—————— TPD32-EV ——————
226
6.13.3 Speed control
ADD SPEED FUNCT
Speed control
[101]
Spd thr [FF]
[102]
Spd threshold - [FF]
[103]
Threshold delay [ms]
[104]
Set error [FF]
[105]
Set delay [ms]
Two speed control messages are provided:
-
when a particular, adjustable speed is not exceeded.
-
when the speed corresponds to the set rference value
Parameter description
No.
Value
Standard
Configuration
min
max
Factory
American
Factory
Standard
Spd thr [FF]
101
1
32767
1000
1000
-
Spd threshold - [FF]
102
1
32767
1000
1000
-
Threshold delay [ms]
103
0
65535
100
100
-
Spd threshold
Speed exceeded (0)
Speed not exceeded (1)
393
0
1
Digital output 3 *
Set error [FF]
104
1
32767
100
100
-
Set delay [ms]
105
1
65535
100
100
-
Set speed
Speed not ref. val. (0)
Speed = ref. val. (1)
394
0
1
-
* This function can be assigned to a programmable digital output.
Spd thr
Switch point for the “Speed not exceeded” for clockwise rotation of the drive in the
units defined by the Factor function.
Spd threshold -
Switch point for the “Speed not exceeded” for counter-clockwise rotation of the drive
in the units defined by the Factor function.
Threshold delay
Setting of a delay time in milliseconds which is active when the speed is lowered within
the limits of the set threshold.
Spd threshold
Message “Set speed not exceeded” (via a programmable digital input)
High Speed not exceeded
Low Speed exceeded
Set error
Defines a tolerance band around the speed reference in the units specified by the Factor function.
Set delay
Setting of a delay time in milliseconds which is active when the speed is lowered within
the limits of the set threshold.
Set speed
Message “The speed corresponds to the reference value” (via a programmable digital output)
High Speed corresponds to the reference value
Low Speed does not corresponds to the reference value
The message “The speed corresponds to the reference value” refers to the total reference value in front of the
Speed ref
speed regulator and to the
Ramp Ref
ramp reference when the ramp is selected.
When the references are lower than ± 1 %, the signal is always low!
Содержание TPD32-EV-...-2B
Страница 1: ... Instruction manual Industrial Application DC drives TPD32 EV ...
Страница 62: ... TPD32 EV 62 10 mm 0 4 150 mm 6 150 mm 6 150 mm 6 10 mm 0 4 10 mm 0 4 50 mm 2 Figure 3 3 2 Mounting Clearance ...
Страница 372: ... TPD32 EV 372 9 BLOCK DIAGRAM 9 1 CONTROL BLOCK DIAGRAMS ...
Страница 373: ... Instruction manual 373 ...
Страница 374: ... TPD32 EV 374 ...
Страница 375: ... Instruction manual 375 ...
Страница 376: ... TPD32 EV 376 ...
Страница 377: ... Instruction manual 377 ...
Страница 378: ... TPD32 EV 378 ...
Страница 379: ... Instruction manual 379 ...
Страница 380: ... TPD32 EV 380 ...
Страница 381: ... Instruction manual 381 ...
Страница 382: ... TPD32 EV 382 ...
Страница 383: ... Instruction manual 383 ...
Страница 384: ... TPD32 EV 384 ...
Страница 385: ... Instruction manual 385 ...
Страница 386: ... TPD32 EV 386 ...
Страница 387: ... Instruction manual 387 ...
Страница 388: ... TPD32 EV 388 ...
Страница 389: ... Instruction manual 389 ...
Страница 390: ... TPD32 EV 390 ...
Страница 391: ... Instruction manual 391 ...
Страница 392: ... TPD32 EV 392 ...
Страница 393: ... Instruction manual 393 ...
Страница 394: ... TPD32 EV 394 ...
Страница 395: ... Instruction manual 395 ...
Страница 396: ... TPD32 EV 396 ...
Страница 397: ... Instruction manual 397 ...
Страница 398: ... TPD32 EV 398 ...
Страница 399: ... Instruction manual 399 ...
Страница 400: ... TPD32 EV 400 ...
Страница 401: ... Instruction manual 401 ...
Страница 402: ... TPD32 EV 402 ...
Страница 501: ... Instruction manual 501 APPENDIX 3 ACCESSORIES A3 1 EAM Adapter Kit EAM1579 EAM1580 ...
Страница 503: ......