Goodman GCV9 Series Скачать руководство пользователя страница 35

35

C

ONDENSATE

 T

RAP

 

AND

 D

RAIN

 S

YSTEM

 (Q

UALIFIED

 S

ERVICER

O

NLY

)

Annually inspect the drain tubes, drain trap, and field-supplied drain
line for proper condensate drainage.  Check drain system for hose
connection tightness, blockage, and leaks.  Clean or repair as nec-
essary.

F

LAME

 S

ENSOR

 (Q

UALIFIED

 S

ERVICER

 O

NLY

)

Under some conditions, the fuel or air supply can create a nearly
invisible coating on the flame sensor.  This coating acts as an insu-
lator causing a drop in the flame sense signal.  If the flame sense
signal drops too low the furnace will not sense flame and will lock
out.  The flame sensor should be carefully cleaned by a qualified
servicer using emery cloth or steel wool.  Following cleaning, the
flame sense signal should be as indicated in the Specifications Sheet.

F

LUE

 P

ASSAGES

 (Q

UALIFIED

 S

ERVICER

 O

NLY

)

The heat exchanger flue passageways should be inspected at the
beginning of each heating season.  If necessary, clean the pas-
sageways as outlined below.

1. Turn OFF the electrical power and gas supply to the  furnace.
2. Disconnect the gas line and remove the burner/ manifold

assembly by removing the screws securing the assembly to
the partition panel.

3. Disconnect the flue pipe system from the induced draft blower.
4. Remove the induced draft blower and, drain and pressure

tap hoses from the recuperator coil front cover.

5. Remove the recuperator coil front cover to expose the coil

tubes and turbulators.

6. Remove the recuperator coil turbulators individually by slowly

pulling each turbulator forward firmly.

7. Clean the recuperator coil tubes using a long handle wire

brush, such as a gun cleaning brush.

8. Clean the primary heat exchanger tubes using a wire brush

attached to a length of high grade stainless steel cable, such
as drain cleanout cable. Attach a  variable speed reversible
drill to the other end of the cable.  Slowly rotate the cable
with the drill  and insert it into one of the heat exchanger
tubes.  While reversing the drill, work the cable in and out
several times to obtain sufficient cleaning.  Repeat for each
tube.

9. Clean residue from furnace using a vacuum cleaner.
10. Replace the parts removed in the previous steps in reverse

order.

11. Turn on electrical power and gas to furnace.  Check for leaks

and proper unit operation.

12. Severe heat exchanger fouling is an indication of an

operational problem.  Perform the checks listed in  

Section

XIV, Startup Procedure and Adjustments

 to reduce the

chances of repeated fouling.

XX. INTERNAL FILTER REMOVAL

Internal filters are an accessory item and are not included with your
furnace.  For further details, see your distributor.

B

OTTOM

 R

ETURN

 R

EMOVAL

1. Turn OFF electrical power to furnace.
2. Remove blower compartment door.
3. Push back and up on the wire filter retainer to release it from

under the front lip of the furnace basepan.

4. Slide filter forward and out.
5. Replace filter by reversing the procedure.

B

LOWER

 C

OMPARTMENT

 R

EMOVAL

1. Turn OFF electrical power to furnace.
2. Remove blower compartment door.
3. Grasp lower portion of filter and lift up.

Front of Furnace

Blower

Grab Here
And Lift

F

ilt

e

r

Front of Furnace

Blower

4. Angle filter toward the blower until filter clears bottom rail.
5. Lower filter down and pull outward.

Front of Furnace

Blower

Front of Furnace

Blower

6. Replace filter by reversing procedure.

XXI. BEFORE LEAVING AN INSTALLATION

Cycle the furnace with the thermostat at least three times.
Verify cooling and fan only operation.

Review the Owner’s Manual with the homeowner and discuss
proper furnace operation and maintenance.

Leave literature packet near furnace.

XXII. REPAIR & REPLACEMENT PARTS

When ordering any of the listed functional parts, be sure to
provide the furnace model, manufacturing, and serial
numbers with the order.

Although only functional parts are shown in the parts list, all
sheet metal parts, doors, etc. may be ordered by description.

Parts are available from your distributor.

