gpelectric.com  |  [page 15]

3.5  MOUNTING PROCEDURE

To mount the GP-ICR-50 in a wall, the opening behind the wall must be at least 2” (5cm) of depth to allow room for the remote and cable.

1.  Cut a 3” x 5” rectangular opening in the wall, ensure there is enough material for the screws to securely mount the remote.
2.  Use the GP-ICR-50 as a template for the 4 holes, mark the positions of the 4 holes with a pencil/pen.
3.  Drill the 4 pilot holes for the #8 x 3/4” screws.
4.  Route one end of the remote control cable through the wall opening to the Inverter / Charger, plug this end into the REMOTE port.
5.  Take the other end of the remote cable and plug it into the rear of the GP-ICR-50.  The remote should power up if the 

Inverter/Charger

 

is connected to the battery bank.  All power to operate the GP-ICR-50 is provided by the 

Inverter/Charger 

through the remote cable.

6.  When the remote powers up, secure the remote control unit to the wall using the four Phillips screws supplied.

Remote Control Port

Remote Cable

Inverter/Charger

Panel / 

Wall

Mounting 

Screws

(304mm)

12”

 

(51mm)

2”

 

 

(124mm)

4.9”

(124mm)

4.9”

 

 

(346mm)

13.6”

(7mm)

(13mm)

.28”

 

(321mm)

12.6”

 

 

.51” 

(205mm)

8.1”

 

(349mm)

13.7”

 

(378mm)

14.9”

 

REMOTE

BATTERY

TEMP

ON/OFF

STATUS

INV. / CHR.

MODE

AC INPUT

INV. AC

OUTPUT

NEG

-

POS

+

BATTERY

TEMP

REMOTE

CAUTION:

• TO PREVENT FIRE, DO NOT COVER OR OBSTRUCT VENTILATION OPENINGS. DO NOT MOUNT IN ZERO-CLEARANCE 

COMPARTMENT. OVERHEATING MAY RESULT.  • RISK OF ELECTRIC SHOCK, DO NOT REMOVE COVER, NO USER 

SERVICEABLE PARTS INSIDE.  REFER SERVICING TO QUALIFIED SERVICE PERSONNEL.  • TO REDUCE RISK OF 

ELECTRIC SHOCK, DO NOT EXPOSE TO RAIN OR SPRAY.  • BATTERY POLARITY MUST BE CORRECT OR DAMAGE WILL 

RESULT.  • PROVIDED WITH INTEGRAL PROTECTION   AGAINST OVERLOADS.  • CHARGE ONLY LEAD ACID TYPE 

RECHARGEABLE BATTERIES, EACH 6 or 12 CELLS IN THE BATTERY.

MISE EN GARDE:

• POUR PRÉVENIR LES RISQUES D’INCENDIE, NE PAS COUVRIR NI OBSTRUER LES OUVERTURES D’AÉRATION. NE 

PAS MONTER LE PRODUIT DANS UN COMPARTIMENT SANS AUCUN DÉGAGEMENT.  RISQUE DE SURCHAUFFE.  • 

RISQUE DE DÉCHARGE ÉLECTRIQUE, NE PAS RETIRER LE COUVERCLE, NE CONTIENT AUCUNE PIÈCE SUSCEPTIBLE 

D’ÊTRE RÉPARÉE PAR L’UTILISATEUR. CONFIEZ L’ENTRETIEN À DU PERSONNEL QUALIFIÉ.  • POUR RÉDUIRE LES 

RISQUES DE DÉCHARGE ÉLECTRIQUE, NE PAS L’EXPOSER À LA PLUIE OU À LA PULVÉRISATION.  • L’ORIENTATION 

DE LA POLARITÉ DES PILES DOIT ÊTRE CORRECTE, AU RISQUE D’ENDOMMAG ER LE PRODUIT.  • FOURNI AVEC UNE 

PROTECTION INTÉGRALE CONTRE LA SURCHARGE.  •  NE CHARGER QUE DES PILES AU PLOMB RECHARGEABLES 

CONTENANT CHACUNE 6 ou 12 CELLULES.

