43
LRG 1x-6x - Installation & Operating Manual -
819878-00
Changing the controller group
To set the controller group, please also observe the instructions in the Installation & Operating
Manual of the LRR 1-60 conductivity controller.
Note the setting instructions on page 40 and proceed as follows:
1.
Select the parameter “
GrP
”.
2.
Press and hold the rotary knob until the currently assigned controller group flashes on the display.
3.
Set the desired ID (0001 to 0004).
4.
Save your set value by pressing the rotary knob for approx. 1 second.
Changing the alarm limit value of the limiter function
Notes on setting the alarm limit value “AL.Hi”
This setting only concerns the limit value for the safety shutoff via the URS 60/URS 61
safety control unit.
The limit value indicator contacts of the LRR 1-60 conductivity controller are independent from this.
For this, also observe the information in the relevant Installation & Operating Manual.
Note the setting instructions on page 40 and proceed as follows:
1.
Select the parameter “
AL.Hi
”.
2.
Press and hold the rotary knob until the display test starts by showing “
....
”.
3.
The following numbers and decimal points run across the display from right to left:
“...., 1, 2, 3, 4, 5, 6, 7, 8, 9, ....”
4.
Check that all numbers and decimal points are displayed correctly.
The display test runs automatically until it has finished, and cannot be interrupted.
5.
The display test ends with the message “
donE
”.
6.
When the display test is complete, the last digit of the limit value flashes.
7.
Set the following required limit values:
■
■
LRG 1x-60: 0000 – 6000
■
■
LRG 16-61: 0000 - 9999
8.
Save your set value by pressing the rotary knob for approx. 1 second.
A display test performed once opens a 10 minute input window in which several safety-
relevant parameters can then also be changed without the display test repeating itself.
Bringing into service