The fire suppression system installed in the
Giles
ventless hood is an
ANSUL® R
‐
102 Restaurant Fire Suppression
System (UL
‐
710B Listed)
.
Final field set
‐
up, charging, certification and arming of the system must be performed
by an authorized Ansul distributor/dealer in accordance with the system listing.
The fire suppression system is designed and UL
listed to provide fire protection for the fryer. It is a mechanically
activated system that protects continuously. This factory
installed system is self
contained and includes all piping,
nozzles (appliance & plenum), Automan release mechanism, detector link brackets, conduit for link cable, exhaust
outlet fire damper and a 1
1/2 gal. stainless steel wet chemical suppressant storage tank.
.
Field set
up by an Ansul agent shall include, but may not be limited to, installation of proper fusible detector links
and cable, filling & installing the provided suppressant storage tank, installing a remote manual activation station,
installing a compressed gas firing cartridge, testing, certifying and arming the system.
Necessary parts and labor
for system field set
‐
up is the responsibility of the customer and is not included with hood purchase
.
2.05 Fire Suppression System
12
Installation
FSH
−
2
−
PH
.XXX = ±.020
SHEET METAL DEPT.
DECIMALS
ANGULAR ± 2°
DECIMALS
MACHINE SHOP
.XX = ±.010
.XX = ±.031
TITLE:
MONTGOMERY, ALABAMA
RESTRICTED CON
THIS DRAWING AND ALL THE INFORMA
EXCLUSIVE PROPERTY OF GILES ENTE
ON A CONFIDENTIAL BASIS. THE RECIP
DRAWING, TO RETURN IT UPON REQUE
DRAWING OR THE INFORMATION SHOW
PARTY WITHOUT THE PRIOR WRITTEN
REF, 3 VIEW
FSH-2
SUBJECT/MODEL:
ENTERPRISES, INC.
SYM.
REVISIONS
DESCRIPTION
60A RECEPT.
NEMA 15-60R
(SUPPLIED WITH
3 PH ONLY)
APPLIANCE
STAND OFF
IN HOOD
26 7/8
683
24 3/8
619
20 1/4
515
INSIDE
22 3/16
564
24 1/8
613
67 1/8 1705
31 7/16
799
30 15/16
787
28 1/8
714
3
76
38 1/16 967
46 1/8 1172
FIRE EXTING
MANUAL PULL
CONNECTION
HOOD AND APPLIANCE
INTERLOCK CONNECTION
( 1 PHASE ONLY)
POWER CONNECTION
(HOOD ONLY 1PHASE)
(HOOD AND APPLIANCE 3 PH)
85 7/16 2170
7'
-2
7/16"
2195
M
IN
. T
O
C
E
IL
IN
G
AIR FLOW
C
CHANGE TO LOW PROFILE DIVERTER
B
CHANGED TO 3-WAY AIR DIVERTER
A
RELEASE FOR PRODUCTION
FIRE ALARM TIE-IN BOX
INCHES [mm]
2.04.2
Hood Clearances
SIDE
FRONT
BACK
Содержание FSH-2-PH
Страница 4: ......
Страница 14: ...4 Introduction FSH 2 PH ...
Страница 36: ...26 Overview FSH 2 PH ...
Страница 45: ...35 Operation FSH 2 PH NOTES ...
Страница 53: ...43 Cleaning Maintenance FSH 2 PH ...
Страница 56: ...46 Troubleshooting FSH 2 PH ...
Страница 58: ...48 Parts List FSH 2 PH 1 2 3 5 6 8 7 4 Not shown 7 02 Ventless Hood Front ...
Страница 60: ...50 Parts List FSH 2 PH 4 7 5 6 1 2 3 8 9 10 11 12 13 14 15 ILS Only Not Shown 7 03 Control Box ...
Страница 62: ...52 Parts List FSH 2 PH 3 4 1 2 6 10 7 9 11 13 12 5 8 17 14 16 18 19 20 21 22 23 24 15 7 04 Ventless Hood Rear ...
Страница 64: ...54 Parts List FSH 2 PH Notes ...
Страница 65: ......