LRG 1x-6x - Installation & Operating Manual -
819878-00
Behaviour on the occurrence of alarms
The conductivity electrode
is immersed
The conductivity limit value is
exceeded = Alarm limit value
AL.Hi
Display:
Hi.C and 1234 alternately
LED 1
:
Alarm LED lights up red
The alarm signal and the actual measured value
are displayed alternately
The MAX alarm is active
LED 3 or 4
: lights up green
Display of the set unit
LED 2:
flashes green
The equipment is performing a self-test
LED 2:
is OFF
MAX alarm occurrence
■
■
The alarm state is transferred to the URS 60/URS 61 safety control unit via CAN data telegram.
■
■
Once the time delay has elapsed, the alarm signal triggers the safety shutoff.
■
■
The signal outputs are activated.
■
■
The URS 60/URS 61 safety control unit does not automatically lock the safety contacts.
Behaviour in the event of an error (fault code display)
The conductivity electrode
is immersed or not immersed.
There is an error.
Display:
e.g. E005
LED 1
:
Alarm LED lights up red
A fault code is permanently displayed;
fault code display see page 54
There is an active error
LED 3 or 43
: lights up green
Display of the set unit
LED 2:
flashes green
The equipment is performing a self-test
LED 2:
is OFF
Error or internal fault
■
■
The error or fault state is transferred to the URS 60/URS 61 safety control unit via
CAN data telegram.
■
■
The error causes this unit to execute the safety shutoff without a delay.
■
■
The URS 60/URS 61 safety control unit does not automatically lock the safety contacts.
Electrode alarms and errors faults cannot be acknowledged.
When the alarm or error is cancelled the display also goes blank, and the URS 60/URS 61
safety control unit closes the safety contacts again.
Start, operation, alarm and test