WARNING:

 

•  THIS EQUIPMENT EMPLOYS COMPONENTS THAT TEND TO PRODUCE ARCS OR SPARKS. TO  PREVENT FIRE OR 

EXPLOSION, DO NOT INSTALL IN COMPARTMENTS CONTAINING BATTERIES OR FLAMMABLE MATERIALS.  • RISK 

OF ELECTRIC SHOCK. USE ONLY THE GROUND-FAULT CIRCUIT-INTERRUPTER RECEPTACLE OR CIRCUIT 

BREAKER SPECIFIED IN THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THIS UNIT. OTHER 

TYPES MAY FAIL TO OPERATE PROPERLY WHEN CONNECTED TO THIS UNIT.  • RISK OF ELECTRIC SHOCK, 

HEATSINKS ARE NOT BONDED TO GROUND, TEST BEFORE TOUCHING.  • INTENDED FOR CONTINUOUS DUTY.     

AVERTISSEMENT:

• CET ÉQUIPEMENT EMPLOIE DES COMPOSANTS POUVANT PROVOQUER DES ARCS ÉLECTRIQUES OU DES 

ÉTINCELLES. POUR PRÉVENIR LES RISQUES D’INCENDIE OU D’EXPLOSION, NE PAS INSTALLER LE PRODUIT 

DANS UN COMPARTIMENT CONTENANT DES PILES OU DES MATÉRIAUX INFLAMMABLES.  • RISQUE DE 

DÉCHARGE ÉLECTRIQUE. UTILISER UNIQUEMENT LE RÉCEPTACLE D’INTERRUPTEUR DE CIRCUIT DE MISE À LA 

MASSE OU LE COUPE-CIRCUIT INDIQUÉS DANS LE MANUEL D’INSTALLATION ET D’UTILISATION FOURNI AVEC CE 

PRODUIT. LES AUTRES TYPES PEUVENT NE PAS FONCTIONNER CORRECTEMENT LORSQU’ILS SONT 

CONNECTÉS À CE PRODUIT.  • RISQUE DE DÉCHARGE ÉLECTRIQUE, PUITS THERMIQUES NON MIS À LA TERRE, 

TESTER AVANT DE TOUCHER.  • PRÉVU POUR UNE UTILISATION CONTINUE. 

DANGER:

• TO REDUCE THE RISK OF EXPLOSION - DO NOT INSTALL IN MACHINERY SPACE OR AREA IN WHICH IGNITION 

- PROTECTED EQUIPMENT IS REQUIRED.

• POUR RÉDUIRE LE RISQUE D’EXPLOSION, NE PAS INSTALLER LE PRODUIT DANS UN COMPARTIMENT 

MACHINE OU UNE ZONE CONTENANT UN ALLUMAGE — L’ÉQUIPEMENT PROTÉGÉ EST EXIGÉ

CB2

INPUT

50A

CB1

INPUT

50A

 

 

 

REMOTE

BATTERY

TEMP

ON/OFF

STATUS

INV. / CHR.

MODE

AC INPUT

INV. AC

OUTPUT

NEG

-

POS

+

CAUTION:

• TO PREVENT FIRE, DO NOT COVER OR OBSTRUCT VENTILATION OPENINGS. DO NOT MOUNT IN ZERO-CLEARANCE 

COMPARTMENT. OVERHEATING MAY RESULT.  • RISK OF ELECTRIC SHOCK, DO NOT REMOVE COVER, NO USER 

SERVICEABLE PARTS INSIDE.  REFER SERVICING TO QUALIFIED SERVICE PERSONNEL.  • TO REDUCE RISK OF 

ELECTRIC SHOCK, DO NOT EXPOSE TO RAIN OR SPRAY.  • BATTERY POLARITY MUST BE CORRECT OR DAMAGE WILL 

RESULT.  • PROVIDED WITH INTEGRAL PROTECTION   AGAINST OVERLOADS.  • CHARGE ONLY LEAD ACID TYPE 

RECHARGEABLE BATTERIES, EACH 6 or 12 CELLS IN THE BATTERY.

