Goodman GCV9 Series Скачать руководство пользователя страница 24

24

Propane Gas

Natural Gas

Inlet Gas Supply Pressure

Minimum:5.0" W.C.   Maximum :10.0" W.C.
Minimum:11.0" W.C. Maximum :13.0" W.C.

H

IGH

 A

LTITUDE

 D

ERATE

When this furnace is installed at high altitude, the appropriate High
Altitude orifice kit must be applied.  This is required due to the natu-
ral reduction in the density of both the gas fuel and combustion air
as altitude increases.  The kit will provide the proper design certified
input rate within the specified altitude range.
High altitude kits are purchased according to the installation altitude
and usage of either natural or propane gas.  Contact your distributor
for a tabular listing of appropriate altitude ranges and correspond-
ing manufacturer’s high altitude (Natural, propane gas, and/or Pres-
sure Switch) kits.
Do 

not

 derate the furnace by adjusting the manifold pressure to a

lower pressure than specified on the furnace rating plate.  The com-
bination of the lower air density and a lower manifold pressure will
prohibit the burner orifice from drawing the proper amount of air into
the burner.  This may cause incomplete combustion, flashback, and
possible yellow tipping.
In some areas the gas supplier may artificially derate the gas in an
effort to compensate for the effects of altitude.  If the gas is artifi-
cially derated, the appropriate orifice size must be determined based
upon the BTU/ft

3

 content of the  derated gas and the altitude.  Refer

to the National Fuel Gas Code, NFPA 54/ANSI Z223.1, and infor-
mation provided by the gas supplier to determine the proper orifice
size.
A different pressure switch may be required at high altitude regard-
less of the BTU/ft

3

 content of the fuel used.  Contact your distributor

for a tabular listing of appropriate altitude ranges and correspond-
ing manufacturer’s pressure switch kits.

P

ROPANE

 G

AS

 C

ONVERSION

WARNING

P

OSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH MAY OCCUR IF

THE CORRECT CONVERSION KITS ARE NOT INSTALLED. 

T

HE APPROPRIATE KITS

MUST BE APPLIED TO INSURE SAFE AND PROPER FURNACE OPERATION. 

A

LL

CONVERSIONS MUST BE PERFORMED BY A QUALIFIED INSTALLER OR SERVICE

AGENCY.

This unit is configured for natural gas.  The appropriate
manufacturer’s propane gas conversion kit, must be applied for pro-
pane gas installations.  Refer to the 

Section VIII, Propane Gas /

High Altitude Installations

 section for details.

G

AS

 V

ALVE

This unit is equipped with a 24 volt gas valve controlled during fur-
nace operation by the integrated control module.  As shipped, the
valve is configured for natural gas.  The valve is field convertible for
use with propane gas by replacing the regulator spring with a pro-
pane gas spring from an appropriate manufacturer’s propane gas
conversion kit.  Taps for measuring the gas supply pressure and
manifold pressure are provided on the valve.
The gas valve has a manual ON/OFF control located on the valve
itself.  This control may be set only to the “ON” or “OFF” position.
Refer to the lighting instructions label or 

Section XIV, Startup Proce-

dure & Adjustment 

for use of this control during start up and shut

down periods.

G

AS

 P

IPING

 C

ONNECTIONS

G

ENERAL

CAUTION

T

O AVOID POSSIBLE UNSATISFACTORY OPERATION OR EQUIPMENT DAMAGE

DUE TO UNDERFIRING OF EQUIPMENT, USE THE PROPER SIZE OF

NATURAL/PROPANE GAS PIPING NEEDED WHEN RUNNING PIPE FROM THE

METER/TANK TO THE FURNACE.

When sizing a trunk line, be sure to include all appliances which
will operate simultaneously when sizing a trunk line.
The gas piping supplying the furnace must be properly sized based
on the gas flow required, specific gravity of the gas, and length of
the run.  The gas line installation must comply with local codes, or in
their absence, with the latest edition of the National Fuel Gas Code,
NFPA 54/ANSI Z223.1.

Natural Gas  Capacity of Pipe

In Cubic Feet of Gas  Per Hour (CFH)

Length of

Nominal Black  Pipe Size

Pipe in Feet

1/2"

3/4"

1"

1 1/4"

1 1/2"

10

132

278

520

1050

1600

20

92

190

350

730

1100

30

73

152

285

590

980

40

63

130

245

500

760

50

56

115

215

440

670

60

50

105

195

400

610

70

46

96

180

370

560

80

43

90

170

350

530

90

40

84

160

320

490

100

38

79

150

305

460

(Pressure 0.5 psig or less and pressure drop of 0.3" W.C.; Based on
0.60 Specific Gravity Gas)

CFH =

BTUH Furnace Input   
Heating Value of Gas (BTU/Cubic Foot)

To connect the furnace to the building’s gas piping, the installer must
supply a ground joint union, drip leg, manual shutoff valve, and line
and fittings to connect to gas valve.  In some cases, the installer
may also need to supply a transition piece from 1/2" pipe to a larger
pipe size.
The following stipulations apply when connecting gas piping.  Refer
to 

Gas Piping Connections 

figure for typical gas line connections to

the furnace.

