83
Note 1 - Is there a permanent
mains live supply connected to the
hopper/boiler?
Check that the permanent live from
the fused spur is correctly connected
to terminal L1 on the 4-way plug at
the rear of the hopper. Also check that
4-way plug is fully pushed into the
socket on the flying lead, at the rear of
the hopper. Refer to Sections 8.4 and
8.5 for further details.
Also check that 5-way plug from hopper
is fully pushed into the socket at the top
left rear of the boiler.
Check that the fused spur is switched
ON and, if necessary, check the fuse
is OK.
Note 2 - Is there a permanent mains
live supply connected to the burner?
Check that the two 7-way plugs are fully
pushed into the two lower sockets on
the left side of the burner.
Also check for permanent live on
terminal L1 of burner plug No.1. Refer
to Figure 8-5.
Note 3 – Has the boiler overheat
thermostat tripped?
Unscrew and remove the black cover
from the overheat reset button on the
boiler control panel to check if boiler
overheat thermostat has tripped. If YES,
go to Section 12.4 for further guidance.
Note 4 – Has the pellet feed tube
thermostat tripped?
Remove top section of burner cover
and disconnect the lead from the pellet
feed tube thermostat. Check the reset
button to see if thermostat has tripped,
if YES, go to Section 12.5 for further
guidance.
Note 5 - Is the combustion chamber
door closed and catch fully
engaged?
The combustion chamber door is fitted
with a safety interlock. Once the door
catch is disengaged all power to the
burner is interrupted. Refer to Section
10.5.2. Check that catch is FULLY
engaged when door is closed.
Note 6 - Is the door microswitch
operational?
Check electrical continuity of door
micro-switch. Replace if faulty. Refer to
Figure 8-5 and 12-5.
12.3 No Screen Display - Boiler will not fire – blank screen
Primary Fault
Secondary follow on checks
BLANK DISPLAY SCREEN
Is electrical
supply switched
on? Is there
power to terminal
L1 on 4-way plug
at rear of hopper?
Yes
No
Yes
Yes
No
No
No
No
No
Are all plugs
correctly fitted?
i.e. the three
burner plugs and
the plug from
hopper to the
boiler?
Has the boiler
overheat stat
tripped?
Unscrew black
cover on control
panel and check
Has the pellet
feed tube stat
tripped? Unclip
and remove lead
from stat and
check
Is the
combustion
chamber door
closed and the
door catch fully
engaged?
Is the power
to terminal L1
of burner plug
No.1?
Check continuity
of burner fuse
on PCB.
Is it OK?
Is the ribbon
cable fitted
correctly to PCB
and back of
display?
Replace burner
PCB does
this rectify the
problem?
Correctly fit
all plugs –
push fully into
sockets
Go to the
‘BOILER
OVERHEAT
STAT’ fault
finding chart
Go to the
‘PELLET FEED
TUBE STAT’
fault finding
chart
Close door and
fully engage
door catch
Is door catch
microswitch
operational?
Replace
faulty door
microswitch?
Replace burner
fuse
Correctly fit
ribbon cable at
both ends
Correctly fit
ribbon cable at
both ends
Yes
No
No
Note 1
Note 3
Note 2
Note 4
Note 5
Note 5
No
Yes
Yes
Yes
Yes
Check electrical
supply to hopper/
boiler
and rectify as
necessary
No
Figure 12-5:
Location of door
microswitch (side panel removed)