MISE EN GARDE:

• POUR PRÉVENIR LES RISQUES D’INCENDIE, NE PAS COUVRIR NI OBSTRUER LES OUVERTURES D’AÉRATION. NE 

PAS MONTER LE PRODUIT DANS UN COMPARTIMENT SANS AUCUN DÉGAGEMENT.  RISQUE DE SURCHAUFFE.  • 

RISQUE DE DÉCHARGE ÉLECTRIQUE, NE PAS RETIRER LE COUVERCLE, NE CONTIENT AUCUNE PIÈCE SUSCEPTIBLE 

D’ÊTRE RÉPARÉE PAR L’UTILISATEUR. CONFIEZ L’ENTRETIEN À DU PERSONNEL QUALIFIÉ.  • POUR RÉDUIRE LES 

RISQUES DE DÉCHARGE ÉLECTRIQUE, NE PAS L’EXPOSER À LA PLUIE OU À LA PULVÉRISATION.  • L’ORIENTATION 

DE LA POLARITÉ DES PILES DOIT ÊTRE CORRECTE, AU RISQUE D’ENDOMMAG ER LE PRODUIT.  • FOURNI AVEC UNE 

PROTECTION INTÉGRALE CONTRE LA SURCHARGE.  •  NE CHARGER QUE DES PILES AU PLOMB RECHARGEABLES 

CONTENANT CHACUNE 6 ou 12 CELLULES.

WARNING:

 

•  THIS EQUIPMENT EMPLOYS COMPONENTS THAT TEND TO PRODUCE ARCS OR SPARKS. TO  PREVENT FIRE OR 

EXPLOSION, DO NOT INSTALL IN COMPARTMENTS CONTAINING BATTERIES OR FLAMMABLE MATERIALS.  • RISK 

OF ELECTRIC SHOCK. USE ONLY THE GROUND-FAULT CIRCUIT-INTERRUPTER RECEPTACLE OR CIRCUIT 

BREAKER SPECIFIED IN THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THIS UNIT. OTHER 

TYPES MAY FAIL TO OPERATE PROPERLY WHEN CONNECTED TO THIS UNIT.  • RISK OF ELECTRIC SHOCK, 

HEATSINKS ARE NOT BONDED TO GROUND, TEST BEFORE TOUCHING.  • INTENDED FOR CONTINUOUS DUTY.     

AVERTISSEMENT:

• CET ÉQUIPEMENT EMPLOIE DES COMPOSANTS POUVANT PROVOQUER DES ARCS ÉLECTRIQUES OU DES 

ÉTINCELLES. POUR PRÉVENIR LES RISQUES D’INCENDIE OU D’EXPLOSION, NE PAS INSTALLER LE PRODUIT 

DANS UN COMPARTIMENT CONTENANT DES PILES OU DES MATÉRIAUX INFLAMMABLES.  • RISQUE DE 

DÉCHARGE ÉLECTRIQUE. UTILISER UNIQUEMENT LE RÉCEPTACLE D’INTERRUPTEUR DE CIRCUIT DE MISE À LA 

MASSE OU LE COUPE-CIRCUIT INDIQUÉS DANS LE MANUEL D’INSTALLATION ET D’UTILISATION FOURNI AVEC CE 

PRODUIT. LES AUTRES TYPES PEUVENT NE PAS FONCTIONNER CORRECTEMENT LORSQU’ILS SONT 

CONNECTÉS À CE PRODUIT.  • RISQUE DE DÉCHARGE ÉLECTRIQUE, PUITS THERMIQUES NON MIS À LA TERRE, 

TESTER AVANT DE TOUCHER.  • PRÉVU POUR UNE UTILISATION CONTINUE. 

DANGER:

• TO REDUCE THE RISK OF EXPLOSION - DO NOT INSTALL IN MACHINERY SPACE OR AREA IN WHICH IGNITION 

- PROTECTED EQUIPMENT IS REQUIRED.

• POUR RÉDUIRE LE RISQUE D’EXPLOSION, NE PAS INSTALLER LE PRODUIT DANS UN COMPARTIMENT 

MACHINE OU UNE ZONE CONTENANT UN ALLUMAGE — L’ÉQUIPEMENT PROTÉGÉ EST EXIGÉ

CB2

INPUT

50A

CB1

INPUT

50A

CAUTION:

• TO PREVENT FIRE, DO NOT COVER OR OBSTRUCT VENTILATION OPENINGS. DO NOT MOUNT IN ZERO-CLEARANCE 

COMPARTMENT. OVERHEATING MAY RESULT.  • RISK OF ELECTRIC SHOCK, DO NOT REMOVE COVER, NO USER 

SERVICEABLE PARTS INSIDE.  REFER SERVICING TO QUALIFIED SERVICE PERSONNEL.  • TO REDUCE RISK OF 

ELECTRIC SHOCK, DO NOT EXPOSE TO RAIN OR SPRAY.  • BATTERY POLARITY MUST BE CORRECT OR DAMAGE WILL 

RESULT.  • PROVIDED WITH INTEGRAL PROTECTION   AGAINST OVERLOADS.  • CHARGE ONLY LEAD ACID TYPE 

RECHARGEABLE BATTERIES, EACH 6 or 12 CELLS IN THE BATTERY.

MISE EN GARDE:

• POUR PRÉVENIR LES RISQUES D’INCENDIE, NE PAS COUVRIR NI OBSTRUER LES OUVERTURES D’AÉRATION. NE 

PAS MONTER LE PRODUIT DANS UN COMPARTIMENT SANS AUCUN DÉGAGEMENT.  RISQUE DE SURCHAUFFE.  • 

RISQUE DE DÉCHARGE ÉLECTRIQUE, NE PAS RETIRER LE COUVERCLE, NE CONTIENT AUCUNE PIÈCE SUSCEPTIBLE 

D’ÊTRE RÉPARÉE PAR L’UTILISATEUR. CONFIEZ L’ENTRETIEN À DU PERSONNEL QUALIFIÉ.  • POUR RÉDUIRE LES 

RISQUES DE DÉCHARGE ÉLECTRIQUE, NE PAS L’EXPOSER À LA PLUIE OU À LA PULVÉRISATION.  • L’ORIENTATION 

DE LA POLARITÉ DES PILES DOIT ÊTRE CORRECTE, AU RISQUE D’ENDOMMAG ER LE PRODUIT.  • FOURNI AVEC UNE 

PROTECTION INTÉGRALE CONTRE LA SURCHARGE.  •  NE CHARGER QUE DES PILES AU PLOMB RECHARGEABLES 

CONTENANT CHACUNE 6 ou 12 CELLULES.

WARNING:

 

•  THIS EQUIPMENT EMPLOYS COMPONENTS THAT TEND TO PRODUCE ARCS OR SPARKS. TO  PREVENT FIRE OR 

EXPLOSION, DO NOT INSTALL IN COMPARTMENTS CONTAINING BATTERIES OR FLAMMABLE MATERIALS.  • RISK 

OF ELECTRIC SHOCK. USE ONLY THE GROUND-FAULT CIRCUIT-INTERRUPTER RECEPTACLE OR CIRCUIT 

BREAKER SPECIFIED IN THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THIS UNIT. OTHER 

TYPES MAY FAIL TO OPERATE PROPERLY WHEN CONNECTED TO THIS UNIT.  • RISK OF ELECTRIC SHOCK, 

HEATSINKS ARE NOT BONDED TO GROUND, TEST BEFORE TOUCHING.  • INTENDED FOR CONTINUOUS DUTY.     

AVERTISSEMENT:

• CET ÉQUIPEMENT EMPLOIE DES COMPOSANTS POUVANT PROVOQUER DES ARCS ÉLECTRIQUES OU DES 

ÉTINCELLES. POUR PRÉVENIR LES RISQUES D’INCENDIE OU D’EXPLOSION, NE PAS INSTALLER LE PRODUIT 

DANS UN COMPARTIMENT CONTENANT DES PILES OU DES MATÉRIAUX INFLAMMABLES.  • RISQUE DE 

DÉCHARGE ÉLECTRIQUE. UTILISER UNIQUEMENT LE RÉCEPTACLE D’INTERRUPTEUR DE CIRCUIT DE MISE À LA 

MASSE OU LE COUPE-CIRCUIT INDIQUÉS DANS LE MANUEL D’INSTALLATION ET D’UTILISATION FOURNI AVEC CE 

PRODUIT. LES AUTRES TYPES PEUVENT NE PAS FONCTIONNER CORRECTEMENT LORSQU’ILS SONT 

CONNECTÉS À CE PRODUIT.  • RISQUE DE DÉCHARGE ÉLECTRIQUE, PUITS THERMIQUES NON MIS À LA TERRE, 

TESTER AVANT DE TOUCHER.  • PRÉVU POUR UNE UTILISATION CONTINUE. 

