LRG 1x-6x - Installation & Operating Manual -
819878-00
Checking installation and function
When you have remedied system errors, perform a function test as follows.
■
■
Checking installation and function.
■
■
Perform an equipment test; see page 52. In this case, the equipment must behave as if there were
an alarm.
■
■
When bringing into service and after each replacement of the LRG 1x-6x conductivity electrode
the displayed measured value and the set alarm limit value must be checked and an equipment test
must be performed.
System errors in the LRG 1x-6x conductivity electrode also trigger a system error
in the URS 60/URS 61 safety control unit. The output contacts open without a delay and the
relevant signal output is activated.
If you require assistance, please tell us the indicated fault code.
In the event of errors or faults that cannot be remedied with the aid of this Installation & Opera-
ting Manual, please contact our service centre or authorised agent in your country.