Location

This water heater should be located close enough to the 

outside wall so that it is within the venting requirements 

listed in these installation instructions and as close as  

possible to the main use of hot water. This location 

must not be subject to freezing temperatures. The 

water heater should be positioned, so that there is 

easy access to the burner, gas control valve, and 

drain valve. It must be located close to a suitable 

free-flowing floor drain. Where a floor drain is not 

adjacent to the water heater, a suitable drain pan 

must be installed under the water heater (

see Figure 

10

). This drain pan should be at least four (4) inches 

(10.2 cm) larger than the diameter of the water heater, 

and at least one (1) inch (2.5 cm) deep, providing 

access to the drain valve. This pan must not restrict 

the flow of ventilation and combustion air. This pan 

must be piped to a suitable drain to prevent damage 

to property in the event of a water leak from the pip-

ing, the relief valve, or the water heater.

Sooner or later, all water heaters leak. The  
manufacturer, based on national building codes, 
has given the necessary instructions to prevent 
damage to the building. Under no circumstances 
is the manufacturer to be held liable for any water 
damage, in connection with this water heater. 

This water heater is approved for installation on 

either a combustible or non-combustible floor. 

However, should this water heater be installed directly 

on carpeting, the carpeting must be protected by a 

wood or metal panel beneath the water heater. This 

panel must extend at least three (3) inches (7.6 cm) 

beyond the width and depth of the water heater. 

Should the water heater be installed in an alcove or 

closet, the entire floor area must be covered by the 

panel. 

Minimum Clearances

The minimum clearances from combustible material 

for this water heater are: Two (2) inches (5.1 cm) 

from the sides and rear, four (4) inches (10.2 cm) 

from the front, and eighteen (18) inches (45.7 cm) 

from the top (

see Figure 1

).

3

INSTALLATION INSTRUCTIONS

IMPORTANT 

 

These instructions have been written as a guide for the proper installation and operation of your water heater, and 

the manufacturer of this water heater will not accept any liability where these instructions have not been followed. 

However, for your safety and to avoid damage caused by improper installation, this water heater must be 

installed by a Certified Licensed Professional, and meet all local codes or, in the absence of local codes, CAN/

CSA B149.1, Natural Gas and Propane Gas Installation Code, in Canada, and/or the National Fuel Gas Code, 

ANSI Z223.1/NFPA 54, in the United States.

Before proceeding with the installation instructions:

1)

 Inspect the water heater and its component parts for possible damage. 

DO NOT 

install or attempt to 

repair any damaged component parts. If you detect any damage, contact the dealer where the water 

heater was purchased or the manufacturer listed on the warranty card.

2)

 Verify that the type of gas being supplied corresponds to that which is marked on the rating plate and 

gas control valve of the water heater. 

     Vapours from flammable 

liquids will explode and 

catch fire causing death 

or severe burns.

Do not use or store flammable 

products, such as gasoline, 

solvents or adhesives in the 

same room or area near the 

water heater.

Keep flammable products:

1. far away from heater,

2. in approved containers,

3. tightly closed, and

4. out of children's reach.

DANGER

!

Flammable Vapours

FLAMMABLES

Water heater has a main 

burner and pilot flame. 

The pilot flame:

1.  is on all the time, and

2.  will ignite flammable 

 vapours.

Vapours:

1.  cannot be seen,

2.  are heavier than air,

3.  go a long way on the floor,  

 and

4.  can be carried from other  

  rooms to the pilot flame by  

  air currents.

Installation:
Do not install the water heater 
where flammable products will 
be stored or used unless the 
main burner and pilot flames

are at least 18" above the 
floor. This will reduce, but not 
eliminate, the risk of vapours 
being ignited by the main 
burner or pilot flame.

Read and follow the water heater warnings and instructions.
If owners manual is missing, contact the retailer or manufacturer.

!

Содержание LIGHT DUTY COMMERCIAL POWER VENT GAS-FIRED WATER HEATERS

Страница 1: ...ersonal injury or death DO NOT store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance...

Страница 2: ...ur Water Heater 18 Replacement Parts 19 Troubleshooting Guide 20 Warranty 23 SAFETY INFORMATION Your safety and the safety of others is extremely important during the installation operation and servic...

Страница 3: ...m the top see Figure 1 3 INSTALLATION INSTRUCTIONS IMPORTANT These instructions have been written as a guide for the proper installation and operation of your water heater and the manufacturer of this...

Страница 4: ...BTU 4 8 m3 kW of the total input rating for all gas appliances installed in that space Water heaters installed in confined spaces require additional air This can be provided in two ways In Canada ref...

Страница 5: ...tecting the openings Screens must not be smaller 5 INSTALLATION INSTRUCTIONS Install above insulation Vent to outdoors Outlet air to attic 1 in2 4 000 BTU h Confined space Inlet air duct 1 in2 4 000 B...

Страница 6: ...stall the venting system could result in property damage personal injury or death Before installing the vent piping make sure that the vent system layout has been properly planned Verify that the loca...

Страница 7: ...2 inches 30 cm Shall not install Clearance to permanently closed window Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of two 2 feet 61 cm from the cen...

Страница 8: ...t all horizontal runs have a minimum rise of 1 4 inch per foot 21 mm m of run see Figure 10 When the installation is completed the vent terminal must be a minimum of eighteen 18 inches 45 7 cm from th...

Страница 9: ...installed into the relief valve The discharge line Must not be smaller than the outlet pipe size of the relief valve Must not terminate less than six 6 inches 15 2 cm and not more than twelve 12 inche...

Страница 10: ...t size of piping for this water heater consult CAN CSA B149 1 National Gas and Propane Installation Codes in Canada and or the National Fuel Gas Code ANSI Z223 1 NFPA 54 in the United States Only new...

Страница 11: ...tanks 4 Do not use toxic chemicals to clean the potable water heating system 5 Where water temperature in excess of 140o F 60o C is required for a space heating application a mixing valve must be inst...

Страница 12: ...uses an external electrical source for power It must be electrically grounded in accor dance with all local codes or in the absence of local codes CSA C22 1 Canadian Electrical Code in Canada and or t...

Страница 13: ...n installed with a minimum rise of 1 4 inch per foot 21 mm m of run L Has all the vent piping been secured with the appropriate primer and solvent based cement L Has the venting been supported at the...

Страница 14: ...our water heater immedi ately contact a qualified installer service agency or the gas supplier DO NOT light this water heater if It is not full of water The gas supplied does not match the type listed...

Страница 15: ...ature See Figure 13 for an explanation of what each of the temperature indica tors mean To decrease the temperature press and release the COOLER button once The temperature indi cators will now displa...

Страница 16: ...y occur 1 When the water heater is filled with cold water for the first time 2 If the water heater has been undersized 3 When large amounts of hot water are drawn from the water heater in a short peri...

Страница 17: ...t may be required Under no circumstances is the anode to be removed from the water heater on a permanent basis Removal of the anode will lead to premature failure of the water heater and void the warr...

Страница 18: ...listed in the Troubleshooting Guide does not solve the problem or if your par ticular problem is not listed in the guide contact the installer of the water heater or the local gas utility 3 If you sti...

Страница 19: ...bly 4 Complete burner assembly 5 Outer access door 6 Inner access door 7 Drain valve 8 Overflow tube 9 Dip tube 10 Temperature pressure relief valve 11 Flue baffle 12 Complete blower assembly 13 Vent...

Страница 20: ...that the hot surface ignitor and flame sensor rod are wired correctly and in good working condition 5 Low voltage to the water heater Check and repair 7 The gas valve driver circuit 1 Turn off the po...

Страница 21: ...w gas control valve High operating costs Gas control valve set too high Turn temperature dial to desired temperature Sediment or lime in tank Drain Check to see if water treatment is necessary Water h...

Страница 22: ...m up Problem should go away If it persists check all plumbing connections for leaks Heavy draws of hot water with very cold refill water Let water heater warm up Problem should go away If it persists...

Страница 23: ...10 If the heater is operated at water temperatures exceeding the maximum setting of the operating or high limit control or the heater is not supplied with potable water free to circulate at all times...

Страница 24: ...____________________________________________ ___________________________________________________________________________________________________________ _______________________________________________...

Отзывы: