TROUBLESHOOTING GUIDE

Disconnect the electrical power before servicing the water heater. Service should only be performed by a  

qualified service technician. Failure to follow these instructions can result in personal injury and/or death.

WARNING

AVERTISSEMENT

DANGER

CONDITION (code#)

CAUSE

REMEDY

1

An open earth ground circuit  

to the ignition.

1) Check that the earth ground conductor is properly connected at the fuse box or break-

er panel and the water heater.

2) Check that the grounding conductors on the water heater are properly connected and 

secure.

2

A wiring error or a high  

resistance to earth ground.

1) Check for proper connection of the line neutral and line hot wires. 

2) Check that the water heater is securely connected to earth ground.

3

The pressure switch remained 

closed longer than 5 seconds 

after the call for heat began.

1) The pressure switch wiring is incorrect.

2) The pressure switch is defective and must be replaced.

4

The pressure switch remained  

open longer than 5 seconds 

after the power venter was 

energized.

(see note at the bottom of the page)

1) The pressure switch wiring is incorrect.

2) The pressure switch tubing is not connected correctly.

3) There are obstructions or restrictions in the water heater air intake or exhaust flue.

5

The self diagnostic test has  

detected an error in the hot 

surface ignitor circuit.

1) Check the wiring is correct and secure.

2) Disconnect the ignitor connector and measure the ignitor resistance with  

an accurate ohmmeter between pins 1 and 2. Resistance should be         

  

between 11.5 and 18.8 ohms. If the reading is incorrect, replace the hot surface ignitor. 

3) If the above checks are good, replace the gas control valve.

6

The maximum number of  

ignition retries or recycles has 

been reached and the system 

is in lockout.

1) Check if the gas supply is off or too low to operate.

2) Check the flame sensor rod to see that it is located properly and free from contamina-

tion. Reposition the flame sensor rod or lightly clean it with an abrasive cloth.

3) The hot surface ignitor may not be positioned correctly. Reposition as necessary.

4) Check that the hot surface ignitor and flame sensor rod are wired correctly and in good 

working condition.

5) Low voltage to the water heater. Check and repair.

7

The gas valve driver circuit.

1) Turn off the power to the water heater for 10 seconds and then back on.

2) If the above step did not clear the error, replace the gas control valve.

8

The internal microcomputer.

1) Turn off the power to the water heater for 10 seconds and then back on.

2) If the above step did not clear the error, replace the gas control valve.

9

The internal circuit.

1) Turn off the power to the water heater for 10 seconds and then back on

2) If the above step did not clear the error, replace the gas control valve.

10

Flame signal sensed out of  

proper sequence.

Replace the gas control valve.

11

The high temperature thermal 

cutoff is open.

Replace the gas control valve.

12

One of the temperature adjust  

buttons is stuck closed.

1) Make sure that there are no objects leaning against the front of the control.

2) Lightly press and release each of the buttons once.

3) If the above actions do not clear the error, the control will continue to regulate the 

water temperature at the last setting, but you will not be  able to change settings 

unless you replace the gas control valve.

13

The water temperature sensor 

is either open or  

short-circuited.

1) Check that all of the wiring is correct and that there are no open or  shorted circuits.

2) If no wiring problems are found, the gas control valve must be replaced.

14

The self-diagnostic test found 

aproblem with the flame 

vapour sensor

1) Check that all wiring is correct and that there are no open or shorted circuits.

2) If no wiring problems are found, the flammable vapour sensor must be replaced.

15

The control detected the  

presence of flammable 

vapours near the appliance 

and entered lockout.

1) Identify the source of the flammable vapours and remove it from the area surrounding  

the water heater

2) Contact a qualified service technician or the gas supplier to have the water heater 

inspected immediately

Note for models with a manual reset only: Since the high limit switch on the blower is in series with the pressure switch, the problem could be that 

the high limit switch tripped. Reset the high limit Switch by pressing on the red button in the middle of the switch.

20

Содержание LIGHT DUTY COMMERCIAL POWER VENT GAS-FIRED WATER HEATERS

Страница 1: ...ersonal injury or death DO NOT store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS DO NOT try to light any appliance...

Страница 2: ...ur Water Heater 18 Replacement Parts 19 Troubleshooting Guide 20 Warranty 23 SAFETY INFORMATION Your safety and the safety of others is extremely important during the installation operation and servic...

Страница 3: ...m the top see Figure 1 3 INSTALLATION INSTRUCTIONS IMPORTANT These instructions have been written as a guide for the proper installation and operation of your water heater and the manufacturer of this...

Страница 4: ...BTU 4 8 m3 kW of the total input rating for all gas appliances installed in that space Water heaters installed in confined spaces require additional air This can be provided in two ways In Canada ref...

Страница 5: ...tecting the openings Screens must not be smaller 5 INSTALLATION INSTRUCTIONS Install above insulation Vent to outdoors Outlet air to attic 1 in2 4 000 BTU h Confined space Inlet air duct 1 in2 4 000 B...

Страница 6: ...stall the venting system could result in property damage personal injury or death Before installing the vent piping make sure that the vent system layout has been properly planned Verify that the loca...

Страница 7: ...2 inches 30 cm Shall not install Clearance to permanently closed window Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of two 2 feet 61 cm from the cen...

Страница 8: ...t all horizontal runs have a minimum rise of 1 4 inch per foot 21 mm m of run see Figure 10 When the installation is completed the vent terminal must be a minimum of eighteen 18 inches 45 7 cm from th...

Страница 9: ...installed into the relief valve The discharge line Must not be smaller than the outlet pipe size of the relief valve Must not terminate less than six 6 inches 15 2 cm and not more than twelve 12 inche...

Страница 10: ...t size of piping for this water heater consult CAN CSA B149 1 National Gas and Propane Installation Codes in Canada and or the National Fuel Gas Code ANSI Z223 1 NFPA 54 in the United States Only new...

Страница 11: ...tanks 4 Do not use toxic chemicals to clean the potable water heating system 5 Where water temperature in excess of 140o F 60o C is required for a space heating application a mixing valve must be inst...

Страница 12: ...uses an external electrical source for power It must be electrically grounded in accor dance with all local codes or in the absence of local codes CSA C22 1 Canadian Electrical Code in Canada and or t...

Страница 13: ...n installed with a minimum rise of 1 4 inch per foot 21 mm m of run L Has all the vent piping been secured with the appropriate primer and solvent based cement L Has the venting been supported at the...

Страница 14: ...our water heater immedi ately contact a qualified installer service agency or the gas supplier DO NOT light this water heater if It is not full of water The gas supplied does not match the type listed...

Страница 15: ...ature See Figure 13 for an explanation of what each of the temperature indica tors mean To decrease the temperature press and release the COOLER button once The temperature indi cators will now displa...

Страница 16: ...y occur 1 When the water heater is filled with cold water for the first time 2 If the water heater has been undersized 3 When large amounts of hot water are drawn from the water heater in a short peri...

Страница 17: ...t may be required Under no circumstances is the anode to be removed from the water heater on a permanent basis Removal of the anode will lead to premature failure of the water heater and void the warr...

Страница 18: ...listed in the Troubleshooting Guide does not solve the problem or if your par ticular problem is not listed in the guide contact the installer of the water heater or the local gas utility 3 If you sti...

Страница 19: ...bly 4 Complete burner assembly 5 Outer access door 6 Inner access door 7 Drain valve 8 Overflow tube 9 Dip tube 10 Temperature pressure relief valve 11 Flue baffle 12 Complete blower assembly 13 Vent...

Страница 20: ...that the hot surface ignitor and flame sensor rod are wired correctly and in good working condition 5 Low voltage to the water heater Check and repair 7 The gas valve driver circuit 1 Turn off the po...

Страница 21: ...w gas control valve High operating costs Gas control valve set too high Turn temperature dial to desired temperature Sediment or lime in tank Drain Check to see if water treatment is necessary Water h...

Страница 22: ...m up Problem should go away If it persists check all plumbing connections for leaks Heavy draws of hot water with very cold refill water Let water heater warm up Problem should go away If it persists...

Страница 23: ...10 If the heater is operated at water temperatures exceeding the maximum setting of the operating or high limit control or the heater is not supplied with potable water free to circulate at all times...

Страница 24: ...____________________________________________ ___________________________________________________________________________________________________________ _______________________________________________...

Отзывы: