5
Installation
FSH
−
2
−
PH
1. Before unpacking, review dimensions and clearances shown in
Section 1.03
and determine whether the
location selected for installation is suitable.
2. Keep the unit and the surrounding area free and clear of combustible materials.
3. Do not allow obstructions in the area around the exhaust outlet on top of hood. Minimum clearance
required between the top of diverter and ceiling is
0.00” ...
it is advisable to provide some clearance for ease
of movement should a future need arise.
4. Provide adequate space for future servicing and proper operation.
5. After final positioning, be sure to adjust the leveling legs so that the unit is level, side to side, front to back
and corner to corner.
The legs must be installed on hood during the installation process.
6. Before operation, make sure the unit is secured in position and cannot be unintentionally move.
The following sections summarize procedures for proper installation. To help avoid personal injury and damage to the
equipment, be sure to adhere to all installation instructions.
Equipment installation is the complete responsibility of the purchaser. It is advisable to engage the services of
professional commercial kitchen equipment specialists, licensed electricians, and qualified HVAC contractors to assist
with the details of installation.
Giles Technical Suppor
t @ 800.554.4537 is available for assistance, if necessary.
2. Installation
2.01 Location
•
DO NOT ALTER, ADD ATTACHMENTS OR OTHERWISE MODIFY THE EQUIPMENT.
•
Failure to comply with installation requirements as specified by the Giles Hood Approval Letter will void the
factory warranty.
IMPORTANT!!
Before installing a
GILES
Recirculating Ventless Hood system ensure that ...
A. all necessary approvals have been obtained from local code authorities,
B. fryer to be used with the hood is within the hood’s listing limitations stated in Section 2.04, and
C. the installation site complies with all specific requirements and limitations as outlined in the
GFSE
Recirculating/Ventless Hood Approval Letter (HAL)
... this document is available for review & download at
www.gfse.com
on the
HOME
page, under
SUPPORT
on the
VENTLESS SUPPORT DOCUMENTS
page.
To ensure satisfactory hood performance after installation, the site MUST comply with all minimum
requirements for kitchen size (>300 sq ft), ceiling height, fresh outdoor air make
up, room air exchange rate,
supplemental exhaust ventilation, clearances, and etc. as stipulated in the
Hood Approval Letter (HAL)
.
•
MAXIMUM of 1 hood per 300 sq ft of commercial kitchen space.
•
Fresh outside air make
up must be equal to a MINIMUM of 15 complete room air exchanges per hour.
•
Giles makes no representation as to a proper design or layout of any food service establishment in which
ventless hoods will be used. Further, Giles does not perform site inspections prior to installation of its
equipment.
•
NOTE:
Hood produces a sound level of approximately
65 dB
when in operation.
Содержание FSH-2-PH
Страница 4: ......
Страница 14: ...4 Introduction FSH 2 PH ...
Страница 36: ...26 Overview FSH 2 PH ...
Страница 45: ...35 Operation FSH 2 PH NOTES ...
Страница 53: ...43 Cleaning Maintenance FSH 2 PH ...
Страница 56: ...46 Troubleshooting FSH 2 PH ...
Страница 58: ...48 Parts List FSH 2 PH 1 2 3 5 6 8 7 4 Not shown 7 02 Ventless Hood Front ...
Страница 60: ...50 Parts List FSH 2 PH 4 7 5 6 1 2 3 8 9 10 11 12 13 14 15 ILS Only Not Shown 7 03 Control Box ...
Страница 62: ...52 Parts List FSH 2 PH 3 4 1 2 6 10 7 9 11 13 12 5 8 17 14 16 18 19 20 21 22 23 24 15 7 04 Ventless Hood Rear ...
Страница 64: ...54 Parts List FSH 2 PH Notes ...
Страница 65: ......