Gas valve opens at end of igniter warm up period, delivering
gas to burners and establishing flame.

Integrated control module monitors flame presence.  Gas
valve will remain open only if flame is detected.

If the thermostat call is for low heat, gas valve and induced
draft blower will continue on low stage. If the call is for
high heat, the gas valve and induced draft blower will
change to high stage.

Circulator blower is energized on heat speed following a
thirty (30) second blower on delay.  The circulator blower
requires thirty seconds to ramp up to full speed.
Electronic air cleaner terminal is energized with circulator
blower.

Furnace is now operating on the specified stage called
for by the two-stage thermostat.

Furnace runs, integrated control module monitors safety
circuits continuously.

If the two-stage thermostat changes the call from low
heat to high heat, the integrated control module will
immediately switch the induced draft blower, gas valve,
and circulator blower to their high stage settings.

If the two-stage thermostat changes the call from high
heat to low heat, the control will immediately switch the
induced draft blower and gas valve to their low stage
settings.  The circulator blower will remain on high
heating speed for thirty (30) seconds before switching to
the low heat circulating speed.

R and W1 (or R and W1/W2) thermostat contacts open,
completing the call for heat.

Gas valve closes, extinguishing flame.

Induced draft blower is de-energized following a fifteen
second post purge. Humidifier terminals are de-energized.

Circulator blower continues running for the selected heat
off delay period (90, 120, 150 or 180 seconds).  The
speed run during this period depends on the last heat
call provided by the thermostat.
If the last call for heat was a call for low heat, the air
circulator motor will run on low heat speed for the duration
of the heat off delay period (90, 120, 150 or 180 seconds).
If the last call for heat was a call for high heat, the air
circulating motor will run on the high heating speed for
thirty (30) seconds and then switch to the low heating
speed for the 

balance 

of the heat off delay period (60,

90, 120 or 150 seconds).

Circulator blower and electronic air cleaner terminal is
de-energized.

Circulator blower ramps down to OFF during the 30

seconds following the heat off delay period.

Furnace awaits next call from thermostat.

C

OOLING

 M

ODE

The normal operational sequence in cooling mode is as fol-
lows:

R and Y1/G or Y2/G thermostat contacts close, initiating
a call for cool.

Integrated control module performs safety circuit checks.

Outdoor fan and compressor are energized to their
appropriate speed.

Circulator blower is energized on the appropriate cool
speed at the level and time determined by the selected
ramping profile.  Electronic air cleaner terminal is
energized with circulator blower.

Furnace circulator blower and outdoor cooling unit run
their appropriate speeds, integrated control module
monitors safety circuits continuously.

R and Y1/G or Y2/G thermostat contacts open,
completing the call for cool.

Outdoor fan and compressor are de-energized.

Circulator blower continues running during a cool off delay
period.  The OFF delay time and airflow level are
determined by the selected ramping profile.

Electronic air cleaner terminal and circulator blower are
de-energized.

Furnace awaits next call from thermostat.

F

AN

 O

NLY

 M

ODE

The normal operational sequence in fan only mode is as fol-
lows:

R and G thermostat contacts close, initiating a call for
fan.

Integrated control module performs safety circuit checks.

Circulator blower is energized on continuous fan speed
(25% of the furnace’s maximum airflow capability)
following a five (5) second delay.  Electronic air cleaner
terminal is energized.

Circulator blower runs, integrated control module
monitors safety circuits continuously.

R and G thermostat contacts open, completing the call
for fan.

Circulator blower is de-energized.  Electronic air cleaner
terminal is de-energized.

Furnace awaits next call from thermostat.

O

PERATIONAL

 C

HECKS

The burner flames should be inspected with the burner com-
partment door installed.  Flames should be stable, quiet, soft,
and blue (dust may cause orange tips but they must not be
yellow).  Flames should extend directly outward from the burn-
ers without curling, floating, or lifting off.  Flames must not
impinge on the sides of the heat exchanger firing tubes.

Содержание DVC80603B

Страница 1: ...s a matter of common sense a matter of thinking before acting Most dealers have a list of specific good safety practices follow them The precautions listed in this Installation Manual are intended as...

Страница 2: ...LEANOUT 13 CHECK 5 LINER CONDITION 13 CHECK 6 DILUTION AIR 13 CHECK 7 COMPLETE THE INSTALLATION 13 FIX 1 LINER TERMINATION 14 FIX 2 CHANGE VENTING ARRANGEMENTS 14 FIX 3 REBUILD THE CROWN 14 FIX 4 RELI...

Страница 3: ...ATION 34 POWER UP 34 HEATING MODE 34 COOLING MODE 35 FAN ONLY MODE 35 OPERATIONAL CHECKS 35 SAFETY CIRCUIT DESCRIPTION 36 INTEGRATED CONTROL MODULE 36 PRIMARY LIMIT 36 AUXILIARY LIMIT 36 ROLLOUT LIMIT...

Страница 4: ...AND IN SUCH CASE ALTERNATIVE HEAT SOURCES SHOULD BE UTILIZED WARNING TO PREVENT POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK THE FURNACE MUST BE LOCATED TO PROTECT THE ELE...

Страница 5: ...trol module to electrostatic discharge This procedure is applicable to both installed and non installed ungrounded furnaces 1 Disconnect all power to the furnace Do not touch the integrated control mo...

Страница 6: ...els currently in pro ductioncanbeviewedatwww goodmanmfg comor www amana hac com If your model is not currently in production or does not appear on the website please contact your installing con tracto...

Страница 7: ...hese pub lications are available from National Fire Protection Association Inc 1 Batterymarch Park Quincy MA 02269 NOTE Furnaces with NOx screens meet the California NOx emission standards and Califor...

Страница 8: ...ing salts or chemicals carbon tetrachloride halogen type refrigerants cleaning solutions such as perchloroethylene printing inks paint removers varnishes hydrochloric acid cements and glues antistatic...

Страница 9: ...ing Turn on clothes dryers and any appliance not connected to the venting system Turn on any exhaust fans such as range hoods and bathroom exhausts so they shall operate at maximum speed Do not operat...

Страница 10: ...ap pliances i e water heaters All installations must be vented in accordance with National Fuel Gas Code NFPA54 ANSI Z223 1 latest edition In Canada the furnaces must be vented in ac cordance with the...

Страница 11: ...t on the suitability of this type of venting In most situations the existing masonry chimneys will require a properly sized metallic liner POSSIBILITY OF PROPERTY DAMAGE PERSONAL INJURY OR DEATH DAMAG...

Страница 12: ...clude fireplaces wood stoves coal fur naces and incinerators Proper Chimney Termination Check 1 Chimney channel free of solid and liquid fuel appliances Check 2 Change venting arrangements Fix 2 Crown...

Страница 13: ...air will not be available the chimney must be relined Fix 4 CHECK 7 COMPLETE THE INSTALLATION If Checks 1 through 6 have been satisfactory and the liner is an acceptable size as determined by the tabl...

Страница 14: ...or solid fuel appliances They are not suitable for use with gas fired appliances Flexible liners specifically intended and tested for gas applications are listed in the UL Gas and Oil Equipment Direc...

Страница 15: ...N AFTER SERVICING CAUTION HIGH VOLTAGE TO AVOID THE RISK OF INJURY ELECTRICAL SHOCK OR DEATH THE FURNACE MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR IN THEIR ABSENCE WITH THE LATES...

Страница 16: ...CODE WARNING To ensure proper unit grounding the ground wire should run from the furnace ground screw located inside the furnace junc tion box all the way back to the electrical panel NOTE Do not use...

Страница 17: ...ermine the time to transition from low stage to high stage To use a single stage thermostat turn off power to the fur nace move the thermostat selection DIP switch to the OFF position Set the desired...

Страница 18: ...inals for controlling power to an optional field supplied humidifier and or electronic air cleaner The accessory load specifications are as follows Humidifier 1 0 Amp maximum at 120 VAC Electronic Air...

Страница 19: ...iring rate by changing orifices or increasing the manifold pressure This can cause poor combustion and equipment failure High altitude installations may require both a pressure switch and an orifice c...

Страница 20: ...the furnace Use two pipe wrenches when making connection to the gas valve to keep it from turning The orientation of the gas valve on the manifold must be maintained as shipped from the factory Instal...

Страница 21: ...AK SINCE PROPANE GAS IS HEAVIER THAN AIR ANY LEAKING GAS CAN SETTLE IN ANY LOW AREAS OR CONFINED SPACES PROPANE GAS ODORANT MAY FADE MAKING THE GAS UNDETECTABLE EXCEPT WITH A WARNING DEVICE WARNING A...

Страница 22: ...e blower from interfering with combustion air or draft when a cen tral return is used a connecting duct must be installed be tween the unit and the utility room wall A room closet or alcove must not b...

Страница 23: ...or dirty filter Circulating air filters must be inspected monthly for dirt accumulation and replaced if necessary Failure to maintain clean filters can cause prema ture heat exchanger failure A new ho...

Страница 24: ...losethemanualgasshutoffvalveexternaltothefurnace 4 Replace the burner compartment door GASSUPPLYPRESSUREMEASUREMENT CAUTION TO PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE THE INLET GAS SUPPLY PRE...

Страница 25: ...The manifold pressure must be measured with the burners operating To measure and adjust the manifold pressure use the following procedure 1 Turn OFF gas to furnace at the manual gas shutoff valve exte...

Страница 26: ...justment for details NOTE The final manifold pressure cannot vary by more than 0 3 w c from the specified setting Consult your local gas supplier if additional input rate adjustment is required 5 Repe...

Страница 27: ...Acooling airflow of 990 CFM can be attained by setting the cooling speed to C and the adjustment to minus 4 Continuous fan speed in legacy mode is 25 of the furnace s maximum airflow capability For co...

Страница 28: ...et System Airflow Consideration section for details DVC81005C DVC80805C DVC80603B MVC81005C MVC80805C MVC80604B To set airflow C 7 5 min 82 60 sec 100 A 60 sec 100 TAP 1 2 3 4 5 6 7 8 To set Comfort M...

Страница 29: ...he dual 7 segment LED display In general lower heating speeds will reduce electrical consump tion lower operating sound levels of the blower and increase the outlet air temperature delivered to the ho...

Страница 30: ...he CTK0 thermostat provides the airflow demand The thermostat may be configured for a low medium or high continuous fan speed The low medium and high fan speeds correspond to 25 50 and 75 respec tivel...

Страница 31: ...ee tables below for listing of furnace submenus Touch the or _ to step through the list of submenus and view settings If a setting can be adjusted _ and keys will appear Use the _ or keys to adjust th...

Страница 32: ...y repeated faults are shown a maximum of 3 times DIAGNOSTICS Submenu Item Indication for Display Only not User Modifiable Model Number MOD NUM Displays the furnace model number Serial Number SER NUM D...

Страница 33: ...m CL TRM 10 to 10 in 2 increments default is 0 Selects the airflow trim amount for the non communicating compatible single stage AC unit Cool Airflow Profile CL PRFL A B C or D default is A Selects th...

Страница 34: ...tions LED 2 Flashes Out of box reset Control power up Learn button depressed None None Off No power Communications error No power to furnace Open fuse Communications error Check fuses and circuit brea...

Страница 35: ...balance of the heat off delay period 60 90 120 or 150 seconds Circulator blower and electronic air cleaner terminal is de energized Circulator blower ramps down to OFF during the 30 seconds following...

Страница 36: ...and or blocked condensate drain condi tions FLAME SENSOR The flame sensor is a probe mounted to the burner manifold assembly which uses the principle of flame rectification to de termine the presence...

Страница 37: ...ear This check should be per formed at the beginning of the heating season This will ensure that all furnace components are in proper working order and that the heating system functions appropriately...

Страница 38: ...ect the flue pipe system from the induced draft blower 4 Remove the induced draft blower and collector box cover 5 Clean the primary heat exchanger tubes using a wire brush attached to a length of hig...

Страница 39: ...nse signal Sand sensor if coated and or oxidized x Check flue piping for blockage proper length elbows and termination x Verify proper induced draft blower performance x Turn power OFF prior to repair...

Страница 40: ...l for heat IMPROPER FLAME E4 x Short to ground in flame sense circuit x Lingering burner flame x Slow closing gas valve x Correct short at flame sensor or in flame sensor wiring x Check for lingering...

Страница 41: ...Repair replace if necessary x Inspect flue and or inlet air piping for blockage proper length elbows and termination Check drain system Correct as necessary x Check induced draft blower performance C...

Страница 42: ...has lost communications with circulator blower motor MOTOR COMM b1 x Loose wiring connection at circulator motor control leads x Failed circulator blower motor x Failed integrated control module x Ti...

Страница 43: ...et thermostat Call for Service icon illuminated x ComfortNet thermostat scrolls Check Furnace message b6 x Circulator blower motor shuts down for over or under voltage condition x Circulator blower mo...

Страница 44: ...G CYCLE HIGH STAGE PRESSURE SWITCH STUCK OPEN REVERSED 115 VAC POLARITY DATA NOT YET ON NETWORK INVALID MEMORY CARD DATA BLOWER MOTOR NOT RUNNING BLOWER COMMUNICATION ERROR BLOWER HP MIS MATCH BLOWER...

Страница 45: ...30 sec 50 7 5 min 82 30 sec 50 Select desired Comfort Mode profile see profiles above Set switches 5 and 6 to the appropriate ON OFF positions A OFF OFF OFF OFF OFF OFF OFF OFF Model Tap Low Stage Hig...

Страница 46: ...CIRCULATOR BLOWER R 1 GND JUNCTION BOX SWITCH TEMP NEUTRAL 115kBTU MODELS BLOWER COMPARTMENT DOOR SWITCH OPEN WHEN DOOR OPEN C LINE BK 4 NEUTRAL POLARIZED AND C FS 2 PLUG CONNECTION DISCONNECT PU 3 I...

Страница 47: ...47 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 48: ...48 Goodman Manufacturing Company L P 5151 San Felipe Suite 500 Houston TX 77056 www goodmanmfg com 2011 2012 Goodman Manufacturing Company L P...

Отзывы: