Mounting and operating manual GIA 20 EB with electrically insulated supply
page 6 of 32
2. Product description
2.1. Scope of supply
monitoring- / controlling device
1 mounting bracket
screw-in/plug-in clamps
mounting and operating manual
2.2. Function
The GIA 20 EB is a universally applicable microprocessor controlled displaying, monitoring and
controlling device.
The power supply-connection is electrically insulated towards the
device’s other
connections.
Universal input
The device supports one universal interface for the connection of:
Standard transmitter signals
(0-20 mA, 4-20 mA, 0-50 mV, 0-1 V, 0-2 V and 0-10 V),
- RTD (for Pt100 and Pt1000),
- Thermocouple probes (type K, J, N, T and S),
- Frequency (TTL and switching contact).
As well as flow rate and rotation measuring, counting, etc. ...
Switching output and alarm
The GIA 20EB features two outputs, which can be configured as
2-point-controller, 3-point-controller, 2-point-controller with min./max. alarm, common or individual
min./max. alarm.
The state of the outputs is displayed with the LED’s below the front 4-digit LED-display
The left LED displays the state of the 1st output, the right LED displays the state of the 2nd output.
Interface
Furthermore both devices supports one EASYBus-interface for communicating with a host com-
puter that makes the device to a full functions EASYBus-module.
When leaving our factory the GIA 20 EB has been subjected to various inspection tests and is
completely calibrated
.
Before the GIA 20
EB can be used, it has to be configured for the customer’s applica-
tion!
Important:
At the configuration of the device you have to adjust the input signal (see chapter 6)
first and then the output function (see chapter 7) or the offset-/slope- adjustment (see chapter 8)
In order to avoid undefined input states and unwanted or wrong switching pro-
cesses, we suggest to connect the device’s switching outputs after You have
configured the device properly.
By calling a configuration menu the measurement and regulation of the device
will be deactivated.
By leaving the menu the device will be reinitialised and the measur-
ing/regulation will be started again. At the input
function “counter” the counter
state will be reset by leaving the menu.