SECTION 4 - INSTALLATION
4
Field Communication Wiring
Two-wire Connections for AFP/DCM2 Assembly
The two-wire connections to the AFP/DCM2 are conceptually the same for all unit types. Figure 17 shows
the general block diagram. In all cases, the M02993A005 is used to connect the POS pump and CRIND
two-wire cable to P300 on the AFP/DCM2.
Figure 17: Block Diagram - Two-wire Connections for AFP/DCM2 Assembly
High-speed data interface
(DCM2 only). Enabled with J3.
P300
Current Loop
Interface
Current Loop
Interface
Signal Conversion and
Routing Logic
P300
Red/Yellow
Blue/Yellow
MOC/Generic Selection Jumper
(AFP = JP5, DCM2 = JP4)
P302A to Side A, PIP3
P302B to Side B, PIP3
Note: For DCM2, the pump two-wire (red/yellow) cable is for Applause Media System.
Field Wiring and Jumper Configuration Chart
If you are using the dedicated high-speed connection, refer to installation instructions in
“Dedicated High-Speed Field Wiring (Non-POS) Instructions (DCM2.2 only)”
POS
AFP Board
DCM2 Board
Passport
Blue/Yellow
POS CRIND Current Loop
Blue/Yellow
NC
Red/Yellow
NC
Red/Yellow
POS CRIND Current Loop
J5
Install
J4
Install
Third-party
Blue/Yellow
POS CRIND Current Loop
Remove
Blue/Yellow
POS CRIND Current Loop
Remove
Red/Yellow
POS Pump Current Loop
Red/Yellow
POS Pump Current Loop
J5
Remove
J4
Remove
High-speed data sent
through Back Room
Communication
Module (BRCM) 2
Not Applicable
J3
Install
Note: J5 is located at the bottom right corner of AFP. J3 and J4 located at the bottom left corner of DCM2.
Содержание FlexPay IV CRIND
Страница 1: ...MDE 5222F December 2018 FlexPay IV CRIND Retrofit Kit Installation Instructions for Encore 300 500...
Страница 2: ...This page is intentionally left blank...
Страница 8: ...MDE 5222F 4 SECTION 1 INTRODUCTION 1 This page is intentionally left blank...
Страница 50: ...MDE 5222F 46 SECTION 4 INSTALLATION 4 This page is intentionally left blank...
Страница 59: ...55 SECTION 6 APPENDICES MDE 5222F 6 Figure 7 Cable Block Diagram for FlexPay IV DCM2 2...