Mounting and operating manual GIA 20 EB with electrically insulated supply
page 16 of 32
When changing the measuring mode “InP“ the values for the offset and slope-
adjustment will be reset. Furthermore a change of the device scaling for standard sig-
nals (di.Lo, di.Hi, dP) or of the resolution and unit for temperature can possibly influ-
ence the values of the offset and slope-adjustment. Therefore you may check your
offset and slope-adjustment after changing the input configuration.
The change of the device scaling for standard signals (di.Lo, di.Hi, dP) or of the reso-
lution and unit for temperature can possibly change the switching and alarm points.
Therefore you may check your output settings afterwards!
6.2. Measuring temperature
(Pt100, Pt1000 RTD probes and thermocouple type J, K, N, S or T)
This chapter describes how to configure the device for temperature measuring with the help of ex-
ternal platinum RTD probes or thermocouple probes.. This instruction demands that you selected
“
t.res
“ or “
t.tc
“ as your desired input type like it is explained in chapter 6.1.
The display must show
INP
.
Parameter
Button 1
Value
Button 2 / 3
Description
Notes
SENS
(with
T .RES
)
P
T0.
1
Pt100
(3-wire)
Meas.-range: -50.0 ... +200.0 °C
(-58.0 ... + 392.0 °F)
P
T
1
Meas.-range: -200 ... + 850 °C
(-328 ... + 1562 °F)
1000
Pt1000
(2-wire)
Meas.-range: -200 ... + 850 °C
(-328 ... + 1562 °F)
SENS
(with
T .TC
)
N,CR
type K
(
NiCr-Ni
)
Meas.-range: -270 ... +1350 °C
(-454 ... + 2462 °F)
S
type S
(
Pt10Rh-Pt
)
Meas.-range: -50 ... +1750 °C
(- 58 ... + 3182 °F)
N
type N
(
NiCrSi-NiSi
)
Meas.-range: -270 ... +1300 °C
(-454 ... + 2372 °F)
J
type J
(
Fe-CuNi
)
Meas.-range: -170 ... + 950 °C
(-274 ... + 1742 °F)
T
type T
(
Cu-CuNi
)
Meas.-range: -270 ... + 400 °C
(-454 ... + 752 °F)
UN,T
°C oder °F
unit
F, LT
0.01 ... 2.00
s
filter
see info filter
O
V
TP
output
Output configuration will be explained in chapter 7.
According to your settings different parameters will
be shown.
Finish configuration:
Press
Button 1
as often till the device executes a reset. The values will be stored at it.
F,LT
:
filter
this digital filter is a digital replica of a low pass filter.
A filter value of at least 0.1 is recommended for the input type S.