12.4.24 Basic settings
The different settings are summarized with the
Basic settings
parameter.
In-
dex
Sub
-
In-
dex
Off-
set
Access
Rights
Lengt
h
Index name
Parameter
Type
Default
Values
0x50
1
0
R/W
1 bit
Basic settings
Inversion of
LED colours
Boolean
0
0
1
2
1
R/W
1 bit
On site
initialization
Boolean
0
0
1
3
2
R/W
1 bit
Operating mode
Boolean
0
0
1
4
3
R/W
1 bit
IO-Link process
data
Boolean
0
0
1
Description of parameter values
Index name
Parameter
Values
Description
Basic settings
Inversion of LED col-
ours
0
(Standard)
LEDs Close = green and Open = yellow (
not
inversed).
1
(Inversed)
LEDs Close = yellow and Open = green (inversed).
On site initialization
0
(Enabled)
On-site initialization (see “Initialization“,
page 46) activated.
1
(Disabled)
On-site initialization (see “Initialization“,
page 46) deactivated.
Operating mode
0
Operating mode for positioner activated.
1
Operating mode for OPEN/CLOSE control activated.
IO-Link process data
0
(Disabled)
Use of IO-Link process data (see “Process data“,
page 22) is deactivated.
1
(Enabled)
Use of IO-Link process data (see “Process data“,
page 22) is activated.
GEMÜ R563
www.gemu-group.com
37 / 53
12 Specific data IO-Link (pin 6)