Functional Parts List-

Gas Valve

Blower Motor

Gas Manifold

Blower Wheel

Natural Gas Orifice

Blower Mounting Bracket

Propane Gas Orifice

Blower Cutoff

Igniter

Blower Housing

Flame Sensor

Capacitor

Rollout Limit Switch

Heat Exchanger

Primary Limit Switch

Recuperator Coil

Auxiliary Limit Switch

Coil Front Cover

Pressure Switch

Integrated Control Module

Induced Draft Blower

Transformer

Door Switch

Содержание GCV9 Series

Страница 1: ...han when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of co...

Страница 2: ...ES 12 TERMINATION LOCATIONS 13 CANADIAN VENTING REQUIREMENTS 13 STANDARD FURNACE CONNECTIONS 13 ALTERNATE FURNACE CONNECTIONS 14 NON DIRECT VENT SINGLE PIPE PIPING 16 DIRECT VENT DUAL PIPE PIPING 17 V...

Страница 3: ...cuit Description 33 GENERAL 33 INTEGRATED CONTROL MODULE 33 PRIMARY LIMIT 33 AUXILIARY LIMIT 33 ROLLOUT LIMIT 33 PRESSURE SWITCHES 33 FLAME SENSOR 33 XVIII Troubleshooting 33 ELECTROSTATIC DISCHARGE E...

Страница 4: ...warranty certificate is also supplied with the unit Read the warranty carefully and note what is covered Keep the warranty certificate in a safe location for future reference If additional informatio...

Страница 5: ...itch 24 Inductor Not All Models 25 Two Stage Integrated Control Module with fuse and diagnostic LED 26 24 Volt Thermostat Connections 27 Transformer 40 VA 28 ECM Variable Speed Circulator Blower 29 Au...

Страница 6: ...ion are replaced The input rate and temperature rise are set per the furnace rating plate The input rate and temperature rise are set per the furnace rating plate 100 outside air is provided for combu...

Страница 7: ...ems Do not install the furnace where the combustion air is exposed to the following substances chlorinated waxes or cleaners chlorine based swimming pool chemicals water softening chemicals deicing sa...

Страница 8: ...rrected Corrections must be in accordance with the latest edition of the Na tional Fuel Gas Code NFPA 54 ANSI Z223 1 and or CSA B149 In stallation Codes printing inks paint removers varnishes hydrochl...

Страница 9: ...red a part of the unconfined space 5 3 3 Equipment Located in Confined Spaces a All Air from Inside the Building The confined space shall be pro vided with two permanent openings communicating directl...

Страница 10: ...ree area in 5 3 3 consideration shall be given to the block ing effect of louvers grilles or screens protecting openings Screens used shall not be smaller than 1 4 inch mesh If the area through a desi...

Страница 11: ...ed for the drain trap Additionally the appropriate downward piping slope must be maintained from the drain trap to the drain location Refer to Section X Condensate Drain Trap and Lines for further det...

Страница 12: ...is the responsibility of the installer to follow the manufacturers recommendations and to verify that all vent flue piping and connec tors are compatible with furnace flue products Additionally it is...

Страница 13: ...es should be made for minor expansion and contraction due to temperature variations For this reason particular care must be taken to secure piping when a long run is followed by a short offset of less...

Страница 14: ...t flue and combustion air intake piping run vertically from the side of the cabinet NOTE Standard and alternate locations can be combined i e an installation may use the standard combustion air intake...

Страница 15: ...tion refer to the following steps and the Alternate Combus tion Air Intake Location figure NOTE Counterflow unit instructions follow the upflow instructions 1 Remove and save the four screws securing...

Страница 16: ...be in stalled on the inside and outside of the wall The wall penetration should be sealed with silicone caulking material In a basement installation the vent flue pipe can be run between joist spaces...

Страница 17: ...er for construction of the vent flue and combustion air intake pipe systems of a direct vent dual pipe installation The number of elbows tabulated represents the number of elbows and or tees in each V...

Страница 18: ...LEVEL Standard Horizontal Terminations Dual Pipe 24 MAX 3 MIN 24 MAX AIR INTAKE 90 MEDIUM RADIUS ELBOW 12 MIN ABOVE HIGHEST ANTICIPATED SNOW LEVEL Alternate Horizontal Vent Termination Dual Pipe SUPPO...

