Each opening shall have a minimum free area of 

one (1) in

2

/1,000 BTU (22.0 cm

2

/kW)

 of the total 

input rating of all gas appliances in the confined 

space, but not less than one hundred (100) square 

inches (645 cm

2

). One opening shall commence within 

six (6) inches (15.2 cm) of the top and one within six (6) 

inches (15.2 cm) of the bottom of the enclosure.

2) All Air From Outdoors:

  The confined space shall be provided with two  

permanent openings, one commencing within six (6) 

inches (15.2 cm) of the top and one commencing 

within six (6) inches (15.2 cm) from the bottom of the 

enclosure. The openings shall communicate directly 

or by ducts, with the outdoors or spaces (crawl or 

attic) that freely communicate with the outdoors.

  A) When communicating directly with the outdoors, 

each opening shall have a minimum free area of 

one (1) in

2

/4,000 BTU (5.5 cm

2

/kW) 

of the total input 

rating of all gas appliances in the enclosure (see 

Figure 5).

 B) When communicating with the outdoors through 

vertical ducts, each opening shall have a minimum 

free area of 

one (1) in

2

/4,000 BTU (5.5 cm

2

/kW)

 of 

the total input rating of all gas appliances in the 

enclosure (see Figure 6).

 C) When communicating with the outdoors through 

horizontal ducts, each opening shall have a minimum 

free area of 

one (1) in

2

/2,000 BTU (11.0 cm

2

/kW)

 of 

the total input rating of all gas appliances in the 

enclosure (see Figure 7).

When ducts are used, they shall be of the same  

cross-sectional area as the free area of the openings 

to which they connect. The minimum short side 

dimension of rectangular air ducts shall not be less 

than three (3) inches (7.62 cm).

Louvers and Grilles

In calculating free area for ventilation and combustion 

air supply openings, consideration must be given to 

the blocking effect of louvers, grilles, or screens pro-

tecting the openings. Screens must not be smaller 

5

INSTALLATION INSTRUCTIONS

Confined space

Confined space

Permanent 

opening

--------------

1 in

2

/1,000 BTU/h

(min. : 100 in

2

)

Outlet air to attic

1 in

2

/4,000 BTU/h

Vent 

to outdoors

Install above 

insulation

Inlet air from the 

crawl space

1 in

2

/4,000 BTU/h

Open foundation vent

Install above 

insulation

Vent 

to outdoors

Outlet air to attic

1 in

2

/4,000 BTU/h

Confined 

space

Inlet air duct

Inlet air duct

1 in

2

/4,000 BTU/h

12'' max.

Inlet

Outlet

Outdoor air duct

1 in

2

/2,000 BTU/h

1 in

2

/2,000 BTU/h

Confined 

space

Alternate

air inlet

Confined

space

Confined

space

18'' 

24'' 

Espace restreint

18'' 

24'' 

Entrée d'air

alternative

1 po

2

/2 000 BTU/h

1 po

2

/2 000 BTU/h

Conduite d'air extérieur

Sortie

Entrée

12'' max.

Conduite d'entrée d'air

Conduite

d'entrée d'air

1 po

2

/4 000 BTU/h

Évent de 

fondation

1 po

2

/4 000 BTU/h

Entrée d'air du

sous-sol

Espace 

restreint

Installez 

au-dessus 

de l'isolation

Installez 

au-dessus 

de l'isolation

Évent menant

à l'extérieur

Sortie d'air 

au grenier

1 po

2

/4 000 BTU/h

Ouverture

permanente

--------------

1 po

2

/1 000 BTU/h 

1 po

2

1 000 BTU/h 

(min. : 100 po

2

)

Espace restreint

Espace

restreint

Évent menant

à l'extérieur

Espace 

restreint

Sortie d'air 

au grenier

1 po

2

/4 000 BTU/h

Espace 

restreint

Figure 3

Figure 4

Figure 5

Figure 6

Figure 7

Figure 2

Permanent 

opening

--------------

1 square inch/

1,000 BTU/h

Ouverture 

permanente

--------------

Figure 7

Confined space

Confined space

Permanent 

opening

--------------

1 in

2

/1,000 BTU/h

(min. : 100 in

2

)

Outlet air to attic

1 in

2

/4,000 BTU/h

Vent 

to outdoors

Install above 

insulation

Inlet air from the 

crawl space

1 in

2

/4,000 BTU/h

Open foundation vent

Install above 

insulation

Vent 

to outdoors

Outlet air to attic

1 in

2

/4,000 BTU/h

Confined 

space

Inlet air duct

Inlet air duct

1 in

2

/4,000 BTU/h

12'' max.

Inlet

Outlet

Outdoor air duct

1 in

2

/2,000 BTU/h

1 in

2

/2,000 BTU/h

Confined 

space

Alternate

air inlet

Confined

space

Confined

space

18'' 

24'' 

Espace restreint

18'' 

24'' 

Entrée d'air

alternative

1 po

2

/2 000 BTU/h

1 po

2

/2 000 BTU/h

Conduite d'air extérieur

Sortie

Entrée

12'' max.