DANGER:

• TO REDUCE THE RISK OF EXPLOSION - DO NOT INSTALL IN MACHINERY SPACE OR AREA IN WHICH IGNITION 

- PROTECTED EQUIPMENT IS REQUIRED.

• POUR RÉDUIRE LE RISQUE D’EXPLOSION, NE PAS INSTALLER LE PRODUIT DANS UN COMPARTIMENT 

MACHINE OU UNE ZONE CONTENANT UN ALLUMAGE — L’ÉQUIPEMENT PROTÉGÉ EST EXIGÉ

CB2

INPUT

50A

CB1

INPUT

50A

Temperature Sensor

®

®

MODEL: GP-IC2000-12 Inverter / Charger

gpelectric.com

Inverter Operation

 

Continuous Output Power (-20~40°C): 2000VA

 DC Input: 12.6V

 Maximum Continuous Input Current: 267ADC

 Nominal  AC Output Voltage/Frequency:  120VAC(±5%)/60Hz(±0.1Hz)

 Maximum Continuous Output Current: 16.7AAC 

 Surge Power: 3400 Real Watts (5 seconds)

 THD: <5%

Charger Operation

Bypass Operation

 

Continuous Charger Current  (-20~40°C) : 100 [email protected] VDC nominal with 120 VAC / 60Hz (15 AAC) input

Input / Output Voltage: 120 (L1-N) / 120 (L2-N) VAC

 Input Voltage: 120 VAC

 Maximum AC Input Current: 50 AAC

 Maximum Power: 12000 VA

 DC Output Range: 8.5 to 16.5VDC

 Grid Input Frequency: 60Hz

 Generator Input Frequency Range: 50 to 70Hz

 Power Factor: >0.98

Conforms to UL 458 (6th Ed.) and UL STD 1741 (2nd. Ed.) 

 Certified to CSA C22.2 No. 107.1-01

5GW2

MQ7275

MARINE POWER INVERTER

5DA7

E198012

POWER INVERTER

E483757

®

MODEL: GP-IC2000-12 Inverter / Charger

gpelectric.com

Inverter Operation

 

Continuous Output Power (-20~40°C): 2000VA

 DC Input: 12.6V

 Maximum Continuous Input Current: 267ADC

 Nominal  AC Output Voltage/Frequency:  120VAC(±5%)/60Hz(±0.1Hz)

 Maximum Continuous Output Current: 16.7AAC 

 Surge Power: 3400 Real Watts (5 seconds)

 THD: <5%

Charger Operation

Bypass Operation

 

Continuous Charger Current  (-20~40°C) : 100 [email protected] VDC nominal with 120 VAC / 60Hz (15 AAC) input

Input / Output Voltage: 120 (L1-N) / 120 (L2-N) VAC

 Input Voltage: 120 VAC

 Maximum AC Input Current: 50 AAC

 Maximum Power: 12000 VA

 DC Output Range: 8.5 to 16.5VDC

 Grid Input Frequency: 60Hz

 Generator Input Frequency Range: 50 to 70Hz

 Power Factor: >0.98

Conforms to UL 458 (6th Ed.) and UL STD 1741 (2nd. Ed.) 

 Certified to CSA C22.2 No. 107.1-01

5GW2

MQ7275

MARINE POWER INVERTER

5DA7

E198012

POWER INVERTER

E483757

®

MODEL: GP-IC2000-12 Inverter / Charger

gpelectric.com

Inverter Operation

 

Continuous Output Power (-20~40°C): 2000VA

 DC Input: 12.6V

 Maximum Continuous Input Current: 267ADC

 Nominal  AC Output Voltage/Frequency:  120VAC(±5%)/60Hz(±0.1Hz)

 Maximum Continuous Output Current: 16.7AAC 

 Surge Power: 3400 Real Watts (5 seconds)

 THD: <5%

Charger Operation

Bypass Operation

 

Continuous Charger Current  (-20~40°C) : 100 [email protected] VDC nominal with 120 VAC / 60Hz (15 AAC) input

Input / Output Voltage: 120 (L1-N) / 120 (L2-N) VAC

 Input Voltage: 120 VAC

 Maximum AC Input Current: 50 AAC

 Maximum Power: 12000 VA

 DC Output Range: 8.5 to 16.5VDC

 Grid Input Frequency: 60Hz

 Generator Input Frequency Range: 50 to 70Hz

 Power Factor: >0.98

Conforms to UL 458 (6th Ed.) and UL STD 1741 (2nd. Ed.) 

 Certified to CSA C22.2 No. 107.1-01

5GW2

MQ7275

MARINE POWER INVERTER

5DA7

E198012

POWER INVERTER

E483757

4.9"

(12.45cm)

2.8"

(7.1cm)

INSTALLATION

Содержание DOMETIC GP-ICR-50

Страница 1: ...ADINGS INVERTER ON OFF CHARGER ON OFF ENTER SET BACK UNIT SETUP REMOTE SETTINGS 2022 Go Power Worldwide Technical Support and Product Information gpelectric com Go Power Dometic 201 710 Redbrick Stree...

Страница 2: ...he Go Power Remote Control Please retain this manual for future reference Product Packaging Please safely store the packing the GP ICR 50 was delivered in or please recycle the packaging components as...

Страница 3: ...EM OVERVIEW 10 3 2 UNIT DIMENSIONS 14 3 3 MOUNTING REQUIREMENTS 14 3 4 INSTALLATION TOOLS 14 3 5 MOUNTING PROCEDURE 15 4 OPERATION 16 4 1 REMOTE NAVIGATION 16 4 2 SUB MENU ITEMS OPTIONS 18 4 3 SHORE P...

Страница 4: ...proper operation may have a risk of electric shock or damage to equipment and property GENERAL SAFETY WARNING Limitations on Use CAUTION Equipment Damage This equipment is NOT intended for use with li...

Страница 5: ...be impaired EQUIPMENT SAFETY WARNING Lethal Voltage Review the system configuration to identify all possible sources of energy Ensure ALL sources of power are disconnected before performing any insta...

Страница 6: ...ther electrical parts Never charge a frozen battery Never use old or untested batteries Check each battery s label for age type and date code to ensure all batteries are identical If a battery must be...

Страница 7: ...at the information is accurate correct reliable or current The specifications in this manual are for reference purposes only and are subject to change without notice For additional information please...

Страница 8: ...e remote control like brightness power save mode Unit Setup Menu When the icon is pointing to unit readings you are in the unit settings menu These are the Inverter Charger main settings like search w...

Страница 9: ...function of the Inverter Charger Green Inverting No colour Not Inverting RJ 11 Cable Entry Point Remote control cable entry point Mounting Holes These 4 holes are used to attach the GP ICR 50 to a su...

Страница 10: ...diagrams on pages 12 15 show how the GP ICR 50 and Inverter Charger typically installed in a mobile RV application The diagrams show where the remote and Inverter Charger are installed and how the mob...

Страница 11: ...ble to Battery Bank Battery Bank Cables From Solar Charge Controller GP IC Remote AC Power OUTPUT to RV appliances IC Series Inverter Charger IC Series Inverter Charger Cables to from Battery Bank AC...

Страница 12: ...ransfer Switch Solar Panel Solar Panel Solar Charge Controller Refrigerator Vent Cover or Cable Entry Plate Fuse Battery Temperature Sensor Typical RV Solar Kit sold separately by Go Power To Battery...

Страница 13: ...wer 120 240 VAC el Sub Panel 120 VAC 240 VAC cabin install Remote Control Optional Battery Disconnect Switch not required if circuit breaker is used Battery Bank Fuse or Circuit Breaker IC Series Inve...

Страница 14: ...n dry and protected Make sure the LCD screen is visible and access to the menu navigation buttons is clear and un obstructed Always check for hidden electrical wires pipes and cables before drilling c...

Страница 15: ...8 x 3 4 screws 4 Route one end of the remote control cable through the wall opening to the Inverter Charger plug this end into the REMOTE port 5 Take the other end of the remote cable and plug it into...