Страница 19: ...d through the right or left side panel and into the drain trap secured to the outside of the cabinet NOTE Refer to Section X Condensate Drain Lines and Drain Trap Alternate Vent Flue Hose Connections...

Страница 20: ...p 2 Secure drain trap to side panel at the mounting holes dimples or crosshairs on counterflow models located below the grommet drain holes 3 Attach PVC drain line to drain trap outlet with either a 9...

Страница 21: ...NG ANY ELECTRICAL WIRING CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION VERIFY PROPER OPERATION AFTER SERVICING WIRING...

Страница 22: ...e Condensing Unit Single Stage Cooling Dehumidistat Optional NOTE To apply a single stage heating thermostat the thermostat selector jumper on the integrated Control module must be set on single stage...

Страница 23: ...eaner 1 0 Amp maximum at 120 VAC Turn OFF power to the furnace before installing any accessories Follow the humidifier or air cleaner manufacturers instructions for locating mounting grounding and con...

Страница 24: ...ring the gas supply pressure and manifold pressure are provided on the valve The gas valve has a manual ON OFF control located on the valve itself This control may be set only to the ON or OFF positio...

Страница 25: ...opane gas leak Rust can reduce the level of odorant in propane gas Do not rely on your sense of smell Contact a local propane connection is 375 in lbs excessive over tightening may damage the gas valv...

Страница 26: ...ng a pair of seamer pliers or seamer tongs NOTE Airflow area will be reduced by ap proximately 18 if duct flanges are not unfolded This could cause performance issues and noise issues WARNING EDGES OF...

Страница 27: ...ds If the furnace is installed without filters the warranty will be voided On upflow units guide dimples locate the side return cutout locations Use a straight edge to scribe lines connecting the dimp...

Страница 28: ...h an ignition device which automatically lights the burner Do not try to light the burner by hand 5 Move the furnace gas valve manual control to the OFF position 6 Wait five minutes then smell for gas...

Страница 29: ...w 8 Remove regulator cover screw from the low LO outlet pressure regulator adjust tower and turn screw clockwise to increase pressure or counterclockwise to decrease pressure 9 Energize main M solenoi...

Страница 30: ...t High Stage Heat Tap Model 390 520 715 930 600 800 1100 1430 840 920 1000 1080 1210 1325 1440 1555 A B C D 520 715 910 1170 800 1100 1400 1800 1125 1195 1265 1335 1620 1720 1820 1920 A B C D 520 715...

Страница 31: ...to enhance cooling performance and increase comfort level The ramping profiles are selected using DIP switches 5 and 6 Refer to the following figure for switch positions and their corresponding taps...

Страница 32: ...e monitors flame presence Gas valve will remain open only if flame is detected If the thermostat call is for low heat gas valve and induced draft blower will continue on low stage If the call is for h...

Страница 33: ...etected will take the necessary precau tions and provide diagnostic information through an LED PRIMARY LIMIT The primary limit control is located on the partition panel and moni tors heat exchanger co...

Страница 34: ...r leakage Check the outside termination and the connections at and internal to the furnace Heat exchanger Check for corrosion and or buildup within the heat exchanger passageways Burners Check for pro...

Страница 35: ...9 Clean residue from furnace using a vacuum cleaner 10 Replace the parts removed in the previous steps in reverse order 11 Turn on electrical power and gas to furnace Check for leaks and proper unit...

Страница 36: ...36...

Страница 37: ...Inspect pressure switch hose Repair if necessary Inspect flue and or inlet air piping for blockage proper length elbows and termination Check drain system Correct as necessary Correct pressure switch...

Страница 38: ...emove obstruction Check circulator blower speed and performance Correct speed or replace blower if necessary Check burners for proper alignment Check flue and air inlet piping for blockage proper leng...

Страница 39: ...OLS SINGLE CONTROL ON 45 kBTU PK PINK PLUG CONNECTION BURNER COMPARTMENT BLOWER COMPARTMENT VT IGNITER 2 MANUFACTURER S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING PK YL 5 FLASHES FLAME SE...

Страница 40: ...40 2004 2006 Goodman Manufacturing Company L P 2550 North Loop West Suite 400 Houston TX 77092 www goodmanmfg com...

Отзывы: