AQUA ECOLOGIC | instructions for use, maintenance and installation |
September 2015
15
The walls are made of wood, or in any
case, flammable, or parts that are
flammable.
100
150
170
Concrete wall or a roof
50
100
120
A wall or a brick roof
30
100
120
Table 2:
Insulation thickness for the part of the system that passes through the wall or roof
Above all it is necessary to provide the PERFECT AIRFLOW (draft) in pipes for smoke exhaustion that has
to be free, without any obstacles, such as different narrowing or corners. All displacements of the axis must
have a tilted orbit with a maximum angle of 45 degrees from the vertical, while 30 degrees is the best
solution. This displacement would be best done near the top of the chimney resistant to the wind.
According
to the regulations (the top of the chimney resistant to wind, distance, and placement of
the stove
) the distances shown in Table 3 must be met:
Roof slope: The distance between the ridge and the chimney
cap
Minimum height of the chimney measured at
the top slot (at the back of the chimney)
α
Distance in meters
Height in meters
15
0
less than 1.85 m
greater than 1.85 m
0,50 m above the ridge
1,00 m from the slope of the roof
30
0
less than 1.50 m
less than 1.50 m
0,50 m above the ridge
1,30 m from the slope of the roof
45
0
less than 1.30 m
greater than 1.30 m
0,50 m above the ridge
2,00 m from the slope of the roof
60
0
less than 1.20 m
greater than 1.20 m
0,50 m above the ridge
2,60 m from the slope of the roof
Table 3
However, it is required to provide an initial vertical extension of 1,5 m (minimum) in order to provide
proper discharge of smoke.
4.4 COMBUSTION AIR SUPPLY
(Figure 8)
The air required for combustion, which is taken from the environment, must be supplied by a single
ventilation grill mounted on the outer wall of the room. This will ensure better combustion and thus lower
consumption of pellets. It is not recommended to have outside air drawn directly from the tube, as it will
reduce the efficiency of combustion. A ventilation shaft must always be equipped with one ventilation grille
on the outer side as protection from rain, wind, and insects.
This hole must be made on the outer wall of the room where the stove is located.
The supply of combustion air from the garage, a warehouse for combustible materials, or from a
room where there are risks of fire is prohibited.
Содержание Aqua ECOLOGIC
Страница 32: ...AQUA ECOLOGIC instructions for use maintenance and installation September 2015 32 Figure 12...
Страница 41: ...AQUA ECOLOGIC instructions for use maintenance and installation September 2015 41 service...
Страница 42: ...AQUA ECOLOGIC instructions for use maintenance and installation September 2015 42 service...
Страница 43: ...AQUA ECOLOGIC instructions for use maintenance and installation September 2015 43 service...
Страница 44: ...AQUA ECOLOGIC instructions for use maintenance and installation September 2015 44 service...
Страница 45: ...AQUA ECOLOGIC instructions for use maintenance and installation September 2015 45 service...
Страница 46: ...AQUA ECOLOGIC instructions for use maintenance and installation September 2015 46 service service...
Страница 52: ...AQUA ECOLOGIC instructions for use maintenance and installation September 2015 52...
Страница 53: ...__________ PELLET BOILER ECOLOGIC 30 Instructions for use maintenance and installation June 2015...