Use black iron or steel pipe and fittings for building piping.
Where possible, use new pipe that is properly chamfered,
reamed, and free of burrs and chips.  If old pipe is used, be
sure it is clean and free of rust, scale, burrs, chips, and old
pipe joint compound.

Use pipe joint compound on male threads ONLY.  Always
use pipe joint compound (pipe dope) that is APPROVED FOR
ALL GASSES.  DO NOT apply compound to the first two
threads.

Use ground joint unions.

Install a drip leg to trap dirt and moisture before it can enter
the gas valve.  The drip leg must be a minimum of three
inches long.

Install a 1/8" NPT pipe plug fitting, accessible for test gage
connection, immediately upstream of the gas supply
connection to the furnace.

Always use a back-up wrench when making the connection
to the gas valve to keep it from turning.  The orientation of
the gas valve on the manifold must be maintained as shipped
from the factory.  Maximum torque for the gas valve

Содержание GCV9 Series

Страница 1: ...han when the unit is in operation Remember it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use Safety is a matter of co...

Страница 2: ...ES 12 TERMINATION LOCATIONS 13 CANADIAN VENTING REQUIREMENTS 13 STANDARD FURNACE CONNECTIONS 13 ALTERNATE FURNACE CONNECTIONS 14 NON DIRECT VENT SINGLE PIPE PIPING 16 DIRECT VENT DUAL PIPE PIPING 17 V...

Страница 3: ...cuit Description 33 GENERAL 33 INTEGRATED CONTROL MODULE 33 PRIMARY LIMIT 33 AUXILIARY LIMIT 33 ROLLOUT LIMIT 33 PRESSURE SWITCHES 33 FLAME SENSOR 33 XVIII Troubleshooting 33 ELECTROSTATIC DISCHARGE E...

Страница 4: ...warranty certificate is also supplied with the unit Read the warranty carefully and note what is covered Keep the warranty certificate in a safe location for future reference If additional informatio...

Страница 5: ...itch 24 Inductor Not All Models 25 Two Stage Integrated Control Module with fuse and diagnostic LED 26 24 Volt Thermostat Connections 27 Transformer 40 VA 28 ECM Variable Speed Circulator Blower 29 Au...

Страница 6: ...ion are replaced The input rate and temperature rise are set per the furnace rating plate The input rate and temperature rise are set per the furnace rating plate 100 outside air is provided for combu...

Страница 7: ...ems Do not install the furnace where the combustion air is exposed to the following substances chlorinated waxes or cleaners chlorine based swimming pool chemicals water softening chemicals deicing sa...

Страница 8: ...rrected Corrections must be in accordance with the latest edition of the Na tional Fuel Gas Code NFPA 54 ANSI Z223 1 and or CSA B149 In stallation Codes printing inks paint removers varnishes hydrochl...

Страница 9: ...red a part of the unconfined space 5 3 3 Equipment Located in Confined Spaces a All Air from Inside the Building The confined space shall be pro vided with two permanent openings communicating directl...

Страница 10: ...ree area in 5 3 3 consideration shall be given to the block ing effect of louvers grilles or screens protecting openings Screens used shall not be smaller than 1 4 inch mesh If the area through a desi...

Страница 11: ...ed for the drain trap Additionally the appropriate downward piping slope must be maintained from the drain trap to the drain location Refer to Section X Condensate Drain Trap and Lines for further det...

Страница 12: ...is the responsibility of the installer to follow the manufacturers recommendations and to verify that all vent flue piping and connec tors are compatible with furnace flue products Additionally it is...

Страница 13: ...es should be made for minor expansion and contraction due to temperature variations For this reason particular care must be taken to secure piping when a long run is followed by a short offset of less...

Страница 14: ...t flue and combustion air intake piping run vertically from the side of the cabinet NOTE Standard and alternate locations can be combined i e an installation may use the standard combustion air intake...

Страница 15: ...tion refer to the following steps and the Alternate Combus tion Air Intake Location figure NOTE Counterflow unit instructions follow the upflow instructions 1 Remove and save the four screws securing...

Страница 16: ...be in stalled on the inside and outside of the wall The wall penetration should be sealed with silicone caulking material In a basement installation the vent flue pipe can be run between joist spaces...

