Mounting and operating manual GIA 20 EB with electrically insulated supply
page 24 of 32
*
4
:
Low-/High-side-switch: opened in case of an error. Push-Pull-output: low in case of an error.
*
5
:
Low-/High-side-switch: closed in case of an error. Push-Pull-output: high in case of an error
Finish configuration:
Press
Button 1
as often till the device executes a reset. The values will be stored at it.
Switching delay:
The value for the switching-delay is the time [in sec] the device waits at least to switch on the output
again after the output was switched off.
8. Offset- and slope-adjustment
The offset and slope-adjustment function can be used for compensating the tolerance of the used
sensor, and for venire adjustment of the used transducer or transmitter.
The settings of the offset- / slope-adjustment will be cancelled, when no button was
pressed for more than 60 sec. Changes you may have made already
won‘t be saved
and will be lost!
The settings of the offset- / slope-adjustment and alarm-boundaries will automatically
be reset to factory default when any changes for the settings “InP”, “SEnS“ or. “Unit“
had been made!
Calling the Menu:
Press
Button 3
>2 Seconds.
General description and notes to the operating of the menu:
The Display has to show
0FFS
('Offset').
With
Button1
you can go to the next parameter resp. after the last
parameter values will be
saved
.
With
Button 2
or
Button 3
you can adjust the value.
If no key is pressed > 60 sec. the menu will be automatically closed.
Button 1 Button 2 Button 3