In-
dex
Sub-
In-
dex
Access
rights
Index name
Parameter
Function
Factory
settings
Setting options
0xB0
1
R/W
Control parameters
P amplification
P component –
positioner
200
1 … 200
(0.1 … 20.0)
2
R/W
D amplification
D component –
positioner
10
1 … 200
(0.1 … 20.0)
3
R/W
Derivative time
Delay constant
0
0 to 100
(0 to 100 s)
4
R/W
Dead band
Permissible sys-
tem deviation
10
1 … 250
(0.1 … 25.0 %)
0xB2
1
R/W
Open / close tight
Open tight
Sealing function
valve position
OPEN
995
800 … 1000
(80.0 … 100.0 %)
2
R/W
Close tight
Sealing function
valve position
CLOSED
5
0 … 200
(0 … 20.0 %)
0xB4
1
R/W
Split range
Split start
Set set value start
0
0 to Split End –
100
(0.0 to Split End –
10.0%)
2
R/W
Split end
Set set value end
1000
Split Start + 100 to
1000
(Split Start + 10.0%
to 100.0%)
0xB6
1
R/W
Stroke limiter
Max pos
Stroke limiter
valve position
OPEN
1000
Min Pos to 1000
(Min Pos to
100.0%)
2
R/W
Min pos
Stroke limiter
valve position
CLOSED
0
0 to Max Pos
(0.0% to Max Pos)
0xB8
1
R/W
Set value (W) input
Direction
Set value direction
set value input
0
0
→
Rise (rising)
1
→
Fall (falling)
2
R/W
Type
Determine signal
input
1
0
→
0 to 20 mA
1
→
4 to 20 mA
2
→
0 to 10 V
3
R/W
I min
Determine min-
imum current in-
put
35
0 to 40
(0 to 4.0 mA)
4
R/W
I max
Determine max-
imum current in-
put
205
200 to 220
(20.0 to 22.0 mA)
5
R/W
U max
Determine max-
imum current in-
put
103
100 to 110
(10.0 to 11.0 V)
0xBA
1
R/W
Analog output
Direction
Set value direction
set value output
0
0
→
Rise (rising)
1
→
Fall (falling)
2
R/W
Type
Determine signal
output
1
0
→
0 to 20 mA
1
→
4 to 20 mA
2
→
0 to 10 V
3
R/W
Min.
Determine min-
imum signal out-
put
0
0 to Max
(0.0% to Max)
4
R/W
Max
Determine max-
imum signal out-
put
1000
Min to 1000
(Min to 100%)
www.gemu-group.com
26 / 53
GEMÜ R563
12 Specific data IO-Link (pin 6)