12.4.35 Set value (W) input
The function of the analog input can be set with the
Set value (W) input
parameter.
In-
dex
Sub
-
In-
dex
Off-
set
Access
Rights
Lengt
h
Index name
Parameter
Type
Default
Values
0xB8
1
0
R/W
1 bit
Set value (W) in-
put
Direction
uint:1
0
0
1
2
8
R/W
2 bits
Type
uint:2
1
0
1
2
3
16
R/W
8 bits
I min
uint:8
35
0 to 40
(0 to 4.0 mA)
4
24
R/W
8 bits
I max
uint:8
205
200 to 220
(20.0 to 22.0 mA)
5
32
R/W
8 bits
U max
uint:8
103
100 to 110
(10.0 to 11.0 V)
Description of parameter values
Index name
Parameter
Values
Description
Set value (W) input
Direction
0
1
Specify direction of the set value input.
0 = Rise (rising)
1 = Fall (falling)
Type
0
1
2
Determine signal input.
0 = 0 to 20 mA
1 = 4 to 20 mA
2 = 0 to 10 V
I min
0 to 40
(0 to 4.0 mA)
Determine minimum value of the current input. If the set
value is not reached, the message "Set value too small" is
issued.
I max
200 to 220
(20.0 to 22.0
mA)
Determine maximum value of the current input. If the set
value is exceeded, the message "Set value too high" is
issued.
U max
100 to 110
(10.0 to 11.0 V)
Determine maximum value of the voltage input. If the set
value is exceeded, the message "Set value too high" is
issued.
GEMÜ R563
www.gemu-group.com
43 / 53
12 Specific data IO-Link (pin 6)