7

To ensure proper furnace operation, install, operate and
maintain the furnace in accordance with these installa-
tion and operation instructions, all local building codes
and ordinances.

  In their absence, follow the latest edition of

the National Fuel Gas Code (NFPA 54/ANSI Z223.1), and/or
CAN/CSA B149 Installation Codes, local plumbing or waste
water codes, and other applicable codes.

A copy of the National Fuel Gas Code (NFPA 54/ANSI Z223.1)
can be obtained from any of the following:

American National Standards Institute

1430 Broadway

New York,  NY  10018

National Fire Protection Association

1 Batterymarch Park

Quincy, MA  02269

CSA International

8501 East Pleasant Valley

Cleveland, OH 44131

A copy of the CAN/CSA B149 Installation Codes can also be
obtained from:

CSA International

178 Rexdale Boulevard

Etobicoke, Ontario, Canada M9W 1R3

The rated heating capacity of the furnace should be greater
than or equal to the total heat loss of the area to be heated.
The total heat loss should be calculated by an approved method
or in accordance with “ASHRAE Guide” or “Manual J-Load Cal-
culations” published by the Air Conditioning Contractors of
America.

In the USA, this furnace MUST be installed in accordance with
the latest edition of the ANSI  Z223.1 booklet entitled “National
Fuel Gas Code” (NFPA 54), and the requirements or codes of
the local utility or other authority having jurisdiction. In Canada,
this furnace must be installed in accordance with the current
CAN/CGA-B149.1 & 2 Gas Installation Codes, local plumbing
or waste water codes and other applicable codes.  Additional
helpful publications available from the NFPA are, NFPA 90A -
Installation of Air Conditioning and Ventilating System and NFPA
90B - Warm Air Heating and Air Conditioning System.

All venting shall be in accordance with PART 7, Venting of Equip-
ment, of the National Fuel Gas Code, ANSI Z223.1, or appli-
cable local building and/or air conditioning codes.  These pub-
lications are available from:

National Fire Protection Association, Inc.

1 Batterymarch Park,  Quincy, MA  02269

NOTE:

 Furnaces with NOx screens meet the California NOx

emission standards and California seasonal efficiency stan-
dards. ANNUAL inspections of the furnace and its vent system
is strongly recommended.

L

OCATION

 R

EQUIREMENTS

 

AND

 C

ONSIDERATIONS

Your unit model type determines which installation procedures
must be used. For *MVC8 models, you must follow instruc-
tions for Horizontal Left, Horizontal Right or Upflow installa-
tions only. These furnaces are not approved for Downflow in-
stallations.
Downflow models 

*DVC8

 

ARE NOT APPROVED FOR HORI-

ZONTAL OR UPFLOW INSTALLATIONS

. For these models,

use only the instructions for downflow installation only.

T

O

 

PREVENT

 

POSSIBLE

 

EQUIPMENT

 

DAMAGE

,

 

PROPERTY

 

DAMAGE

,

 

PERSONAL

 

INJURY

 

OR

 

DEATH

,

 

THE

 

FOLLOWING

 

BULLET

 

POINTS

 

MUST

 

BE

 

OBSERVED

 

WHEN

 

INSTALLING

 

THIS

 

UNIT

.

WARNING

Follow the instructions listed below when selecting a furnace
location.  Refer also to the guidelines provided in 

Section V,

Combustion and Ventilation Air Requirements.

Centrally locate the furnace with respect to the
proposed or existing air distribution system.

Ensure the temperature of the return air entering the
furnace is between 55°F and 100°F when the furnace
is heating.

Provisions must be made for venting combustion
products outdoors through a proper venting system.
The length of flue pipe could be a limiting factor in
locating the furnace.

Ensure adequate combustion air is available for the
furnace.  Improper or insufficient combustion air can
expose building occupants to gas combustion products
that could include carbon monoxide.  Refer to

Combustion and Ventilation Air Requirements 

section

.

The furnace must be level. If the furnace is to be set
on a floor that may become wet or damp at times, the
furnace should be supported above the floor on a
concrete base sized approximately 1-1/2" larger than
the base of the furnace.

Ensure upflow or horizontal furnaces are not installed
directly on carpeting, or any other combustible
material.  The only combustible material allowed is
wood.

Содержание DVC80603B

Страница 1: ...s a matter of common sense a matter of thinking before acting Most dealers have a list of specific good safety practices follow them The precautions listed in this Installation Manual are intended as...

Страница 2: ...LEANOUT 13 CHECK 5 LINER CONDITION 13 CHECK 6 DILUTION AIR 13 CHECK 7 COMPLETE THE INSTALLATION 13 FIX 1 LINER TERMINATION 14 FIX 2 CHANGE VENTING ARRANGEMENTS 14 FIX 3 REBUILD THE CROWN 14 FIX 4 RELI...

