66
Settings in the burner menu’s below
are based on the boiler using the
Grant fixed angle pellet feed auger
at 45° and an auger motor fixed
speed of 8.1 rpm. Only EN Plus
Grade A1 (BS EN ISO 17225-2)
pellets MUST be used with the Grant
Spira boilers. These pellets must be
bark and sand free AND approved
by Grant UK BEFORE being used
in the Spira boilers. Failure to use
approved pellets will invalidate the
product guarantee.
!
CAUTION
9.7.1.2 ‘menu 2-4- POWER PELLET’
The parameters stored within this folder
are:
•
TIME LOAD MAX:
Time the pellet
feed auger operates to deliver
pellets to the brazier when the
burner is in max flame mode.
Adjusting this time adjusts the
boiler input in max flame, i.e. the
larger the load time, the greater the
input, alternatively the smaller the
load time the lower the input (see
table Section 2.2.1).
Units 000.0 seconds.
Default setting:
5-18 and 6-26 = 25 (2.5 seconds)
Default setting:
9-36 = 65 (6.5 seconds)
•
TIME PAUSE MAX:
Time between
pellet feed auger operations when
the burner is in max flame mode.
Adjusting this time adjusts the
boiler input in max flame, i.e. the
larger the pause time, the lower
the input, alternatively the smaller
the pause time the higher the input
(see table Section 2.2.1).
•
TIME PAUSE MIN:
Time between
pellet feed auger operations in min
flame. Adjusting this time adjusts
the boiler input in min flame, i.e.
the larger the pause time, the lower
the input, alternatively the smaller
the pause time the higher the input
(see table Section 2.2.1).
Units 000.0 seconds.
Default setting 5-18:
0220 (22.0 seconds)
Default setting 6-26:
0140 (14.0 seconds)
Default setting 9-36:
0250 (25 seconds)
9.7.1.3 ‘menu 3-4- CLEAN’
The parameters stored within this folder
are:
•
TIME CLEAN BRAZ:
Total
pellet feed auger run time before
burner brazier cleaning operation
activates. Default setting:
5-18, 6-26 and 9-36 =180 (180
minutes)
•
TIME CLEAN BOILER:
Total
pellet feed auger run time before
boiler cleaning operation activates.
Default setting:
5-18, 6-26 and 9-36 =180 (180
minutes)
•
TIME CLEAN PERIOD:
Time
period boiler cleaning function is
operational once ‘TIME CLEAN
BOILER’ has elapsed. Default
setting:
5-18, 6-26 and 9-36 =60 (60
seconds)
•
FLASH CLEANING:
Setting
determines when the burner brazier
and boiler cleaning operations start
after the ‘TIME CLEAN BRAZ’ and
’TIME CLEAN BOILER’ periods
have elapsed.
1 = Burner firing interrupted and
shut down, brazier and boiler
cleaned immediately auger run
time exceeds ‘
TIME CLEAN
BRAZ
’ and ‘
TIME CLEAN
BOILER
’ periods.
0 = Burner firing not interrupted.
Brazier and boiler cleaned at next
burner shut-down after auger
run time exceeds ‘
TIME CLEAN
BRAZ
’ and ‘
TIME CLEAN
BOILER
’ periods.
Default setting:
5-18, 6-26 and 9-36 = 1.
Consideration must be given to
the demand of the heating system
before adjusting this setting.
For example, if the boiler is to
be installed in a hotel, you may
choose to change this setting to 0
to ensure there is an uninterrupted
supply.
•
HOURS SERVICE:
Time
lapse period before the burner
screen displays ‘SERVICE’.
This is to indicate a service is
now due. Default setting 5-18,
6-26 and 9-36 = 400 (400 hrs).
RESET SERVICE:
to cancel the
‘
SERVICE
’ display on the burner
screen after the boiler has been
serviced. Press button 3 (‘SET’)
followed by button 4 (‘RESET’) five
times to exit the menu.
IT IS ESSENTIAL TO RESET
THE SERVICE DISPLAY AFTER
EACH SERVICE.
9.7.1.4 ‘Menu 4-4- SETUP FAN’
•
POWER MAXIMUM:
Burner fan
speed setting when burner in ‘max’
output mode.
Default setting: 5-18 = 31
Default setting: 6-26 = 36
Default setting: 9-36 = 43
•
POWER MINIMUM:
Burner fan
speed setting when burner in ‘min’
output mode.
Default setting: 5-18 = 16
Default setting: 6-26 = 21
Default setting: 9-36 = 26
•
POWER LIGHTING:
Burner fan
speed setting when burner in
lighting mode.
Default setting:
5-18, 6-26 and 9-36 = 20
•
POWER TEST:
Used to simulate
the burner fan speed for test
purposes only. Once the ‘
POWER
TEST
’ is cancelled from the
screen the burner fan reverts to its
required operational speed.
•
LOAD DEFAULT:
Load factory
default settings. Press button 3 to
activate factory default settings.
9.7.2 ‘MANUFACT’ Menu Folder
‘
MANUFACT
’ displays the
manufacturer folder; this folder cannot
be accessed or modified by the installer
or service engineer.
!
NOTE
Adjusting this setting will also result
in the input during the modulation
period being adjusted as the
modulation input is automatically
calculated on the max/min and load/
pause settings.