Страница 16: ...UNIT SETUP REMOTE SETTINGS Go Power Initializing DC Status 11 68 V 0 0 A DC Status 11 68 V 0 0 A DC Status 11 68 V 0 0 A DC Status 11 68 V 0 0 A DC Status 11 68 V 0 0 A 1 Press the Inverter ON OFF but...

Страница 17: ...S 4 To navigate through the sub menu options first enter the menu using the ENTER SET button 5 Then press the down menu select button to move to the next sub menu option notice the menu arrow does not...

Страница 18: ...03 VAC Dropout 65V 65V 04 Max Cha Time 0 0 25 5 HR 12 0 HR 05 Battery Type Gel Flooded AGM 1 AGM 2 Custom AGM 1 06 Charge Rate 50 IC 2000 40 IC 3000 80 07 Final Charge Multi Stage Float Silent Multi...

Страница 19: ...two AC power sources The IC Series has 2 inputs AC HOT 1 and AC HOT 2 but the current is only monitored on AC HOT 1 If you wire the Inverter Charger in Single In Single Out 50A configurations see the...

Страница 20: ...d the Inverter Charger is inverting A positive value e g 40 0A shows that the batteries are charging and the Inverter Charger is in charging mode State indicator PT Pass Through PS Powershare CHG Char...

Страница 21: ...temperature of the field effect transistors FETs inside the Inverter Charger 4 5 UNIT SETUP MENU Menu Heading Selections Adjustments Range Default Setting Unit Setup 01 Search Watts OFF 5 50W 5W 02 Lo...

Страница 22: ...he Inverter Charger to protect the battery bank from over discharge damage If the battery bank voltage drops below the LBCO selected set point continuously for more than one minute the fault LED comes...

Страница 23: ...ettings can be modified and set when the custom battery type option is selected Absorb Sets the level at which the charging voltage is held constant during an absorption cycle The default value is 14...

Страница 24: ...ow charge rates a simple guideline is C 20 so a slow charge rate for the 400 Amp hour capacity battery bank will have a slow charge rate of 20 Amps hour 400 20 20 which means setting the charge rate t...

Страница 25: ...ries produces hydrogen and oxygen gas Ensure the battery compartment has adequate ventilation to dissipate this gas to avoid explosions Ensure your batteries can be equalized only equalize batteries t...

Страница 26: ...udent to make a note of these two numbers for future reference If you ever need to contact Go Power Technical support these two numbers will be required to help the customer service personnel help you...

Страница 27: ...the contrast of the LCD screen and the back light brightness for the best looking display based on the current lighting conditions and viewing angle The default setting is 80 and the range is 0 100 10...

Страница 28: ...Beeping Counts for Error Modes Beep Counts Description 1 UTP Under Temp Protection 2 OTP Over Temp Protection 3 OVP Over Voltage Protection 4 UVP Under Voltage Proection 5 Short circuit or OLP Over Lo...

Страница 29: ...tion of our website to troubleshoot the problem If trouble persists 1 Call your Go Power Technical Support team 1 866 247 6527 or 2 Return defective product to place of purchase Unless approved by Go...

Страница 30: ...being recycled properly is tricky If your in doubt just ask Recyclers that are certified should gladly show you their certification If the re cycler is certified chances are very high that they are re...

Страница 31: ......

Страница 32: ...IT SETUP 02 LowBatCutOut UNIT SETUP 03 VAC Dropout UNIT SETUP 04 Max Cha Time 01 SEARCH WATTS OFF 50W OFF 02 LowBatCutOut 9 00V 10 5V 10 5V 03 VAC Dropout 80V 85V 85V 04 Max Cha Time 0 0HR 25 5HR 12 0...

Страница 33: ...GM1 AGM2 Custom AGM1 06 Charge Rate 0 100 80 07 Final Charge MUTI STAGE FLOAT STAGE SILENT STAGE MUTI STAGE 08 ABS Cha Time 0 5Hr 24 0Hr 2 0Hr Power Save OFF 60MIN OFF Screen Setup Contrast 00 100 80...

Страница 34: ...2022 Go Power Worldwide Technical Support and Product Information gpelectric com Go Power 201 710 Redbrick Street Victoria BC V8T 5J3 Tel 1 866 247 6527 79498_MAN_GP_ICR_50_Rev_C...

Отзывы: