12.4.23 Error action
The safety position can be set with the
Error action
parameter.
The safety position is approached when an error occurs, if the supply voltage is too low within the range of 17.8 V to 21.1 V or
in case of the corresponding signal present at Safe/On.
NOTICE
▶
Except the Temperature Over-Run error device, exceeding the permissible motor temperature.If the permissible temperat-
ure is exceeded, the motor is switched off to prevent damage.
In-
dex
Sub
-
In-
dex
Off-
set
Access
Rights
Lengt
h
Index name
Parameter
Type
Default
Values
0x4F
1
0
R/W
2 bits
Error action
Error action
uint:8
2
0
1
2
2
0
R/W
10
bits
Error time
uint:16
1 (0.1s)
1 … 1000
(0.1s to 100s)
Description of parameter values
Index name
Parameter
Values
Description
Error action
Error action
0
(Hold)
Actuator remains in the current position in case of an
error.
1
(Open)
Actuator moves to the OPEN position in case of an
error.
2
(Close)
Actuator moves to the CLOSED position in case of
an error.
Error time
1 … 1000
Determine delay time between error detection and error
message.
www.gemu-group.com
36 / 53
GEMÜ R563
12 Specific data IO-Link (pin 6)