30
Owner’s Manual for MGG450
Maintenance
Operation
If the unit is not operating and the temperature is below
60 °F (16 °C) ambient, shore power operates a 500 watt
resistive heater inside the fuel conditioning enclosure, a
6.0 kW integrated coolant pump/heater activates, and a
submersed resistive oil pan heater activates. The devices
activate independently of one another.
If the unit is operating and the temperature is below 60 °F
(16 °C) ambient, generator power operates a blower to
move air across the exterior of the exhaust manifold into
the fuel conditioning enclosure.
NOTE:
Block heater and oil pan heaters are not active
while operating.
While installed, the variable-pitch fan automatically varies
the pitch of the blades to maintain optimal airflow based
on coolant temperature and intake manifold temperature.
This operation will inherently minimize fan power
required and lower overall fuel consumption during cooler
ambient operating temperatures.
If a cooling system blockage occurs from reverse flow
operation (snow, ice, leaves, etc.), high coolant and/or
intake manifold temperatures will force the fan back into
forward flow operation. If the blockage is cleared the fan
will return to reverse flow operation once the coolant and
intake manifold temperatures return to normal. If the
blockage is not cleared with the change to forward flow
the unit may shutdown due to high coolant temperature
and/or intake manifold temperature.
Battery
Warmer
Throttle
Intake
Manifold
ENGINE
Exhaust
Manifold
Oil Sump
Turbo
Wellhead Gas
Max Inlet
Pressure-
300psi
Regulator Fuel
Strainer
Regulator
Zero
Governor
Mixer
Gas / Liquid
Separator
Coalescing
Filter
Liquid propane
Vaporizers
Fuel Safety
Valves
Fuel Safety
Valves
Crankcase
Breather Line
Breather Line
e
Resistive
Heater
Block Heater
SHORE
POWER
SYSTEM
Battery
Warmer
Throttle
Intake
Manifold
ENGINE
Exhaust
Manifold
Oil Sump
Turbo
Wellhead Gas
Max Inlet
Pressure-
300psi
Regulator Fuel
Strainer
Regulator
Zero
Governor
Mixer
Gas / Liquid
Separator
Coalescing
Filter
Liquid propane
Vaporizers
Fuel Safety
Valves
Fuel Safety
Valves
Crankcase
Breather Line
Breather Line
e
Resistive
Heater
Block Heater
SHORE
POWER
SYSTEM
Unit Not Operating
Ambient Below 60 degF
Unit Operating
Ambient Below 60 degF
Radiator
and CAC
Radiator
and CAC
AUTO
FAN
AUTO
FAN
001729
Figure 4-3. Variable Pitch Automatic Fan
Содержание MGG450
Страница 8: ...4 Owner s Manual for MGG450 Introduction and Safety This page intentionally left blank ...
Страница 48: ...44 Owner s Manual for Generator Wiring Diagrams and Service Log DC Controls Page 2 of 6 ...
Страница 49: ...Owner s Manual for Generator 45 Wiring Diagrams and Service Log DC Controls Page 3 of 6 ...
Страница 50: ...46 Owner s Manual for Generator Wiring Diagrams and Service Log DC Controls Page 4 of 6 ...
Страница 51: ...Owner s Manual for Generator 47 Wiring Diagrams and Service Log DC Controls Page 5 of 6 ...
Страница 52: ...48 Owner s Manual for Generator Wiring Diagrams and Service Log DC Controls Page 6 of 6 ...
Страница 53: ...Owner s Manual for Generator 49 Wiring Diagrams and Service Log Relay Connections ...
Страница 54: ...50 Owner s Manual for Generator Wiring Diagrams and Service Log AC Connections ...
Страница 55: ...Owner s Manual for Generator 51 Wiring Diagrams and Service Log Control Panel Layout ...
Страница 56: ...52 Owner s Manual for Generator Wiring Diagrams and Service Log Control Faceplate ...
Страница 57: ...Owner s Manual for Generator 53 Wiring Diagrams and Service Log CAN Wiring ...
Страница 58: ...54 Owner s Manual for Generator Wiring Diagrams and Service Log Receptacle ...