Conduite d'entrée d'air

Conduite

d'entrée d'air

1 po

2

/4 000 BTU/h

Évent de 

fondation

1 po

2

/4 000 BTU/h

Entrée d'air du

sous-sol

Espace 

restreint

Installez 

au-dessus 

de l'isolation

Installez 

au-dessus 

de l'isolation

Évent menant

à l'extérieur

Sortie d'air 

au grenier

1 po

2

/4 000 BTU/h

Ouverture

permanente

--------------

1 po

2

/1 000 BTU/h 

1 po

2

1 000 BTU/h 

(min. : 100 po

2

)

Espace restreint

Espace

restreint

Évent menant

à l'extérieur

Espace 

restreint

Sortie d'air 

au grenier

1 po

2

/4 000 BTU/h

Espace 

restreint

Figure 3

Figure 4

Figure 5

Figure 6

Figure 7

Figure 2

Permanent 

opening

--------------

1 square inch/

1,000 BTU/h

Ouverture 

permanente

--------------

Figure 6

Confined space

Confined space

Permanent 

opening

--------------

1 in

2

/1,000 BTU/h

(min. : 100 in

2

)

Outlet air to attic

1 in

2

/4,000 BTU/h

Vent 

to outdoors

Install above 

insulation

Inlet air from the 

crawl space

1 in

2

/4,000 BTU/h

Open foundation vent

Install above 

insulation

Vent 

to outdoors

Outlet air to attic

1 in

2

/4,000 BTU/h

Confined 

space

Inlet air duct

Inlet air duct

1 in

2

/4,000 BTU/h

12'' max.

Inlet

Outlet

Outdoor air duct

1 in

2

/2,000 BTU/h

1 in

2

/2,000 BTU/h

Confined 

space

Alternate

air inlet

Confined

space

Confined

space

18'' 

24'' 

Espace restreint

18'' 

24'' 

Entrée d'air

alternative

1 po

2

/2 000 BTU/h

1 po

2

/2 000 BTU/h

Conduite d'air extérieur

Sortie

Entrée

12'' max.

Conduite d'entrée d'air

Conduite

d'entrée d'air

1 po

2

/4 000 BTU/h

Évent de 

fondation

1 po

2

/4 000 BTU/h

Entrée d'air du

sous-sol

Espace 

restreint

Installez 

au-dessus 

de l'isolation

Installez 

au-dessus 

de l'isolation

Évent menant

à l'extérieur

Sortie d'air 

au grenier

1 po

2

/4 000 BTU/h

Ouverture

permanente

--------------

1 po

2

/1 000 BTU/h 

1 po

2

1 000 BTU/h 

(min. : 100 po

2

)

Espace restreint

Espace

restreint

Évent menant

à l'extérieur

Espace 

restreint

Sortie d'air 

au grenier

1 po

2

/4 000 BTU/h

Espace 

restreint

Figure 3

Figure 4

Figure 5

Figure 6

Figure 7

Figure 2

Permanent 

opening

--------------

1 square inch/

1,000 BTU/h

Ouverture 

permanente

--------------

Figure 5

Confined space

Confined space

Permanent 

opening

--------------

1 in

2

/1,000 BTU/h

(min. : 100 in

2

)

Outlet air to attic

1 in

2

/4,000 BTU/h

Vent 

to outdoors

Install above 

insulation

Inlet air from the 

crawl space

1 in

2

/4,000 BTU/h

Open foundation vent

Install above 

insulation

Vent 

to outdoors

Outlet air to attic

1 in

2

/4,000 BTU/h

Confined 

space

Inlet air duct

Inlet air duct

1 in

2

/4,000 BTU/h

12'' max.

Inlet

Outlet

Outdoor air duct

1 in

2

/2,000 BTU/h

1 in

2

/2,000 BTU/h

Confined 

space

Alternate

air inlet

Confined

space

Confined

space

18'' 

24'' 

Espace restreint

18'' 

24'' 

Entrée d'air

alternative

1 po

2

/2 000 BTU/h

1 po

2

/2 000 BTU/h

Conduite d'air extérieur

Sortie

Entrée

12'' max.

Conduite d'entrée d'air

Conduite

d'entrée d'air

1 po

2

/4 000 BTU/h

Évent de 

fondation

1 po

2

/4 000 BTU/h

Entrée d'air du

sous-sol

Espace 

restreint

Installez 

au-dessus 

de l'isolation

Installez 

au-dessus 

de l'isolation

Évent menant

à l'extérieur

Sortie d'air 

au grenier

1 po

2

/4 000 BTU/h

Ouverture

permanente

--------------

1 po

2

/1 000 BTU/h 

1 po

2

1 000 BTU/h 

(min. : 100 po

2

)

Espace restreint

Espace

restreint

Évent menant

à l'extérieur

Espace 

restreint

Sortie d'air 

au grenier

1 po

2

/4 000 BTU/h

Espace 

restreint

Figure 3

Figure 4

Figure 5

Figure 6

Figure 7

Figure 2

Permanent 

opening

--------------

1 square inch/

1,000 BTU/h

Ouverture 

permanente

--------------

Figure 4

Содержание LIGHT DUTY COMMERCIAL POWER VENT GAS-FIRED WATER HEATERS

Страница 1: ...ersonal injury or death DO NOT store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance...

Страница 2: ...ur Water Heater 18 Replacement Parts 19 Troubleshooting Guide 20 Warranty 23 SAFETY INFORMATION Your safety and the safety of others is extremely important during the installation operation and servic...

Страница 3: ...m the top see Figure 1 3 INSTALLATION INSTRUCTIONS IMPORTANT These instructions have been written as a guide for the proper installation and operation of your water heater and the manufacturer of this...

Страница 4: ...BTU 4 8 m3 kW of the total input rating for all gas appliances installed in that space Water heaters installed in confined spaces require additional air This can be provided in two ways In Canada ref...

Страница 5: ...tecting the openings Screens must not be smaller 5 INSTALLATION INSTRUCTIONS Install above insulation Vent to outdoors Outlet air to attic 1 in2 4 000 BTU h Confined space Inlet air duct 1 in2 4 000 B...

Страница 6: ...stall the venting system could result in property damage personal injury or death Before installing the vent piping make sure that the vent system layout has been properly planned Verify that the loca...

Страница 7: ...2 inches 30 cm Shall not install Clearance to permanently closed window Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of two 2 feet 61 cm from the cen...

Страница 8: ...t all horizontal runs have a minimum rise of 1 4 inch per foot 21 mm m of run see Figure 10 When the installation is completed the vent terminal must be a minimum of eighteen 18 inches 45 7 cm from th...

Страница 9: ...installed into the relief valve The discharge line Must not be smaller than the outlet pipe size of the relief valve Must not terminate less than six 6 inches 15 2 cm and not more than twelve 12 inche...

Страница 10: ...t size of piping for this water heater consult CAN CSA B149 1 National Gas and Propane Installation Codes in Canada and or the National Fuel Gas Code ANSI Z223 1 NFPA 54 in the United States Only new...

Страница 11: ...tanks 4 Do not use toxic chemicals to clean the potable water heating system 5 Where water temperature in excess of 140o F 60o C is required for a space heating application a mixing valve must be inst...

Страница 12: ...uses an external electrical source for power It must be electrically grounded in accor dance with all local codes or in the absence of local codes CSA C22 1 Canadian Electrical Code in Canada and or t...

Страница 13: ...n installed with a minimum rise of 1 4 inch per foot 21 mm m of run L Has all the vent piping been secured with the appropriate primer and solvent based cement L Has the venting been supported at the...

Страница 14: ...our water heater immedi ately contact a qualified installer service agency or the gas supplier DO NOT light this water heater if It is not full of water The gas supplied does not match the type listed...

Страница 15: ...ature See Figure 13 for an explanation of what each of the temperature indica tors mean To decrease the temperature press and release the COOLER button once The temperature indi cators will now displa...

Страница 16: ...y occur 1 When the water heater is filled with cold water for the first time 2 If the water heater has been undersized 3 When large amounts of hot water are drawn from the water heater in a short peri...

Страница 17: ...t may be required Under no circumstances is the anode to be removed from the water heater on a permanent basis Removal of the anode will lead to premature failure of the water heater and void the warr...

Страница 18: ...listed in the Troubleshooting Guide does not solve the problem or if your par ticular problem is not listed in the guide contact the installer of the water heater or the local gas utility 3 If you sti...

Страница 19: ...bly 4 Complete burner assembly 5 Outer access door 6 Inner access door 7 Drain valve 8 Overflow tube 9 Dip tube 10 Temperature pressure relief valve 11 Flue baffle 12 Complete blower assembly 13 Vent...

Страница 20: ...that the hot surface ignitor and flame sensor rod are wired correctly and in good working condition 5 Low voltage to the water heater Check and repair 7 The gas valve driver circuit 1 Turn off the po...

Страница 21: ...w gas control valve High operating costs Gas control valve set too high Turn temperature dial to desired temperature Sediment or lime in tank Drain Check to see if water treatment is necessary Water h...

Страница 22: ...m up Problem should go away If it persists check all plumbing connections for leaks Heavy draws of hot water with very cold refill water Let water heater warm up Problem should go away If it persists...

Страница 23: ...10 If the heater is operated at water temperatures exceeding the maximum setting of the operating or high limit control or the heater is not supplied with potable water free to circulate at all times...

Страница 24: ...____________________________________________ ___________________________________________________________________________________________________________ _______________________________________________...

Отзывы: