42
LRG 1x-6x - Installation & Operating Manual -
819878-00
Bringing into service
Notes on changing communication parameters “bd.rt, Id.Hi or GrP”
All CAN bus devices from GESTRA AG have preset communication parameters,
which enable a standard system to be brought into operation without making any changes.
Please follow the steps below if you need to make changes to communication
parameters:
■
■
Set the same baud rate for all bus participants.
■
■
To apply changed communication parameters, perform the steps below on the URB 60
visual display and operating unit or the SPECTOR
control:
■
◆
Device list - Reimport
To do this, please read the instructions in the Installation & Operating Manual of the URB 60
visual display and operating unit or the SPECTOR
control.
Changing the baud rate
Note the setting instructions on page 40 and proceed as follows:
1.
Select the parameter “
bd.rt
”.
2.
Press and hold the rotary knob until the current baud rate flashes on the display.
3.
Set the desired baud rate (50 kBit/s / 250 kBit/s).
4.
Save your set value by pressing the rotary knob for approx. 1 second.
Changing the limiter ID
To set the limiter ID, please also read the instructions in the Installation & Operating Manual
of the URS 60/URS 61 safety control unit.
Note the setting instructions on page 40 and proceed as follows:
1.
Select the parameter “
Id.Hi
”.
2.
Press and hold the rotary knob until the current limiter ID flashes on the display.
3.
Set the desired ID (0001 to 0008).
4.
Save your set value by pressing the rotary knob for approx. 1 second.