Owner’s Manual for MGG450
39
Troubleshooting
Alarm
Definition
BOC fgen over
Generator frequency was over the Gen >f limit for Gen f del time. Over fre-
quency protection is based on Gener protect: Gen <f and Gen f del set-
points.
BOC ReversePwr
This alarm is issued by the reverse power protection. This protection is
based on Gener protect: Reverse power and ReversePwr del setpoints.
This alarm means that either engine speed/power control does not work
properly or generator current transformers (CT’s) are connected in a
wrong way.
MP L1, L2 or L3 under
Mains L1, L2 or L3 voltage was under the Mains <V MP limit for Mains V
del time. Undervoltage protections are based on Mains protect: Mains <V
MP and Mains V del setpoints. This alarm is issued if voltage protections
are based on phase to neutral voltages. It means that Basic settings: Fix-
VoltProtSel is set to PHASE-NEUTRAL.
MP L1, L2 or L3 over
Mains L1, L2 or L3 voltage was over the Mains >V MP limit for Mains V del
time. Overvoltage protections are based on Mains protect: Mains >V MP
and Mains V del setpoints. This alarm is issued if voltage protections are
based on phase to neutral voltages. It means that Basic settings: FixVolt-
ProtSel is set to PHASE-NEUTRAL.
MP L12, L23 or L31 under
Mains L12, L23 or L31 voltage was under the Mains <V MP limit for Mains
V del time. Undervoltage protections are based on Mains protect: Mains
<V MP and Mains V del setpoints. This alarm is issued if voltage protec-
tions are based on phase to phase voltages. It means that Basic settings:
FixVoltProtSel is set to PHASE-PHASE.
MP L12, L23 or L31 over
Mains L12, L23 or L31 voltage was over the Mains >V MP limit for Mains V
del time. Overvoltage protections are based on Mains protect: Mains >V
MP and Mains V del setpoints. This alarm is issued if voltage protections
are based on phase to phase voltages. It means that Basic settings: Fix-
VoltProtSel is set to PHASE-PHASE.
Mains Avg x >V
If the value of 10 min. average mains voltage of any phase (Mains Avg V1,
Mains Avg V2, Mains Avg V3) exceed value given by setpoint Mains Avg
>V MP (Mains protect group), the MCB is opened and message Mains
Avg x >V appears in alarm list and history record. BO Common MP is acti-
vated (x indicates number of phase).
MP fmns under
Mains frequency was under the Mains <f limit for Mains f del time. Under
frequency protection is based on Mains protect: Mains <f and Mains f del
setpoints.
MP fmns over
Mains frequency was over the Mains >f limit for Mains f del time. Over fre-
quency protection is based on Mains protect: Mains >f and Mains f del set-
points.
Bus meas error
Bus measurement error is issued if bus voltage is out of limits. For details,
refer to description of the Gener protect: BusMeasError setpoint in IGS-
NT-x.y-Reference Guide.
OfL StartBlck
This alarm indicates wrong setpoints setting that disables engine start or
load takeover. Incorrect combination of ProcessControl: Island enable;
ParallelEnable; Synchro enable; MF start enable setpoints setting is the
reason why this alarm is issued. Refer to AUT mode section of the OFF-
MAN-AUT mode chapter in IGS-NT-x.y-Reference Guide for SPTM, SPI or
COMBI application.
StartBlck
This alarm indicates wrong setpoints setting that disables start of genera-
tors. Incorrect combination of ProcessControl: Island enable; ParallelEn-
able; Synchro enable; MF start enablesetpoints setting is the reason why
this alarm is issued. Refer to OFF-MAN-AUT mode chapter in IM-NT-
MCB-MGCB Reference Guide.
Содержание MGG450
Страница 8: ...4 Owner s Manual for MGG450 Introduction and Safety This page intentionally left blank ...
Страница 48: ...44 Owner s Manual for Generator Wiring Diagrams and Service Log DC Controls Page 2 of 6 ...
Страница 49: ...Owner s Manual for Generator 45 Wiring Diagrams and Service Log DC Controls Page 3 of 6 ...
Страница 50: ...46 Owner s Manual for Generator Wiring Diagrams and Service Log DC Controls Page 4 of 6 ...
Страница 51: ...Owner s Manual for Generator 47 Wiring Diagrams and Service Log DC Controls Page 5 of 6 ...
Страница 52: ...48 Owner s Manual for Generator Wiring Diagrams and Service Log DC Controls Page 6 of 6 ...
Страница 53: ...Owner s Manual for Generator 49 Wiring Diagrams and Service Log Relay Connections ...
Страница 54: ...50 Owner s Manual for Generator Wiring Diagrams and Service Log AC Connections ...
Страница 55: ...Owner s Manual for Generator 51 Wiring Diagrams and Service Log Control Panel Layout ...
Страница 56: ...52 Owner s Manual for Generator Wiring Diagrams and Service Log Control Faceplate ...
Страница 57: ...Owner s Manual for Generator 53 Wiring Diagrams and Service Log CAN Wiring ...
Страница 58: ...54 Owner s Manual for Generator Wiring Diagrams and Service Log Receptacle ...