[page 22] | gpelectric.com
SHORE POWER
UNIT READINGS
INVERTER
ON/OFF
CHARGER
ON/OFF
ENTER / SET
BACK
UNIT SETUP
REMOTE SETTINGS
®
SHORE POWER
UNIT READINGS
INVERTER
ON/OFF
CHARGER
ON/OFF
ENTER / SET
BACK
UNIT SETUP
REMOTE SETTINGS
®
SHORE POWER
UNIT READINGS
INVERTER
ON/OFF
CHARGER
ON/OFF
ENTER / SET
BACK
UNIT SETUP
REMOTE SETTINGS
®
UNIT SETUP
01 SEARCH WATTS
UNIT SETUP
02 LowBatCutOut
UNIT SETUP
03 VAC Dropout
1. SEARCH WATTS
The search watts feature helps save the battery power by reducing the
Inverter/
Charger
output to search pulses when there is no detectable load.
If a load greater than the wattage level setting turns on while the Inverter
/ Charger is searching, the inverter starts inverting mode, to power the
appliance.
If the
Inverter/Charger
spends a lot of time searching and you can tolerate small
loads <5 watts, being off, then use the search watts feature. If you have
small loads (digital clocks, satellite receivers, wifi routers) which need to be
on, then the search watts feature should be turned off.
2. LOW BATTERY CUTOUT (LBCO)
The lowbattcutout setting sets the DC voltage level that turns off the
Inverter/
Charger
to protect the battery bank from over-discharge damage. If the battery
bank voltage drops below the LBCO selected set-point continuously for more
than one minute, the fault LED comes on and the Inverter / Charger turns off.
The default setting for the lowbattcutout is 10.5 VDC and the range is 9.00
to 12.2 VDC (increments by 0.01 VDC).
If you want to cycle the batteries slightly - but don’t want to discharge them
more than 20% - then set the LBCO from 11.5 - 12.2 VDC.
In some applications, such as those installed in an off-grid home or when
doing a lot of boon-docking (dry camping) in your RV, you may want to cycle
down to 50% by setting the LBCO from 10.0 to 11.4 VDC. Higher discharge
rates will decrease battery life.
In extreme circumstances you have the ability to discharge the batteries to
80% by setting the LBCO between 9.0 - 9.5 VDC. Higher discharge rates
will decrease battery life.
3. VAC DROPOUT
The VAC dropout shows the minimum AC voltage that must be present at
the AC Input before the Inverter/Charger switches the inverting mode off.
This setting also determines the minimum AC voltage threshold where the AC
Pass through disengages and the inverting mode is switched on to provide
AC power.
The default setting for the VAC dropout is 65 VAC and it cannot be changed
OPERATION