THE CONFIGURATION WEB PAGE DOES NOT SHOW ANY OUTPUT?
►
Press ‘F5’ to refresh the web page. Then return to the output panel. If the output still
does not appear, go to the next step.
►
Open a TELNET session:
Telnet <IP address> 9999
Login: root
Password: gtmt
Enter “factory_default”, refresh the web page.
►
If the output still does not appear, remove the server cover. Check the black cables are
connected correctly and switch the switches are configured (see Appendix C
–
MAINTENANCE).
THE DISPLAY SHOWS
“NO TIME CODE!”
►
“NO TIME CODE!”: The device is not synchronised: check your time source.
►
“
no time code!
” followed by the date: if your device receives the time code, check in
the input panel of the configuration web page that “
Enable autonomous mode
” is
unchecked.