Страница 3: ...ATION 34 POWER UP 34 HEATING MODE 34 COOLING MODE 35 FAN ONLY MODE 35 OPERATIONAL CHECKS 35 SAFETY CIRCUIT DESCRIPTION 36 INTEGRATED CONTROL MODULE 36 PRIMARY LIMIT 36 AUXILIARY LIMIT 36 ROLLOUT LIMIT...

Страница 4: ...AND IN SUCH CASE ALTERNATIVE HEAT SOURCES SHOULD BE UTILIZED WARNING TO PREVENT POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK THE FURNACE MUST BE LOCATED TO PROTECT THE ELE...

Страница 5: ...trol module to electrostatic discharge This procedure is applicable to both installed and non installed ungrounded furnaces 1 Disconnect all power to the furnace Do not touch the integrated control mo...

Страница 6: ...els currently in pro ductioncanbeviewedatwww goodmanmfg comor www amana hac com If your model is not currently in production or does not appear on the website please contact your installing con tracto...

Страница 7: ...hese pub lications are available from National Fire Protection Association Inc 1 Batterymarch Park Quincy MA 02269 NOTE Furnaces with NOx screens meet the California NOx emission standards and Califor...

Страница 8: ...ing salts or chemicals carbon tetrachloride halogen type refrigerants cleaning solutions such as perchloroethylene printing inks paint removers varnishes hydrochloric acid cements and glues antistatic...

Страница 9: ...ing Turn on clothes dryers and any appliance not connected to the venting system Turn on any exhaust fans such as range hoods and bathroom exhausts so they shall operate at maximum speed Do not operat...

Страница 10: ...ap pliances i e water heaters All installations must be vented in accordance with National Fuel Gas Code NFPA54 ANSI Z223 1 latest edition In Canada the furnaces must be vented in ac cordance with the...

Страница 11: ...t on the suitability of this type of venting In most situations the existing masonry chimneys will require a properly sized metallic liner POSSIBILITY OF PROPERTY DAMAGE PERSONAL INJURY OR DEATH DAMAG...

Страница 12: ...clude fireplaces wood stoves coal fur naces and incinerators Proper Chimney Termination Check 1 Chimney channel free of solid and liquid fuel appliances Check 2 Change venting arrangements Fix 2 Crown...

Страница 13: ...air will not be available the chimney must be relined Fix 4 CHECK 7 COMPLETE THE INSTALLATION If Checks 1 through 6 have been satisfactory and the liner is an acceptable size as determined by the tabl...

Страница 14: ...or solid fuel appliances They are not suitable for use with gas fired appliances Flexible liners specifically intended and tested for gas applications are listed in the UL Gas and Oil Equipment Direc...

Страница 15: ...N AFTER SERVICING CAUTION HIGH VOLTAGE TO AVOID THE RISK OF INJURY ELECTRICAL SHOCK OR DEATH THE FURNACE MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR IN THEIR ABSENCE WITH THE LATES...

Страница 16: ...CODE WARNING To ensure proper unit grounding the ground wire should run from the furnace ground screw located inside the furnace junc tion box all the way back to the electrical panel NOTE Do not use...

Страница 17: ...ermine the time to transition from low stage to high stage To use a single stage thermostat turn off power to the fur nace move the thermostat selection DIP switch to the OFF position Set the desired...

Страница 18: ...inals for controlling power to an optional field supplied humidifier and or electronic air cleaner The accessory load specifications are as follows Humidifier 1 0 Amp maximum at 120 VAC Electronic Air...

Страница 19: ...iring rate by changing orifices or increasing the manifold pressure This can cause poor combustion and equipment failure High altitude installations may require both a pressure switch and an orifice c...

Страница 20: ...the furnace Use two pipe wrenches when making connection to the gas valve to keep it from turning The orientation of the gas valve on the manifold must be maintained as shipped from the factory Instal...

Страница 21: ...AK SINCE PROPANE GAS IS HEAVIER THAN AIR ANY LEAKING GAS CAN SETTLE IN ANY LOW AREAS OR CONFINED SPACES PROPANE GAS ODORANT MAY FADE MAKING THE GAS UNDETECTABLE EXCEPT WITH A WARNING DEVICE WARNING A...

Страница 22: ...e blower from interfering with combustion air or draft when a cen tral return is used a connecting duct must be installed be tween the unit and the utility room wall A room closet or alcove must not b...

Страница 23: ...or dirty filter Circulating air filters must be inspected monthly for dirt accumulation and replaced if necessary Failure to maintain clean filters can cause prema ture heat exchanger failure A new ho...

Страница 24: ...losethemanualgasshutoffvalveexternaltothefurnace 4 Replace the burner compartment door GASSUPPLYPRESSUREMEASUREMENT CAUTION TO PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE THE INLET GAS SUPPLY PRE...

Страница 25: ...The manifold pressure must be measured with the burners operating To measure and adjust the manifold pressure use the following procedure 1 Turn OFF gas to furnace at the manual gas shutoff valve exte...

