 Cassette type GKH 12 BA K3DNA2A I GKH 18 BA K3DNA2A I ...
Страница 217: ...JF00301896 ...