In-
dex
Sub-
In-
dex
Access
rights
Index name
Parameter
Function
Factory
settings
Setting options
0x18
0
R/W
Application specific
tag
Text with 32 char-
acters can be
entered
„****************“
0x19
0
R/W
Function tag
Text with 32 char-
acters can be
entered
„****************“
0x1A
0
R/W
Location tag
Text with 32 char-
acters can be
entered
„****************“
0x24
0
RO
Device status
(Simple) device
status
0
→
Operating
properly
2
→
Out of
specification
4
→
Failure
0x25
0
RO
Device status
Detailed device
status
0x4B
1
R/W
Function digital in-
puts
Input 1
Configure digital
input 1
4
0
→
Off
1
→
Open
2
→
Close
3
→
Safe/On
4
→
Init
2
R/W
Input 2
Configure digital
input 2
0
0
→
Off
1
→
Open
2
→
Close
3
→
Safe/On
4
→
Init
0x4C
1
R/W
Function digital in-/
output 1
In- / output 1
Configure digital
inputs/outputs
2
0
→
Output open
1
→
Output close
2
→
Output error
3
→
Output Error &
warning
4
→
Input init
2
R/W
Type in- / output 1
Configure type of
digital inputs/out-
puts
0
0
→
Push-pull
1
→
NPN
2
→
PNP
0x4D
0
R/W
Function digital
output 2
Configure digital
output
1
0
→
Output open
1
→
Output close
2
→
Output error
3
→
Output error &
warning
0x4E
1
R/W
Logic digital in-
puts / outputs
Input 1
Configure logical
digital input 1
0
0
→
Active high
1
→
Active low
2
R/W
Input 2
Configure logical
digital input 2
0
0
→
Active high
1
→
Active low
3
R/W
Input / output 1
Configure logical
digital input/out-
put
0
0
→
Active high
1
→
Active low
4
R/W
Output 2
Configure logical
digital output
0
0
→
Active high
1
→
Active low
0x4F
1
R/W
Error action
Error action
Set safety position
2
0
→
Hold
1
→
Open
2
→
Close
www.gemu-group.com
24 / 53
GEMÜ R563
12 Specific data IO-Link (pin 6)