Страница 26: ...justment for details NOTE The final manifold pressure cannot vary by more than 0 3 w c from the specified setting Consult your local gas supplier if additional input rate adjustment is required 5 Repe...

Страница 27: ...Acooling airflow of 990 CFM can be attained by setting the cooling speed to C and the adjustment to minus 4 Continuous fan speed in legacy mode is 25 of the furnace s maximum airflow capability For co...

Страница 28: ...et System Airflow Consideration section for details DVC81005C DVC80805C DVC80603B MVC81005C MVC80805C MVC80604B To set airflow C 7 5 min 82 60 sec 100 A 60 sec 100 TAP 1 2 3 4 5 6 7 8 To set Comfort M...

Страница 29: ...he dual 7 segment LED display In general lower heating speeds will reduce electrical consump tion lower operating sound levels of the blower and increase the outlet air temperature delivered to the ho...

Страница 30: ...he CTK0 thermostat provides the airflow demand The thermostat may be configured for a low medium or high continuous fan speed The low medium and high fan speeds correspond to 25 50 and 75 respec tivel...

Страница 31: ...ee tables below for listing of furnace submenus Touch the or _ to step through the list of submenus and view settings If a setting can be adjusted _ and keys will appear Use the _ or keys to adjust th...

Страница 32: ...y repeated faults are shown a maximum of 3 times DIAGNOSTICS Submenu Item Indication for Display Only not User Modifiable Model Number MOD NUM Displays the furnace model number Serial Number SER NUM D...

Страница 33: ...m CL TRM 10 to 10 in 2 increments default is 0 Selects the airflow trim amount for the non communicating compatible single stage AC unit Cool Airflow Profile CL PRFL A B C or D default is A Selects th...

Страница 34: ...tions LED 2 Flashes Out of box reset Control power up Learn button depressed None None Off No power Communications error No power to furnace Open fuse Communications error Check fuses and circuit brea...

Страница 35: ...balance of the heat off delay period 60 90 120 or 150 seconds Circulator blower and electronic air cleaner terminal is de energized Circulator blower ramps down to OFF during the 30 seconds following...

Страница 36: ...and or blocked condensate drain condi tions FLAME SENSOR The flame sensor is a probe mounted to the burner manifold assembly which uses the principle of flame rectification to de termine the presence...

Страница 37: ...ear This check should be per formed at the beginning of the heating season This will ensure that all furnace components are in proper working order and that the heating system functions appropriately...

Страница 38: ...ect the flue pipe system from the induced draft blower 4 Remove the induced draft blower and collector box cover 5 Clean the primary heat exchanger tubes using a wire brush attached to a length of hig...

Страница 39: ...nse signal Sand sensor if coated and or oxidized x Check flue piping for blockage proper length elbows and termination x Verify proper induced draft blower performance x Turn power OFF prior to repair...

Страница 40: ...l for heat IMPROPER FLAME E4 x Short to ground in flame sense circuit x Lingering burner flame x Slow closing gas valve x Correct short at flame sensor or in flame sensor wiring x Check for lingering...

Страница 41: ...Repair replace if necessary x Inspect flue and or inlet air piping for blockage proper length elbows and termination Check drain system Correct as necessary x Check induced draft blower performance C...

Страница 42: ...has lost communications with circulator blower motor MOTOR COMM b1 x Loose wiring connection at circulator motor control leads x Failed circulator blower motor x Failed integrated control module x Ti...

Страница 43: ...et thermostat Call for Service icon illuminated x ComfortNet thermostat scrolls Check Furnace message b6 x Circulator blower motor shuts down for over or under voltage condition x Circulator blower mo...

Страница 44: ...G CYCLE HIGH STAGE PRESSURE SWITCH STUCK OPEN REVERSED 115 VAC POLARITY DATA NOT YET ON NETWORK INVALID MEMORY CARD DATA BLOWER MOTOR NOT RUNNING BLOWER COMMUNICATION ERROR BLOWER HP MIS MATCH BLOWER...

Страница 45: ...30 sec 50 7 5 min 82 30 sec 50 Select desired Comfort Mode profile see profiles above Set switches 5 and 6 to the appropriate ON OFF positions A OFF OFF OFF OFF OFF OFF OFF OFF Model Tap Low Stage Hig...

Страница 46: ...CIRCULATOR BLOWER R 1 GND JUNCTION BOX SWITCH TEMP NEUTRAL 115kBTU MODELS BLOWER COMPARTMENT DOOR SWITCH OPEN WHEN DOOR OPEN C LINE BK 4 NEUTRAL POLARIZED AND C FS 2 PLUG CONNECTION DISCONNECT PU 3 I...

Страница 47: ...47 THIS PAGE LEFT INTENTIONALLY BLANK...

Страница 48: ...48 Goodman Manufacturing Company L P 5151 San Felipe Suite 500 Houston TX 77056 www goodmanmfg com 2011 2012 Goodman Manufacturing Company L P...

Отзывы: