18
LRG 1x-6x - Installation & Operating Manual -
819878-00
Technical data
Model and mechanical connection
■
■
LRG 16-60, LRG 16-61, LRG 17-60
Thread G1 A, EN ISO 228-1, see Fig. 9, 10, 11
Nominal pressure rating, admissible service pressure and temperature
■
■
LRG 16-60
PN 40
32 bar (g) at 238 °C
■
■
LRG 16-61
PN 40
32 bar (g) at 238 °C
■
■
LRG 17-60
PN 63
60 bar (g) at 275 °C
Materials
■
■
Terminal box
3.2581 G AlSi12, powder-coated
■
■
Sheath
1.4301 X5 CrNi 18-10
■
■
Measuring electrodes
1.4571 X6CrNiMoTi17-12-2
■
■
Electrode insulation
PTFE
■
■
Screw-in body:
■
◆
Measuring tube, measuring screw
LRG 16-60, LRG 17-60
1.4571, X6CrNiMoTi17-12-2
■
◆
Spacer
LRG 16-60, LRG 16-61, LRG 17-60 PEEK
Deliverable installation lengths of the electrodes (cannot be shortened)
■
■
LRG 16-60, LRG 17-60
200, 300, 400, 500, 600, 800, 1000 (mm)
■
■
LRG 16-61
180, 300, 380, 500, 600, 800, 1000 (mm)
Temperature sensor
■
■
Resistance thermometer
Pt 1000
■
■
Measuring range for the temperature of the medium
0 to 280 °C
Conductivity range at 25 °C
■
■
LRG 16-60, LRG 17-60
0.5 μS/cm to 6,000 μS/cm, 0.25 - 3000 ppm *
■
◆
Preferred measuring range
up to 1000 µS/cm
■
■
LRG 16-61
50 μS/cm to 10,000 μS/cm, 25 - 5000 ppm *
■
◆
Preferred measuring range
from 500 µS/cm
* Conversion µS/cm in ppm (parts per million):
1 μS/cm = 0.5 ppm
Measuring cycle
■
■
1 second