Страница 17: ...er for construction of the vent flue and combustion air intake pipe systems of a direct vent dual pipe installation The number of elbows tabulated represents the number of elbows and or tees in each V...

Страница 18: ...LEVEL Standard Horizontal Terminations Dual Pipe 24 MAX 3 MIN 24 MAX AIR INTAKE 90 MEDIUM RADIUS ELBOW 12 MIN ABOVE HIGHEST ANTICIPATED SNOW LEVEL Alternate Horizontal Vent Termination Dual Pipe SUPPO...

Страница 19: ...d through the right or left side panel and into the drain trap secured to the outside of the cabinet NOTE Refer to Section X Condensate Drain Lines and Drain Trap Alternate Vent Flue Hose Connections...

Страница 20: ...p 2 Secure drain trap to side panel at the mounting holes dimples or crosshairs on counterflow models located below the grommet drain holes 3 Attach PVC drain line to drain trap outlet with either a 9...

Страница 21: ...NG ANY ELECTRICAL WIRING CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION VERIFY PROPER OPERATION AFTER SERVICING WIRING...

Страница 22: ...e Condensing Unit Single Stage Cooling Dehumidistat Optional NOTE To apply a single stage heating thermostat the thermostat selector jumper on the integrated Control module must be set on single stage...

Страница 23: ...eaner 1 0 Amp maximum at 120 VAC Turn OFF power to the furnace before installing any accessories Follow the humidifier or air cleaner manufacturers instructions for locating mounting grounding and con...

Страница 24: ...ring the gas supply pressure and manifold pressure are provided on the valve The gas valve has a manual ON OFF control located on the valve itself This control may be set only to the ON or OFF positio...

Страница 25: ...opane gas leak Rust can reduce the level of odorant in propane gas Do not rely on your sense of smell Contact a local propane connection is 375 in lbs excessive over tightening may damage the gas valv...

Страница 26: ...ng a pair of seamer pliers or seamer tongs NOTE Airflow area will be reduced by ap proximately 18 if duct flanges are not unfolded This could cause performance issues and noise issues WARNING EDGES OF...

Страница 27: ...ds If the furnace is installed without filters the warranty will be voided On upflow units guide dimples locate the side return cutout locations Use a straight edge to scribe lines connecting the dimp...

Страница 28: ...h an ignition device which automatically lights the burner Do not try to light the burner by hand 5 Move the furnace gas valve manual control to the OFF position 6 Wait five minutes then smell for gas...

Страница 29: ...w 8 Remove regulator cover screw from the low LO outlet pressure regulator adjust tower and turn screw clockwise to increase pressure or counterclockwise to decrease pressure 9 Energize main M solenoi...

Страница 30: ...t High Stage Heat Tap Model 390 520 715 930 600 800 1100 1430 840 920 1000 1080 1210 1325 1440 1555 A B C D 520 715 910 1170 800 1100 1400 1800 1125 1195 1265 1335 1620 1720 1820 1920 A B C D 520 715...

Страница 31: ...to enhance cooling performance and increase comfort level The ramping profiles are selected using DIP switches 5 and 6 Refer to the following figure for switch positions and their corresponding taps...

Страница 32: ...e monitors flame presence Gas valve will remain open only if flame is detected If the thermostat call is for low heat gas valve and induced draft blower will continue on low stage If the call is for h...

Страница 33: ...etected will take the necessary precau tions and provide diagnostic information through an LED PRIMARY LIMIT The primary limit control is located on the partition panel and moni tors heat exchanger co...

Страница 34: ...r leakage Check the outside termination and the connections at and internal to the furnace Heat exchanger Check for corrosion and or buildup within the heat exchanger passageways Burners Check for pro...

Страница 35: ...9 Clean residue from furnace using a vacuum cleaner 10 Replace the parts removed in the previous steps in reverse order 11 Turn on electrical power and gas to furnace Check for leaks and proper unit...

Страница 36: ...36...

Страница 37: ...Inspect pressure switch hose Repair if necessary Inspect flue and or inlet air piping for blockage proper length elbows and termination Check drain system Correct as necessary Correct pressure switch...

Страница 38: ...emove obstruction Check circulator blower speed and performance Correct speed or replace blower if necessary Check burners for proper alignment Check flue and air inlet piping for blockage proper leng...

Страница 39: ...OLS SINGLE CONTROL ON 45 kBTU PK PINK PLUG CONNECTION BURNER COMPARTMENT BLOWER COMPARTMENT VT IGNITER 2 MANUFACTURER S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING PK YL 5 FLASHES FLAME SE...

Страница 40: ...40 2004 2006 Goodman Manufacturing Company L P 2550 North Loop West Suite 400 Houston TX 77092 www goodmanmfg com...

Отзывы: