INSTALLATION INSTRUCTIONS

Pressure Build-up in a Water System 

When the water heater operates, the heated water 

expands creating a pressure build-up. This is a natural 

function and is one of the reasons for installing a  

temperature and pressure-relief valve. If the cold water 

supply line has a built-in water meter, check valve, or 

pressure-reducing valve, a suitable expansion tank 

must be installed to prevent pressure build-up or water 

hammer effect. Otherwise, the warranty is void (

see 

Figure 10

). An indication of pressure build-up is fre-

quent discharges of water from the relief valve. If the 

relief valve discharges water on a continuous basis, it 

may indicate a malfunction of the relief valve, and a 

qualified service technician must be called to have the 

system checked, and the problem corrected.

Filling the Water Heater

NEVER

 operate the water heater unless it is  

completely filled with water. Failure to follow this 

instruction can result in premature failure of the 

water heater that is not covered by the warranty.

Check that all of the water piping connections have 

been made. To fill the water heater:
1) Make sure that the water heater drain valve is 

closed by inserting a flat head screwdriver into the 

slot on the head of the drain valve and turning the 

knob clockwise

.

2) Open the cold water supply manual shut-off valve. 

This valve must remain open, as long as the water 

heater is in use. 

NEVER

 operate the water heater with 

the cold water supply manual shut-off valve closed.

3) To make sure the water heater is completely full of 

water, open hot water faucets to let the air out of the 

water heater and plumbing system. Leave the fau-

cets open until a constant flow of water is obtained.

4) Check all of the plumbing connections to make 

sure there are no leaks.

Gas Connections

DO NOT 

attempt to use this water heater with  

any gas other than the type of gas shown on the 

water heater rating plate. Failure to follow this 

instruction can result in property damage, personal 

injury, or death.

The gas piping must be installed as indicated in

  

Figure 10

. For the correct size of piping for this water 

heater, consult CAN/CSA B149.1, National Gas and 

Propane Installation Codes (in Canada) and/or the 

National Fuel Gas Code, ANSI Z223.1/NFPA 54, in the 

United States.  Only new piping with cleanly cut 

threads may be used, together with a suitable sealing 

compound that is approved for natural and propane 

gases. It is mandatory that a readily accessible manual 

shut-off valve be installed in the gas supply line. The 

gas supply manual shut-off valve must be close to the 

water heater. A drip leg (sediment trap) must be 

installed in the gas line ahead of the gas control valve 

to prevent dirt from entering it. A union must be 

installed between the gas control valve and the gas 

supply manual shut-off valve for easy maintenance of 

the water heater. 

NEVER

 use an open flame to test for gas leaks. 

A fire or explosion could occur resulting in property 

damage, personal injury, or death.

The water heater and its gas connection must be 

leak tested before placing the appliance into opera-

tion. To leak test the system:

1) Turn on the manual gas shut-off valve near the 

water heater.

2) Use a soapy water solution to test all connections 

and fittings for leaks. Bubbles indicate a gas leak.

3) Correct all leaks.

Make sure that the inlet pressure to the water heater 

does not exceed 

1

/

2

 psi (3.5 kPa) for both natural and 

propane gases. Pressures in excess of 

1

/

2

 psi (3.5 kPa) 

can damage the gas control valve, resulting in a fire or 

explosion from leaking gas. For purposes of adjust-

ment, the minimum inlet pressure is indicated on the 

water heater rating plate.
If any pressure testing of the gas line is undertaken 

at test pressures in excess of 

1

/

2

 psi (3.5 kPa), the 

water heater and its gas supply manual shut-off 

valve must be disconnected from the gas supply pip-

ing system, and the end of the pipe sealed with a 

female cap. If the testing is to be undertaken at a test 

pressure less than 

1

/

2

 psi (3.5 kPa), the gas supply 

manual shut-off valve must be closed. 

A high altitude orifice 

MUST BE

 installed for 

water heaters operating above 2,000 feet (610 m). 

Failure to follow this instruction can result in pro-

perty damage, personal injury, or death.

10

WARNING

AVERTISSEMENT

DANGER

WARNING

AVERTISSEMENT

DANGER

WARNING

AVERTISSEMENT

DANGER

WARNING

AVERTISSEMENT

DANGER

Содержание LIGHT DUTY COMMERCIAL POWER VENT GAS-FIRED WATER HEATERS

Страница 1: ...ersonal injury or death DO NOT store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance...

Страница 2: ...ur Water Heater 18 Replacement Parts 19 Troubleshooting Guide 20 Warranty 23 SAFETY INFORMATION Your safety and the safety of others is extremely important during the installation operation and servic...

Страница 3: ...m the top see Figure 1 3 INSTALLATION INSTRUCTIONS IMPORTANT These instructions have been written as a guide for the proper installation and operation of your water heater and the manufacturer of this...

Страница 4: ...BTU 4 8 m3 kW of the total input rating for all gas appliances installed in that space Water heaters installed in confined spaces require additional air This can be provided in two ways In Canada ref...

Страница 5: ...tecting the openings Screens must not be smaller 5 INSTALLATION INSTRUCTIONS Install above insulation Vent to outdoors Outlet air to attic 1 in2 4 000 BTU h Confined space Inlet air duct 1 in2 4 000 B...

Страница 6: ...stall the venting system could result in property damage personal injury or death Before installing the vent piping make sure that the vent system layout has been properly planned Verify that the loca...

Страница 7: ...2 inches 30 cm Shall not install Clearance to permanently closed window Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of two 2 feet 61 cm from the cen...

Страница 8: ...t all horizontal runs have a minimum rise of 1 4 inch per foot 21 mm m of run see Figure 10 When the installation is completed the vent terminal must be a minimum of eighteen 18 inches 45 7 cm from th...

Страница 9: ...installed into the relief valve The discharge line Must not be smaller than the outlet pipe size of the relief valve Must not terminate less than six 6 inches 15 2 cm and not more than twelve 12 inche...

Страница 10: ...t size of piping for this water heater consult CAN CSA B149 1 National Gas and Propane Installation Codes in Canada and or the National Fuel Gas Code ANSI Z223 1 NFPA 54 in the United States Only new...

Страница 11: ...tanks 4 Do not use toxic chemicals to clean the potable water heating system 5 Where water temperature in excess of 140o F 60o C is required for a space heating application a mixing valve must be inst...

Страница 12: ...uses an external electrical source for power It must be electrically grounded in accor dance with all local codes or in the absence of local codes CSA C22 1 Canadian Electrical Code in Canada and or t...

Страница 13: ...n installed with a minimum rise of 1 4 inch per foot 21 mm m of run L Has all the vent piping been secured with the appropriate primer and solvent based cement L Has the venting been supported at the...

Страница 14: ...our water heater immedi ately contact a qualified installer service agency or the gas supplier DO NOT light this water heater if It is not full of water The gas supplied does not match the type listed...

Страница 15: ...ature See Figure 13 for an explanation of what each of the temperature indica tors mean To decrease the temperature press and release the COOLER button once The temperature indi cators will now displa...

Страница 16: ...y occur 1 When the water heater is filled with cold water for the first time 2 If the water heater has been undersized 3 When large amounts of hot water are drawn from the water heater in a short peri...

Страница 17: ...t may be required Under no circumstances is the anode to be removed from the water heater on a permanent basis Removal of the anode will lead to premature failure of the water heater and void the warr...

Страница 18: ...listed in the Troubleshooting Guide does not solve the problem or if your par ticular problem is not listed in the guide contact the installer of the water heater or the local gas utility 3 If you sti...

Страница 19: ...bly 4 Complete burner assembly 5 Outer access door 6 Inner access door 7 Drain valve 8 Overflow tube 9 Dip tube 10 Temperature pressure relief valve 11 Flue baffle 12 Complete blower assembly 13 Vent...

Страница 20: ...that the hot surface ignitor and flame sensor rod are wired correctly and in good working condition 5 Low voltage to the water heater Check and repair 7 The gas valve driver circuit 1 Turn off the po...

Страница 21: ...w gas control valve High operating costs Gas control valve set too high Turn temperature dial to desired temperature Sediment or lime in tank Drain Check to see if water treatment is necessary Water h...

Страница 22: ...m up Problem should go away If it persists check all plumbing connections for leaks Heavy draws of hot water with very cold refill water Let water heater warm up Problem should go away If it persists...

Страница 23: ...10 If the heater is operated at water temperatures exceeding the maximum setting of the operating or high limit control or the heater is not supplied with potable water free to circulate at all times...

Страница 24: ...____________________________________________ ___________________________________________________________________________________________________________ _______________________________________________...

Отзывы: