7. Configuration of the output function
Calling the Configuration:
The call happened in the chosen Input Signal when the display shows
“
outP
“.
The output can be scaled arbitrary with the display range.
General description and notes to the operating of the menu:
With
Button1
you can go to the next parameter resp. the values will be saved
With
Button 2
or
Button 3
you can adjust the values.
If no key is pressed > 60 sec. the menu will be automatically closed.
A change of the input configuration can possibly influence the switching
points and alarm boundaries. (e.g.
changing of scaling for standard signals or chang-
ing of resolution or unit for temperature
). Therefore the output configuration and
switching points / alarm boundaries adjustment should be done after the
input configuration has been finished.
Additionally you may check your output settings after the input configura-
tion has been changed!
The alarm-outputs are inverted! This means, that the output will be active when
there is no alarm!
7.1. Output function
Output
Button 1
Function
Button
2 / 3
Output 1
Output 2
Description
Go on in
chapter
O
VTP
NO
off
off
No output,
only displaying unit
--
2P
Switching function 1
off
2-point-controller
3P
Switching function 1
Switching function 2
3-point-controller
2P.AL
Switching function 1
Min-/Max-Alarm,
inverse
2-point-controller
with
Min-/Max-alarm
AL.F1
off
Min-/Max-Alarm,
inverse
Min-/Max-alarm,
common
AL.F2
Max-Alarm,
inverse
Min-Alarm,
inverse
Min-/Max-alarm,
individual
Further parameter:
Press
Button 1
.
Depending on the configuration you have made in the „output“ menu you will get
different Display values. Please follow the specific chapter.
The settings for the switching and alarm points can be made later in an extra menu.