Mounting and operating manual GIA 20 EB with electrically insulated supply
page 15 of 32
6. Configuration of the device
Calling the Configuration:
Press
Button 2
>2 Seconds.
General description and notes to the operating of the menu:
The display shows
INP
('INPUT').
With
Button1
you can go to the next parameter resp. after the last
parameter values will be
saved
.
With
Button 2
or
Button 3
you can adjust the value.
If no key is pressed > 60 sec. the menu will be automatically closed.
6.1. Selecting an input signal type
Input
Button 1
Selection
Button 2 / 3
Description
Signal
proceed in chapter
INP
U
Voltage signal U
0
– 10 V
0
– 2 V
0
– 1 V
0
– 50 mV
I
Current signal I
4
– 20 mA
0
– 20 mA
T.RES
Temperature:
RTD
Pt100
Pt1000
T .TC
Temperature:
Thermocouples
type K
(NiCr-Ni)
type S
(Pt10Rh-Pt)
type N
(NiCrSi-NiSi)
type J
(Fe-CuNi)
type T
(Cu-CuNi)
FREQ
Frequency
TTL-signal
Switch-contact NPN, PNP
RPN
Rotation
TTL-signal
Switch-contact NPN, PNP
(O. VP
Counter up
TTL-signal
Switch-contact NPN, PNP
(O.DN
Counter down
TTL-signal
Switch-contact NPN, PNP
SER,
Interface mode
Serial interface
When changing the measuring mode “InP“, the input signal “SEnS“ and the
display-
unit “Unit“ all settings will be changed to factory default. You have to
set all the other settings. This also regards the settings for offset and slope-
adjustment as well as the switching points!
Button 1 Button 2 Button 3