Owner’s Manual for MGG450
17
Operation
5.
Push the up arrow to return to the home metering
screen.
6.
Push the soft key just below the mode label, select
MANUAL mode and press ENTER.
7.
Push START. If the engine fails to start, see
8.
If the fuel content is unknown and the engine did
not start, select IBTU ON and turn off hBTU ON.
LP Liquid Only Operation
If unit is to be operated only on LP liquid:
1.
Check for leaks in the LP liquid line connection
2.
Push the down arrow on the controller until it dis-
plays the fuel selection screen
3.
Push the soft key just below the mode label, select
MANUAL mode, then select LP Liquid and press
Enter.
4.
Push START. If engine fails to start, see
Gaseous and LP Liquid (Automatic mode)
Operation
If there is sufficient pressure in the gaseous fuel line, the
unit can be started directly on well gas (non-commercial):
1.
Open the manual ball fuel valve located just inside
the frame.
2.
Check for any leaks in the gas line.
3.
Push the down arrow on the controller until it
displays the fuel selection screen.
4.
Push the soft key for both the gaseous fuel
selection and LP liquid operation. The AUTO mode
indicator should illuminate.
NOTE:
Only one gaseous fuel selection can be selected
at a time. Multiple selections will default to the fuel
selection with higher energy content.
5.
Push the up arrow to return to the home metering
screen.
6.
Push the soft key just below the mode label, select
MANUAL mode and press ENTER.
7.
Push START. If engine fails to start, see
50 Hz Operation
The MGG450 is capable of operating at either 60 Hz or
50 Hz. This is achievable by changing the basic settings
of the generator, the AVR configuration and the ignition
mode. The basic settings and ignition mode can be
changed by pressing the “50 Hz ON” soft button at the
bottom of the screen (
, Item A).
shows the factory values of the settings depending on
whether the button is active or not.
A
006353
Figure 3-1. 50 Hz Operation
Table 3-3. Factory Settings
Setpoint
60 Hz
50 Hz
Nomin power
365 kW
295 kW
Nomin current
575 A
550 A
GenNomV
277 V
231 V
GenNomVph-ph
480 V
400 V
BusNomV
277 V
231 V
BusNomVph-ph
480 V
400 V
Nominal freq
60 Hz
50 Hz
Nominal rpm
1,800 rpm
1,500 rpm
1.
Shut the unit down.
2.
Unlock the button (“50 Hz ON”) with a service
passcode or higher to activate.
NOTE:
If the unit is running when the button is pressed it
will open the circuit breaker and initiate shutdown.
The controller will always give a warning as a reminder
that the AVR (Automatic Voltage Regulator) needs to be
configured. This should be cleared once the AVR has
been configured.
The AVR used by the alternator must be reprogrammed
for 50 Hz operation. The AVR is equipped with a type B
USB female port and can be connected using the
EasyReg software provided by Leroy Somer. Once
connected, a 50 Hz file for the MGG450 must be
uploaded to the AVR.
Operation Checks
With engine running, check for the following:
•
Fuel leaks. If a leak is detected, stop engine
immediately by pushing STOP on controller. Repair
leak before proceeding.
Содержание MGG450
Страница 8: ...4 Owner s Manual for MGG450 Introduction and Safety This page intentionally left blank ...
Страница 48: ...44 Owner s Manual for Generator Wiring Diagrams and Service Log DC Controls Page 2 of 6 ...
Страница 49: ...Owner s Manual for Generator 45 Wiring Diagrams and Service Log DC Controls Page 3 of 6 ...
Страница 50: ...46 Owner s Manual for Generator Wiring Diagrams and Service Log DC Controls Page 4 of 6 ...
Страница 51: ...Owner s Manual for Generator 47 Wiring Diagrams and Service Log DC Controls Page 5 of 6 ...
Страница 52: ...48 Owner s Manual for Generator Wiring Diagrams and Service Log DC Controls Page 6 of 6 ...
Страница 53: ...Owner s Manual for Generator 49 Wiring Diagrams and Service Log Relay Connections ...
Страница 54: ...50 Owner s Manual for Generator Wiring Diagrams and Service Log AC Connections ...
Страница 55: ...Owner s Manual for Generator 51 Wiring Diagrams and Service Log Control Panel Layout ...
Страница 56: ...52 Owner s Manual for Generator Wiring Diagrams and Service Log Control Faceplate ...
Страница 57: ...Owner s Manual for Generator 53 Wiring Diagrams and Service Log CAN Wiring ...
Страница 58: ...54 Owner s Manual for Generator Wiring Diagrams and Service Log Receptacle ...