40
LRG 1x-6x - Installation & Operating Manual -
819878-00
Bringing into service
Before bringing into service, check that all equipment is correctly connected:
■
■
Is the polarity of the CAN bus control line correct throughout?
■
■
Is a 120 Ω terminating resistor connected to the terminal devices of the CAN bus line?
Next, switch on the supply voltage.
Changing the factory settings if necessary
You will need the following tools
■
■
Slotted screwdriver, size 2.5
Select and set a parameter:
1.
+
-
Using the screwdriver, turn the rotary knob clockwise or anti-clockwise until the
desired parameter appears on the display. The set value is displayed after approx.
3 seconds.
The following parameters are shown one after the other when you turn the
rotary knob clockwise:
1234
Id.Hi
GrP
bd.rt
°C.in
°C.Pt
AL.Hi
CF
tC
CAL
FiLt
Sout
Unit
diSP
Key to parameters, see page 41.
4.
+
-
Save your set value by pressing the rotary knob for approx. 1 second.
The message “donE” is shown and the parameter appears on the display again.
If you do not enter anything for 30 seconds, the display automatically shows the
actual value again.
2.
+
-
Once you have selected a parameter, press and hold the rotary knob until the current
value of this parameter flashes on the display.
3.
+
-
Set the desired value.
Reducing/increasing the value
Each parameter has an individual, admissible value range.
By pressing the knob briefly, you can jump to the next digit. This is a more convenient
way of making large changes to values.
If you do not set a parameter within 10 seconds, the process is aborted (quit) and
the old parameter value is retained.